Bryant 548D installation instructions IV. Economizer Adjustment, Refrigerant Charge

Page 32

III.OUTDOOR FAN ADJUSTMENT (Fig. 42)

1.Shut off unit power supply.

2.Remove outdoor-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews.

3.Adjust fan height as shown in Fig. 42.

4.Tighten setscrews and replace outdoor-fan assembly.

UNIT

‘‘A’’

VOLTAGE

in.

208/230 V

2.75

460 V and 575 V

3.50

Fig. 42 — Outdoor Fan Adjustment

IV. ECONOMIZER ADJUSTMENT

Refer to Optional Economizer sections on pages 11 and 15.

IMPORTANT: Refer to Troubleshooting Tables 14-16 for addi- tional information.

V. REFRIGERANT CHARGE

A. Checking and Adjustment Refrigerant Charge

The refrigerant system is fully charged with R-22 refriger- ant, tested, and factory-sealed. Unit must operate in cooling mode a minimum of 10 minutes before checking charge.

NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R-22 charge.

A superheat charging chart is attached to the outside of the service access panel. The chart includes the required suction line temperature at given suction line pressures and outdoor ambient temperatures.

An accurate superheat, thermocouple- or thermistor-type thermometer and a gage manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.

CAUTION: When evaluating the refrigerant charge, an indicated adjustment to the specified fac- tory charge must always be very minimal. If a substan- tial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insuf- ficient airflow across either coil or both coils.

Proceed as follows:

1.Remove caps from low- and high-pressure service fittings.

2.Using hoses with valve core depressors, attach low- and high-pressure gage hoses to low- and high- pressure service fittings, respectively.

3.Start unit in Cooling mode and let unit run until sys- tem pressures stabilize.

4.Measure and record the following:

a.Outdoor ambient-air temperature (F db).

b.Evaporator inlet-air temperature (F wb).

c.Suction-tube temperature (F) at low-side service fitting.

d.Suction (low-side) pressure (psig).

5.Using “Cooling Charging Charts” compare outdoor- air temperature (F db) with the suction line pressure (psig) to determine desired system operating suction line temperature. See Fig. 43-45.

6.Compare actual suction-tube temperature with desired suction-tube temperature. Using a tolerance of ± 3° F, add refrigerant if actual temperature is more than 3° F higher than proper suction-tube tem- perature, or remove refrigerant if actual temperature is more than 3° F lower than required suction-tube temperature.

B.To Use Cooling Charging Charts

Take the outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what the suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.

EXAMPLE: (Fig. 43)

Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 psig

Suction Temperature should be . . . . . . . . . . . . . . . . . . . . 49 F (Suction Temperature may vary ±5° F.)

C. Heating Mode Charge

Do not attempt to adjust charge by cooling methods while in Heating mode. When charging is necessary in Heating mode, recover refrigerant and weigh in according to unit data plate refrigerant data.

Fig. 43 — Cooling Charging Chart, 548D090

32

Image 32
Contents Contents Safety ConsiderationsInstallation Provide Unit SupportRoof Curb Details III. Install Condensate Drain Line and External Trap II. Field Fabricate DuctworkIV. RIG and Place Unit PositioningUnit MAX Dimensions Weight Base Unit Dimensions Physical Data Unit Size 548DField Power Supply Make Electrical Connections575-3-60 460-3-60Electrical Data Units Without Electrical Convenience Outlet SIZE†Type RLA LRA FLA81/2 Tons Electrical Data Units With Electrical Convenience OutletMin FLA VI. Adjust FACTORY-INSTALLED Options Stage Unit Voltage208/230 460 575 Durablade Economizer Installation Durablade Economizer Damper Minimum Position Setting EconoMi$er Component Locations Rear EconoMi$er Flange Installation EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsVII. Adjust INDOOR-FAN Speed Typical Belt-Drive Motor Mounting for Size Fan Rpm at Motor Pulley Settings Indoor-Fan Motor PerformanceUnit INDOOR-FAN Maximum Acceptable Continuous BHPFan Performance 548D090 Vertical Discharge Units Standard Motor Belt DriveFan Performance 548D102 Vertical Discharge Units Fan Performance 548D120 Vertical Discharge Units 548D120 10 Tons Standard and Alternate Motors Belt DriveFan Performance 548D090 Horizontal Discharge Units Fan Performance 548D102 Horizontal Discharge Units Fan Performance 548D120 Horizontal Discharge Units Standard and Alternate Motors Belt DriveInternal Wiring VI. Refrigerant Service PortsPRE-START-UP START-UP Unit PreparationIX. Adjust GAS Input XII. Safety ReliefCooling XI. HeatingService Cleaning Cooling, Units With EconoMi$erDefrost Indoor CoilII. Lubrication IV. Economizer Adjustment Refrigerant ChargeCooling Charging Chart 548D102 Problem Cause Remedy TroubleshootingHeating and Cooling Troubleshooting Durablade Economizer Troubleshooting IFCIFO OATDamper does not open EconoMi$er operation limitedTo minimum position Damper positionTypical Wiring Diagram Must Voltage Page START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical

548D specifications

The Bryant 548D heat pump stands out in the HVAC market for its robust performance, energy efficiency, and advanced technology. Known for its reliability, this particular model is designed to provide optimal heating and cooling for both residential and light commercial applications.

One of the standout features of the Bryant 548D is its variable-speed compressor, which allows for precise temperature control and enhances comfort levels in any environment. This technology enables the 548D to operate efficiently at different speeds, adjusting its output based on the heating or cooling demand. As a result, homeowners can enjoy consistent temperature regulation without the wide fluctuations typical of single-stage systems.

In addition to the variable-speed compressor, the Bryant 548D utilizes advanced refrigerant technology. It employs the environmentally friendly Puron refrigerant, which not only improves the unit's efficiency but also reduces its carbon footprint. This makes the 548D a sustainable choice for those looking to minimize their environmental impact while still enjoying superior heating and cooling performance.

Another key characteristic of the Bryant 548D is its impressive energy efficiency rating, often exceeding the minimum requirements set by the Department of Energy. With a high Seasonal Energy Efficiency Ratio (SEER) for cooling in warmer months and an excellent Heating Seasonal Performance Factor (HSPF), the 548D minimizes energy consumption while maximizing comfort.

The 548D also features Quiet Operation technology, ensuring that the system runs quietly in the background without disrupting daily activities. This is particularly beneficial for light commercial spaces or homes where noise can be a concern. The sleek design and compact size make the unit easy to install in various settings without occupying excessive space.

Furthermore, Bryant incorporates advanced smart technology within the 548D model. The system can be integrated with smart thermostats, allowing users to monitor and control their heating and cooling settings remotely. This feature not only enhances convenience but also enables homeowners to program their systems for maximum efficiency.

In conclusion, the Bryant 548D heat pump is an exceptional choice for those seeking a reliable, efficient, and technologically advanced heating and cooling solution. Its combination of variable-speed compression, eco-friendly refrigerant, high energy efficiency, and quiet operation positions it well in the competitive HVAC market, making it a top choice for both residential and light commercial applications. By investing in the Bryant 548D, consumers can enjoy superior comfort and lower energy bills year-round.