Bryant 548D installation instructions Must Voltage

Page 38

NOTES:

1.If any of the original wire furnished must be replaced, it must be replaced with type 90° C wire or its equivalent.

2.Three-phase motors are protected under primary single-phasing conditions.

3.Thermostat: HH07AT172 and P272-2783

Subbase: HH93AZ176, 178 and P272-1882, 1883

4.Set Heat anticipator at .8 amp for 1st stage and .3 amp for 2nd stage.

5.Use copper conductors only.

6.Use copper, copper clad aluminum or aluminum conductors.

7.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CB

MUST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE

Mfg. Pt. No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRIP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Potter &

AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brumfield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 V

W28X-1024-3.2

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AHA — Adjustable Heat Anticipator AWG — American Wire Gage

CContactor, Compressor CAP — Capacitor

CB — Circuit Breaker

CCCooling Capacitor

CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor

DDiode

DB

Defrost Board

DFT

Defrost Thermostat

EC

Enthalpy Control

ECON

Economizer

EPS

Emergency Power Supply

 

 

(nine volt battery)

EQUIP

Equipment

ER

Economizer Relay

FPT

Freeze-Up Protection Thermostat

FU

Fuse

GND

Ground

HC

Heater Contactor (Strip Heat)

HPS

High-Pressure Switch

HR

Heater Relay

IFC

Indoor Fan Contactor

IFM

Indoor Fan Motor

IFMOVL — Indoor Fan Motor Overload Switch

LPS

Low-Pressure Switch

LSM

Limit Switch (Manual Reset)

MCA

Minimum Circuit Amps

MTR

Motor

OAT

Outdoor Air Thermostat

OFC

Outdoor Fan Contactor

OFM

Outdoor Fan Motor

PPlug

PL — Plug Assembly

QT — Quadruple Terminal

LEGEND

RRelay

RVS — Reversing Valve Solenoid

SAT — Supply Air Thermostat

SW1 — Switch Fully Open

SW2 — Switch Fully Closed

SW3 — Switch Minimum Vent Position

SW4 — Switch Maximum Vent Position

TB — Terminal Block

TC — Thermostat-Cooling

TH — Thermostat-Heating

TRAN — Transformer

Field Splice

Marked Wire

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice

Spliced (Marked)

Factory Wiring

Field Control Wiring

Field Power Wiring

Accessory or Optional Wiring

To indicate common potential only, not to represent wiring.

Fig. 46 — Typical Wiring Diagram (cont)

Copyright 2000 Bryant Heating & Cooling Systems

CATALOG NO. 5354-805

Image 38
Contents Installation ContentsSafety Considerations Provide Unit SupportRoof Curb Details IV. RIG and Place Unit III. Install Condensate Drain Line and External TrapII. Field Fabricate Ductwork PositioningUnit MAX Dimensions Weight Base Unit Dimensions Physical Data Unit Size 548D575-3-60 Field Power SupplyMake Electrical Connections 460-3-60Type Electrical Data Units Without Electrical Convenience OutletSIZE† RLA LRA FLA81/2 Tons Electrical Data Units With Electrical Convenience OutletMin FLA VI. Adjust FACTORY-INSTALLED Options Stage Unit Voltage208/230 460 575 Durablade Economizer Installation Durablade Economizer Damper Minimum Position Setting EconoMi$er Component Locations Rear EconoMi$er Flange Installation EconoMi$er Wiring Wiring Diagram for Power Exhaust System Changeover Set Points Default Potentiometer SettingsVII. Adjust INDOOR-FAN Speed Typical Belt-Drive Motor Mounting for Size Unit INDOOR-FAN Maximum Acceptable Fan Rpm at Motor Pulley SettingsIndoor-Fan Motor Performance Continuous BHPFan Performance 548D090 Vertical Discharge Units Standard Motor Belt DriveFan Performance 548D102 Vertical Discharge Units Fan Performance 548D120 Vertical Discharge Units 548D120 10 Tons Standard and Alternate Motors Belt DriveFan Performance 548D090 Horizontal Discharge Units Fan Performance 548D102 Horizontal Discharge Units Fan Performance 548D120 Horizontal Discharge Units Standard and Alternate Motors Belt DrivePRE-START-UP Internal WiringVI. Refrigerant Service Ports START-UP Unit PreparationCooling IX. Adjust GAS InputXII. Safety Relief XI. HeatingDefrost Service CleaningCooling, Units With EconoMi$er Indoor CoilII. Lubrication IV. Economizer Adjustment Refrigerant ChargeCooling Charging Chart 548D102 Problem Cause Remedy TroubleshootingHeating and Cooling Troubleshooting IFO Durablade Economizer TroubleshootingIFC OATTo minimum position Damper does not openEconoMi$er operation limited Damper positionTypical Wiring Diagram Must Voltage Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical

548D specifications

The Bryant 548D heat pump stands out in the HVAC market for its robust performance, energy efficiency, and advanced technology. Known for its reliability, this particular model is designed to provide optimal heating and cooling for both residential and light commercial applications.

One of the standout features of the Bryant 548D is its variable-speed compressor, which allows for precise temperature control and enhances comfort levels in any environment. This technology enables the 548D to operate efficiently at different speeds, adjusting its output based on the heating or cooling demand. As a result, homeowners can enjoy consistent temperature regulation without the wide fluctuations typical of single-stage systems.

In addition to the variable-speed compressor, the Bryant 548D utilizes advanced refrigerant technology. It employs the environmentally friendly Puron refrigerant, which not only improves the unit's efficiency but also reduces its carbon footprint. This makes the 548D a sustainable choice for those looking to minimize their environmental impact while still enjoying superior heating and cooling performance.

Another key characteristic of the Bryant 548D is its impressive energy efficiency rating, often exceeding the minimum requirements set by the Department of Energy. With a high Seasonal Energy Efficiency Ratio (SEER) for cooling in warmer months and an excellent Heating Seasonal Performance Factor (HSPF), the 548D minimizes energy consumption while maximizing comfort.

The 548D also features Quiet Operation technology, ensuring that the system runs quietly in the background without disrupting daily activities. This is particularly beneficial for light commercial spaces or homes where noise can be a concern. The sleek design and compact size make the unit easy to install in various settings without occupying excessive space.

Furthermore, Bryant incorporates advanced smart technology within the 548D model. The system can be integrated with smart thermostats, allowing users to monitor and control their heating and cooling settings remotely. This feature not only enhances convenience but also enables homeowners to program their systems for maximum efficiency.

In conclusion, the Bryant 548D heat pump is an exceptional choice for those seeking a reliable, efficient, and technologically advanced heating and cooling solution. Its combination of variable-speed compression, eco-friendly refrigerant, high energy efficiency, and quiet operation positions it well in the competitive HVAC market, making it a top choice for both residential and light commercial applications. By investing in the Bryant 548D, consumers can enjoy superior comfort and lower energy bills year-round.