Installation
Figure 11: Units on the same level
1 |
2 |
Limitations: The distance between the two units must not exceed 60 m in reality or the equivalent of 90 m taking into account pressure drops.The height of the liquid line in relation to the unit base must be less than 5 m. It is recommended to place a trap on the discharge line at the oil separator outlet, if this discharge line is horizontal for a distance greater than 5 m, at a height greater than the connection to the oil separators.
Figure 12: RTCA (or other manufacturer's condenser) above the RTUB
4
Limitations: The distance between the two units must not exceed 60 m in reality or the equivalent of 90 m taking into account pressure drops. Each 30 m level difference causes a 2% efficiency loss.
17 |