MAKE PIPING CONNECTIONS — Piping connections at the 38AUQ unit are ball valves with stub tube extensions. Do not open the unit service valves until all interconnecting tube brazing as been completed.

The stub tube connections include ¼-in SAE service fittings with Schrader valve cores (see Fig. 7). Before making any brazed connections to the unit service valves, remove both Schrader valve caps and cores and save for re-installation. Con- nect a source for nitrogen to one of these service fittings during tube brazing to prevent the formation of copper oxides inside the tubes at brazed joints.

 

Field Service

Factory

Access Port

(Schrader core)

High-Flow

 

Access Port

 

Service Valve

 

with Stem Cap

Sweat

 

Connection

Fig. 7 — Typical Piping Connection Assembly

When connecting the field tubing to the 38AUQ service valves, wrap the valves in wet rags to prevent overheating

Pressure-test all joints from outdoor unit connections over to the indoor coil, using nitrogen as pressure and with soap-and- bubbles.

When pressure-testing is completed, remove the nitrogen source at the outdoor unit service valves and re-install the two Schrader valve cores. Torque the cores to 2-3 in-lbs (23-34 N-cm).

Where vapor line is exposed to outdoor air, line must be insulated. See Table 7 for insulation requirements.

EVACUATION/DEHYDRATION — Evacuate and dehydrate the connected refrigeration system(s) (excluding the 38AUQ unit) to 500 microns using a two-stage vacuum pump attached to the service ports outside the 38AUQ service valves, follow- ing description in GTAC II, Module 4, System Dehydration.

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personal injury, death and/or equipment damage.

Puron® (R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.

IMPORTANT: Charge in Cooling mode only!

PRELIMINARY CHARGE — Before starting the unit, charge R-410A liquid refrigerant into the high side of each 38AUQ circuit through the liquid service valve(s). The amount of refrigerant added must be at least 80% of the operating charge listed in Table 2 for LINEAR line length LESS the factory charge quantity (if factory shipping charge has not been removed). See the following example.

Allow high and low side pressures to equalize. If pressures do not equalize readily, charge R-410A vapor (using special service manifold with expansion device) into the suction line service port for the low side of system to assure charge in the evaporator. Refer to GTAC II, Module 5, Charging, Recover, Recycling, and Reclamation for liquid charging procedures.

Example:

38AUQ*08

60-ft (18.3 m) linear line length Equivalent line length 90-ft (27.4 m) Liquid Lift: 20-ft (6.1 m)

Select line sizes from Table 2 (38AUQ): Liquid 1/2 in

Suction 1-1/8in.

Charge 23.0 lbs (at 75-ft linear length)

80% of Operating Charge:

0.80 x 23.0 = 17.6 lbs

Factory Shipping Charge: 12 lbs

Field-charge quantity: 17.6 lbs –12.0 lbs = 5.6 lbs

For linear line lengths longer than 100 ft (30.5 m), contact your local Carrier representative for system charge value.

Step 6 — Install Accessories

Accessories requiring modifications to unit wiring should be completed now. These accessories may include Winter Start controls, Low Ambient controls, phase monitor, Compressor LOCout. Refer to the instructions shipped with the accessory.

Step 7 — Complete Electrical Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/ NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.

NOTE: Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63°F (33°C) rise.

Field Power Supply —

If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet's transformer pri- mary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads.

All units except 208/230-v units are factory wired for the volt- age shown on the nameplate. If the 208/230-v unit is to be con- nected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4-in. female spade connector from the 230-v connection and moving it to the 208-v 1/4-in. male terminal on the primary side of the trans- former. Refer to unit label diagram for additional information.

10

Image 10
Contents Contents Safety ConsiderationsReplacement /Retrofit R22 to Puron Installation GuidelineInstallation 38AUQ*07-12 Unit Dimensions Shipping Charge lb Pressurestat Settings psig High CutoutOperating Charge, Typical lb† Qty...TypeNominal Capacity kW Operating Weight kg Aluminum-Fin CoilsPressurestat Settings kPa High Cutout Operating Charge, Typical kg†Type of Coil Service OptionsModel Type Refrigerant OptionsInstallation Maximum Vertical Separation 38AUQ*07-12 Piping Recommendations Single-Circuit UnitPuron-duty Filter Driers Refrigerant Specialties Part Numbers Insulation for Vapor Line Exposed To Outdoor ConditionsField Power Supply Install AccessoriesComplete Electrical Connections Convenience Outlets Units Without Factory-Installed DisconnectUnits with Factory-Installed Disconnect All unitsInstalling Weatherproof Cover Convenience Outlet LocationField Control Wiring ThermostatElectrical Data 38AUQ*07-12 Hz Units PRE-START-UP START-UPStart Unit Advanced Scroll Temperature Protection AstpAdjust Refrigerant Charge Final Checks38AUQ*07 Charging Chart 38AUQ Wiring Diagram 208/230-3-60 shown Operating Sequence Base Unit ControlsQuarterly Inspection 30 days after initial start Routine System MaintenanceService Refrigeration SystemLiquid Line Filter Drier Field Refrigerant Access PortsRefrigerant System Pressure Access Ports Outdoor Coil Metering DevicesCrankcase Heater Heat Pump ControlsCompressor Protection Commercial Defrost ControlReversing valve control Dip Switch PositionDefrost Compressor controlDefrost Thermostats Indoor Fan Off DelayDefrost Speedup Functions Fans Service Valves 38AUQ*08 Exterior 38AUQ*12 Exterior Comfort Alert Diagnostic Module InputLED Status Codes LockoutRoutine Cleaning of Indoor Coil Surfaces Outdoor Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse LubricationFastener Torque Values Service PartsTorque Values Troubleshooting Appendix a Appendix BAppendix C Catalog No 38AUQ-01SIPreliminary Information CUT Along Dotted Linecut Along Dotted Line

38AUQ specifications

The Carrier 38AUQ is a versatile and efficient air conditioning unit designed to meet a variety of residential and light commercial cooling needs. Known for its advanced technology and robust performance, the 38AUQ model showcases Carrier's commitment to sustainability and energy efficiency.

One of the standout features of the Carrier 38AUQ is its use of variable-speed inverter technology. This allows the unit to adjust its cooling output in response to the temperature demands of the environment. By operating at multiple speed levels, it minimizes energy consumption and maximizes comfort, ensuring a consistent, quiet cooling experience.

The 38AUQ is equipped with a high-efficiency compressor, which helps to further enhance its energy performance. This component plays a critical role in ensuring that the unit operates smoothly, reducing both electricity bills and the environmental impact. Efficiency ratings often exceed industry standards, making the 38AUQ a suitable choice for those looking to reduce their carbon footprint while enjoying a comfortable indoor climate.

In terms of design, the Carrier 38AUQ boasts a compact and sleek profile that allows for easy installation in a variety of settings. Its durable construction is built to withstand harsh weather conditions, ensuring longevity and reliability. Additionally, an advanced air purification system is integrated, featuring filters that capture airborne particles, improving indoor air quality.

The unit also offers a range of smart features, including compatibility with smart home systems. Users can remotely control their air conditioning via smartphone apps, allowing for customizable settings and energy management from anywhere. This connectivity aligns with modern living preferences, enhancing convenience and control.

Furthermore, the Carrier 38AUQ is designed with noise reduction in mind. The advanced sound-absorbing materials and quiet operation of its fan and compressor make it one of the quieter air conditioning options on the market. This is particularly beneficial for residential applications, where noise can be a significant concern.

Overall, the Carrier 38AUQ combines cutting-edge technology, energy efficiency, and user-friendly features, making it a top choice for both homeowners and small business operators seeking reliable cooling solutions. Its commitment to performance and efficiency makes it a standout model in the Carrier air conditioning lineup.