Carrier appendix Electrical Data 38AUQ*07-12 Hz Units

Page 14

 

Table 8 — Electrical Data — 38AUQ*07-12

60 Hz Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

FACTORY-

NOMINAL

VOLTAGE

COMPRESSOR

FAN MOTORS

POWER

VOLTAGE

RANGE

SUPPLY

SIZE

INSTALLED

 

 

 

 

38AUQ

OPTION

V-Ph-Hz

MIN

MAX

RLA

LRA

FLA (ea)

QTY

MCA

MOCP

 

 

 

NONE OR DISCONNECT

208/230-3-60

187

253

19.0

123

1.5

2

26.8

45

 

 

 

 

 

CONVENIENCE OUTLET

31.6

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*07

NONE OR DISCONNECT

460-3-60

414

506

9.7

62

0.9

2

13.9

20

 

 

 

CONVENIENCE OUTLET

16.1

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

575-3-60

518

633

7.4

50

0.6

2

10.5

15

 

 

 

 

 

CONVENIENCE OUTLET

12.2

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

208/230-3-60

187

253

25.0

164

1.5

2

34.3

50

 

 

 

 

 

CONVENIENCE OUTLET

39.1

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*08

NONE OR DISCONNECT

460-3-60

414

506

12.2

100

0.9

2

17.1

25

 

 

 

CONVENIENCE OUTLET

19.3

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

575-3-60

518

633

9.0

78

0.6

2

12.5

20

 

 

 

 

 

CONVENIENCE OUTLET

14.2

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

208/230-3-60

187

253

30.1

225

1.5

2

40.6

60

 

 

 

 

 

CONVENIENCE OUTLET

45.4

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*12

NONE OR DISCONNECT

460-3-60

414

506

16.7

114

0.8

2

22.5

30

 

 

 

CONVENIENCE OUTLET

24.7

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

575-3-60

518

633

12.2

80

0.6

2

16.5

25

 

 

 

 

 

CONVENIENCE OUTLET

18.2

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA

Full Load Amps

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP —

Maximum Overcurrent

 

 

Protection

NEC

National Electrical Code

RLA

Rated Load Amps

Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed limits.

NOTES:

1.The MCA and MOCP values are calculated in accordance with the NEC, Article 440.

2.Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL), Standard 1995.

3.The 575-v units are UL, Canada-listed only.

4.Convenience outlet is available as a factory-installed option and is 115-v, 1 ph, 60 Hz.

5.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

max voltage deviation from average voltage

% Voltage Imbalance = 100 x

 

 

average voltage

Example: Supply voltage is 208/230-3-60

AB = 224 v

 

 

 

BC = 231 v

 

 

 

AC = 226 v

 

 

 

(224 + 231 + 226)

681

Average Voltage =

 

 

=

 

3

3

=227

Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v

(BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v.

Determine percent of voltage imbalance.

 

4

% Voltage Imbalance

= 100 x

 

 

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

14

Image 14
Contents Contents Safety ConsiderationsInstallation Installation GuidelineReplacement /Retrofit R22 to Puron 38AUQ*07-12 Unit Dimensions Shipping Charge lb Pressurestat Settings psig High CutoutOperating Charge, Typical lb† Qty...TypeNominal Capacity kW Operating Weight kg Aluminum-Fin CoilsPressurestat Settings kPa High Cutout Operating Charge, Typical kg†Type of Coil Service OptionsModel Type Refrigerant OptionsInstallation Puron-duty Filter Driers 38AUQ*07-12 Piping Recommendations Single-Circuit UnitMaximum Vertical Separation Refrigerant Specialties Part Numbers Insulation for Vapor Line Exposed To Outdoor ConditionsComplete Electrical Connections Install AccessoriesField Power Supply Convenience Outlets Units Without Factory-Installed DisconnectUnits with Factory-Installed Disconnect All unitsInstalling Weatherproof Cover Convenience Outlet LocationField Control Wiring ThermostatElectrical Data 38AUQ*07-12 Hz Units PRE-START-UP START-UPStart Unit Advanced Scroll Temperature Protection AstpAdjust Refrigerant Charge Final Checks38AUQ*07 Charging Chart 38AUQ Wiring Diagram 208/230-3-60 shown Operating Sequence Base Unit ControlsQuarterly Inspection 30 days after initial start Routine System MaintenanceService Refrigeration SystemLiquid Line Filter Drier Field Refrigerant Access PortsRefrigerant System Pressure Access Ports Outdoor Coil Metering DevicesCrankcase Heater Heat Pump ControlsCompressor Protection Commercial Defrost ControlReversing valve control Dip Switch PositionDefrost Compressor controlDefrost Speedup Functions Indoor Fan Off DelayDefrost Thermostats Fans Service Valves 38AUQ*08 Exterior 38AUQ*12 Exterior Comfort Alert Diagnostic Module InputLED Status Codes LockoutRoutine Cleaning of Indoor Coil Surfaces Outdoor Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse LubricationTorque Values Service PartsFastener Torque Values Troubleshooting Appendix a Appendix BAppendix C Catalog No 38AUQ-01SIPreliminary Information CUT Along Dotted Linecut Along Dotted Line

38AUQ specifications

The Carrier 38AUQ is a versatile and efficient air conditioning unit designed to meet a variety of residential and light commercial cooling needs. Known for its advanced technology and robust performance, the 38AUQ model showcases Carrier's commitment to sustainability and energy efficiency.

One of the standout features of the Carrier 38AUQ is its use of variable-speed inverter technology. This allows the unit to adjust its cooling output in response to the temperature demands of the environment. By operating at multiple speed levels, it minimizes energy consumption and maximizes comfort, ensuring a consistent, quiet cooling experience.

The 38AUQ is equipped with a high-efficiency compressor, which helps to further enhance its energy performance. This component plays a critical role in ensuring that the unit operates smoothly, reducing both electricity bills and the environmental impact. Efficiency ratings often exceed industry standards, making the 38AUQ a suitable choice for those looking to reduce their carbon footprint while enjoying a comfortable indoor climate.

In terms of design, the Carrier 38AUQ boasts a compact and sleek profile that allows for easy installation in a variety of settings. Its durable construction is built to withstand harsh weather conditions, ensuring longevity and reliability. Additionally, an advanced air purification system is integrated, featuring filters that capture airborne particles, improving indoor air quality.

The unit also offers a range of smart features, including compatibility with smart home systems. Users can remotely control their air conditioning via smartphone apps, allowing for customizable settings and energy management from anywhere. This connectivity aligns with modern living preferences, enhancing convenience and control.

Furthermore, the Carrier 38AUQ is designed with noise reduction in mind. The advanced sound-absorbing materials and quiet operation of its fan and compressor make it one of the quieter air conditioning options on the market. This is particularly beneficial for residential applications, where noise can be a significant concern.

Overall, the Carrier 38AUQ combines cutting-edge technology, energy efficiency, and user-friendly features, making it a top choice for both homeowners and small business operators seeking reliable cooling solutions. Its commitment to performance and efficiency makes it a standout model in the Carrier air conditioning lineup.