Energy Tech Laboratories LB480, LB360, LB300, LB600 Return AIR Duct Angles, Drain Connections

Page 16

035-18496-000-C-1102

NON-FLAMMABLE COLLAR

24"

DUCT TRANSITION

DUCT

AIR

 

OUTLET

 

 

FLANGED DUCT

BLOWER

CONNECTION

(FIELD

GASKETS

FABRICATED)

(BY INSTALLER)

 

FIGURE 13 - SUGGESTED METHOD FOR CONNECTING DUCTWORK

RETURN AIR DUCT ANGLES

Return air duct angles are shipped turned in. They are intended to be unscrewed and turned for connection of duct- work. The return air grille accessory attaches in the same manner as the panels.

DRAIN CONNECTIONS

All drain lines MUST be trapped and located so they will not be exposed to freezing temperatures.

The evaporator blower has 7/8" OD steel condensate stub at each end of a single drain pan. Both ends are closed with plastic caps. A plastic or rubber ell can be used. (Field sup- plied) Attach the ell to the desired end and run a full size 7/8" drain line to the nearest drain facility. Seal the cap at the unused end with suitable mastic.

Drain piping should be constructed as shown in 14. The 3- inch dimension must equal or exceed the negative static pressure developed by the supply air blowers. If it does not, the condensate will not drain properly and may overflow the drain pan. The trap must be at least 2-inches deep to main- tain a water seal under all operating conditions, especially when the blowers are starting.

FIGURE 14 - RECOMMENDED DRAIN PIPING REFRIGERANT MAINS

Hard drawn copper tubing should be used where no appre- ciable amount of bending around pipes or other obstructions is necessary. Use long radius ells wherever possible. If soft copper is used, care should be taken to avoid sharp bends that may cause a restriction.

Where refrigerant lines pass through a wall, pack fiberglass insulation and a sealing material such as permagum around the refrigerant lines to reduce vibration and to retain some flexibility in the lines.

16

Unitary Products Group

Image 16
Contents Installation Manual Models LB300Table of Contents List of Tables General LimitationsMBH Unit Application DataPhysical Data Description ModelLA300/LB360/LB480 Motor Mounting Blower Motor Mounting LocationsLB600 Motor Mounting Motor Mount Arrangements Location aLA300/LB360/LB480 Motor Arrangements Additional Motor Arrangments for LA300/ LB360/LB480AIR Discharge Conversion Vertical Airflow Arrangements Vertical ArrangementsLocation RiggingClearances LB600 AIR DischargeUnit Mounting Dimensions Corner WeightsAccessory Operating Weight Distribution LBS MountingDetails for Securing Bottom Mounting Supports LB600 Weight Distribution with Suspension Application Insulation Supply AIR DuctsReturn AIR Duct Angles Drain ConnectionsEvaporator Section Piping Expansion Valve Bulb InstallationLiquid Line Solenoids Bearing Alignment LB600 Twin Belt Drive AdjustmentPump OUT Electrical Data Electrical ConnectionsMotor Overload Elements Unit Drive Data Unit Blower Motor DataFAN Peformance Data 25 TON FAN Peformance Data 30 TONFAN Performance Data 40 TON FAN Performance Data 50 TONUnit Dimensions LA300, LB360, LB480 Solenoid WiringLA300 Piping Connections Unit Dimensions Hole Location for Pressure Drop Reading 25-TON Pressure Drop VS. CFM Across Indoor Coil 30-TON Pressure Drop VS. CFM Across Indoor CoilCFM Indoor Unit Wiring Diagram LB360, 480 Indoor Wiring Diagram LA300 035-18496-000-C-1102 035-18496-000-C-1102 Unitary Products Group Unitary 5005 Norman Products York Group Drive 73069