Energy Tech Laboratories LB360, LB480, LB300, LB600 Hole Location for Pressure Drop Reading

Page 25

035-18496-000-C-1102

To check the supply air CFM after the initial balanc- ing has been completed:

1.Drill two (2) 5/16-inch holes in the side panel as shown in Figure 24.

2.Insert at least 8 inches of 1/4 inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the evaporator coil.

3.Using an inclined manometer, determine the pressure drop across a dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pres- sure drop across the wet coil under field conditions would be inaccurate. To assure a dry coil, the refrigerant system should be de-activated while the test is being run.

4.Knowing the pressure drop across a dry coil, the actual CFM through the unit can be determined from the curves shown in Figures 25-28.

If the CFM is above or below the specified value, the supply air motor pulley may have to be readjusted. After one hour of operation, check the belt and pulleys for tightness and align- ment.

Failure to properly adjust the total system air quantity can result in extensive blower dam- age.

After readings have been obtained, remove the tubes and seal up the drilled holes in the side panel. 5/16 inch dot plugs (P/N 029-12880) are available through normal York parts ordering procedures.

25"

7"

5/16"

 

HOLE

EVAPORATOR

COIL

22"

5/16"

HOLE

14"

FILTERS

COIL SECTION

FIGURE 25 - HOLE LOCATION FOR PRESSURE DROP READING

Unitary Products Group

25

Image 25
Contents Models LB300 Installation ManualTable of Contents List of Tables Limitations GeneralUnit Application Data MBHDescription Model Physical DataLA300/LB360/LB480 Motor Mounting Blower Motor Mounting LocationsLB600 Motor Mounting Location a Motor Mount ArrangementsLA300/LB360/LB480 Motor Arrangements Additional Motor Arrangments for LA300/ LB360/LB480AIR Discharge Conversion Vertical Arrangements Vertical Airflow ArrangementsRigging LocationClearances LB600 AIR DischargeCorner Weights Unit Mounting DimensionsAccessory Operating Weight Distribution LBS MountingDetails for Securing Bottom Mounting Supports LB600 Weight Distribution with Suspension Application Supply AIR Ducts InsulationDrain Connections Return AIR Duct AnglesEvaporator Section Piping Expansion Valve Bulb InstallationLiquid Line Solenoids Bearing Alignment LB600 Twin Belt Drive AdjustmentPump OUT Electrical Data Electrical ConnectionsMotor Overload Elements Unit Blower Motor Data Unit Drive DataFAN Peformance Data 30 TON FAN Peformance Data 25 TONFAN Performance Data 40 TON FAN Performance Data 50 TONSolenoid Wiring Unit Dimensions LA300, LB360, LB480LA300 Piping Connections Unit Dimensions Hole Location for Pressure Drop Reading 30-TON Pressure Drop VS. CFM Across Indoor Coil 25-TON Pressure Drop VS. CFM Across Indoor CoilCFM Indoor Unit Wiring Diagram LB360, 480 Indoor Wiring Diagram LA300 035-18496-000-C-1102 035-18496-000-C-1102 Unitary Products Group Unitary 5005 Norman Products York Group Drive 73069