Energy Tech Laboratories LB600 Electrical Connections, Electrical Data, Motor Overload Elements

Page 19

035-18496-000-C-1102

Check belt tension. Drive packages are supplied with fiber- glass belts that must be properly tensioned at installation because they do not stretch. The belt should deflect 3/16" per foot of belt span with a 2 or 3-pound force. Alignment of the resilient motor mount can be corrected by adjustment at the slots on the end opposite the pulleys.

ELECTRICAL CONNECTIONS

The electric box ships complete with motor starter, transform- ers, relays and terminal block for making field connections. Remember: One air handlers with factory installed pump out solenoids, wires to the solenoid must be field connected.

Refer to Figures 30 & 31 for Indoor Unit Wiring Diagrams.

Install a power supply to meet the requirements listed in table 6.

Provide a disconnect switch and fusing as required.

Install interconnecting control wiring between condensing section, evaporator blower and room thermostat.

Starters are shipped without overloads. These must be ordered separately to match the selected motor used in the air handler. See unit’s Technical Guide or price page for cor- rect overload.

NOTE: For the 10HP 200/208-volt motors, install the power wiring to the supply air blower through the starter.

TABLE 6: ELECTRICAL DATA

 

 

 

 

MIN

MAX.

UNIT

 

 

VOLTAGE

FUSE

HP

FLA

CIRCUIT

MODEL

(3PH-60HZ)

SIZE

 

 

AMPACITY

 

 

 

 

(Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

16.7

208

21

35

 

5

15.2

230

19

30

 

 

 

 

 

 

7.6

460

10

15

 

 

 

 

 

 

 

 

LA300

 

6.1

575

8

15

 

 

 

 

 

 

24.2

208

30

50

 

 

 

 

 

 

 

 

 

7.5

22

230

28

45

 

 

 

 

 

 

11

460

14

20

 

 

 

 

 

 

 

 

 

 

9

575

11

20

 

 

 

 

 

 

 

 

16.7

208

21

35

 

 

 

 

 

 

 

5.0

15.2

230

19

30

 

 

 

 

 

 

7.6

460

10

15

 

 

 

 

 

 

 

 

 

 

6.1

575

8

15

 

 

 

 

 

 

 

 

24.2

208

30

50

 

 

 

 

 

 

LB360

7.5

22

230

28

45

 

 

 

 

11

460

14

20

 

 

 

 

 

 

 

 

 

 

9

575

11

20

 

 

 

 

 

 

 

 

30.8

208

39

60

 

 

 

 

 

 

 

10

28

230

35

60

 

 

 

 

 

 

14

460

18

30

 

 

 

 

 

 

 

 

 

 

11

575

14

20

 

 

 

 

 

 

 

 

24.2

208

30

50

 

 

 

 

 

 

 

7.5

22

230

28

45

 

 

 

 

 

 

11

460

14

20

 

 

 

 

 

 

 

 

LB480

 

9

575

11

20

 

 

 

 

 

 

30.8

208

39

60

 

 

 

 

 

 

 

 

 

10

28

230

35

60

 

 

 

 

 

 

14

460

18

30

 

 

 

 

 

 

 

 

 

 

11

575

14

20

 

 

 

 

 

 

 

 

30.8

208

39

60

 

 

 

 

 

 

 

10

28

230

35

60

 

 

 

 

 

 

14

460

18

30

 

 

 

 

 

 

 

 

LB600

 

11

575

14

20

 

 

 

 

 

 

46.2

208

58

100

 

 

 

 

 

 

 

 

 

15

42

230

53

90

 

 

 

 

 

 

21

460

26

45

 

 

 

 

 

 

 

 

 

 

17

575

21

35

TABLE 7: MOTOR OVERLOAD ELEMENTS*

MOTOR HP

VOLTAGE

MODEL NUMBER

 

208

2MP04704600

5

230

2MP04704600

 

 

 

 

460

2MP04704900

 

 

 

 

 

575

2MP04705000

 

 

208

2MP04703700

7.5

230

2MP04704500

 

 

 

 

460

2MP04704300

 

 

 

 

 

575

2MP04704000

 

 

208

2MP04701600

10

230

2MP04704100

 

 

 

 

460

2MP04704200

 

 

 

 

 

575

2MP04704300

 

 

208

2MP04704400

15

230

2MP04701700

 

 

 

 

460

2MP04704500

 

 

 

 

 

575

2MP04704600

 

*. These units are equipped from the factory with a cor- rectly sized motor starter; overload elements are not factory supplied. Three elements required per unit.

Unitary Products Group

19

Image 19
Contents Models LB300 Installation ManualTable of Contents List of Tables Limitations GeneralUnit Application Data MBHDescription Model Physical DataLA300/LB360/LB480 Motor Mounting Blower Motor Mounting LocationsLB600 Motor Mounting Additional Motor Arrangments for LA300/ LB360/LB480 Motor Mount ArrangementsLocation a LA300/LB360/LB480 Motor ArrangementsAIR Discharge Conversion Vertical Arrangements Vertical Airflow ArrangementsLB600 AIR Discharge LocationRigging ClearancesMounting Unit Mounting DimensionsCorner Weights Accessory Operating Weight Distribution LBSDetails for Securing Bottom Mounting Supports LB600 Weight Distribution with Suspension Application Supply AIR Ducts InsulationDrain Connections Return AIR Duct AnglesEvaporator Section Piping Expansion Valve Bulb InstallationLiquid Line Solenoids Bearing Alignment LB600 Twin Belt Drive AdjustmentPump OUT Electrical Data Electrical ConnectionsMotor Overload Elements Unit Blower Motor Data Unit Drive DataFAN Performance Data 50 TON FAN Peformance Data 25 TONFAN Peformance Data 30 TON FAN Performance Data 40 TONSolenoid Wiring Unit Dimensions LA300, LB360, LB480LA300 Piping Connections Unit Dimensions Hole Location for Pressure Drop Reading 30-TON Pressure Drop VS. CFM Across Indoor Coil 25-TON Pressure Drop VS. CFM Across Indoor CoilCFM Indoor Unit Wiring Diagram LB360, 480 Indoor Wiring Diagram LA300 035-18496-000-C-1102 035-18496-000-C-1102 Unitary Products Group Unitary 5005 Norman Products York Group Drive 73069