Operation
motor rotation requires confirmation of the electrical phase sequence of the power supply.The motor is internally connected for clockwise rotation with the incoming power supply phased
When rotation is clockwise, the phase sequence is usually called "ABC;" when counterclockwise, "CBA."This direction may be reversed outside the alternator by interchanging any two of the line wires. It is this possible interchange of wiring that makes a phase sequence indicator necessary if the operator is to quickly determine the phase rotation of the motor.
1.Press the Stop key on the UCM- CLD.
2.Open the electrical disconnect or circuit protection switch that provides line power to the line- power terminal block(s) in the starter panel (or to the unit- mounted disconnect).
3.Connect the
Phase Sequence LeadTerminal
Black (Phase A) L1
Red (Phase B) L2
Yellow (Phase C) L3
4.Turn power on by closing the unit
5.Read the phase sequence on the indicator.The "ABC" LED on the face of the phase indicator will glow if the phase is "ABC."
WARNING
To prevent injury or death due to electrocution, take extreme care when performing service procedures with electrical power energized.
6.If the "CBA" indicator glows instead, open the unit
Do not interchange any load leads that are from the unit contactors or the motor terminals. Doing so may damage the equipment.
7.Reopen the unit disconnect and disconnect the
Start-up Procedures
Daily Unit
•Press the Stop key on the
•If necessary, adjust the setpoint values in the
•Close the fused disconnect switch for the chilled water pumps and the cooling water pumps.
•Energize the pumps to start the water circulation.
•Check the service valves on the discharge line, suction line, oil line and liquid line for each circuit. These valves must be open before starting the compressors.
WARNING
To prevent compressor damage, do not operate the unit until all refrigerant and
•Verify that the chilled water pump runs for one minute after the chiller is commanded to stop for normal chilled water systems).
•Press the Auto key. If the chiller
control calls for cooling and all the safety interlocks are closed, the unit will start.The compressor(s) will load and unload in response to the temperature of the leaving chilled- water temperature.
After the system has been operating for approximately 30 minutes and has become stabilized, complete the
•Check the evaporator refrigerant pressure and the condenser refrigerant pressure in the Refrigerant report of the
•Measure the system overheat.
•Measure the system subcooling.
A shortage of refrigerant is indicated if the operating pressures and the subcooling are low. If the operating pressures, superheat, and subcooling readings indicate a refrigerant shortage,
WARNING
If both suction and discharge pressures are low and subcooling is normal, a problem other than refrigerant shortage exists. Do not add refrigerant, as this may result in overcharging the circuit.
Only use the refrigerant specified on the unit nameplate.
•If operating conditions indicate a refrigerant overcharge, remove refrigerant at the liquid line service valve. Allow refrigerant to escape slowly to minimize oil loss. Do not discharge refrigerant into the atmosphere.
WARNING
Do not allow refrigerant to directly contact skin, or injury from frostbite may result.
Overheating
Normal overheating for each circuit is approximately
22 |