Bryant 548D Heating and Cooling Troubleshooting, Problem Cause Remedy

Page 34

TROUBLESHOOTING

Refer to Tables 14-16 and Fig. 46 for troubleshooting information.

Table 14 — Heating and Cooling Troubleshooting

PROBLEM

CAUSE

REMEDY

Compressor and

Power failure.

Call power company.

outdoor fan

 

 

Fuse blown or circuit breaker tripped.

Replace fuse or reset circuit breaker.

will not start.

Defective thermostat, contactor, transformer, or control relay.

Replace component.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Incorrect or faulty wiring.

Check wiring diagram and rewire correctly.

 

Thermostat setting too high.

Lower thermostat setting below room

 

 

temperature.

 

High-pressure switch tripped.

See problem ‘‘Excessive head pressure.’’

 

Low-pressure switch tripped.

Check for leaks, repair, and recharge.

 

Freeze-up protection thermostat tripped.

See problem ‘‘Suction pressure too low.’’

Compressor will not start

Faulty wiring or loose connections in compressor circuit.

Check wiring and repair or replace.

but outdoor fan runs.

Compressor motor burned out, seized, or internal

Determine cause. Replace compressor.

 

 

overload open.

 

 

Defective overload.

Determine cause and replace.

 

One leg of 3-phase power dead.

Replace fuse or reset circuit breaker.

 

 

Determine cause.

Compressor cycles

Refrigerant overcharge or undercharge.

Recover refrigerant, evacuate system, and

(other than normally

 

recharge to nameplate.

satisfying thermostat).

Defective compressor.

Replace and determine cause.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Blocked outdoor coil or dirty air filter.

Determine cause and correct.

 

Defective overload.

Determine cause and replace.

 

Defective thermostat.

Replace thermostat.

 

Faulty outdoor-fan (cooling) or indoor-fan (heating) motor or

Replace.

 

capacitor.

 

 

Restriction in refrigerant system.

Locate restriction and remove.

Compressor operates

Dirty air filter.

Replace filter.

continuously.

Unit undersized for load.

Decrease load or increase unit size.

 

 

Thermostat set too low.

Reset thermostat.

 

Low refrigerant charge.

Locate leak, repair, and recharge.

 

Leaking valves in compressor.

Replace compressor.

 

Air in system.

Recover refrigerant, evacuate system, and

 

 

recharge.

 

Outdoor coil dirty or restricted.

Clean coil or remove restriction.

Scroll compressor

Compressor rotating in the wrong direction.

Reverse the 3-phase power leads as described in

makes excessive noise.

 

Start-Up, page 28.

Excessive head

Dirty air filter.

Replace filter.

pressure

 

 

Dirty outdoor coil.

Clean coil.

 

 

Refrigerant overcharged.

Remove excess refrigerant.

 

Air in system.

Recover refrigerant, evacuate system, and

 

 

recharge.

 

Condensing air restricted or air short-cycling.

Determine cause and correct.

Head pressure

Low refrigerant charge.

Check for leaks, repair, and recharge.

too low.

 

 

Compressor valves leaking.

Replace compressor.

 

 

Restriction in liquid tube.

Remove restriction.

Excessive suction

High heat load.

Check for source and eliminate.

pressure.

 

 

Compressor valves leaking.

Replace compressor.

 

 

Refrigerant overcharged.

Recover excess refrigerant.

Suction pressure

Dirty air filter (cooling) or dirty outdoor coil (heating).

Replace filter or clean coil.

too low.

 

 

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

 

Metering device or low side restricted

Remove source of restriction.

 

Insufficient indoor airflow (cooling mode).

Increase air quantity. Check filter and replace if

 

 

necessary.

 

Temperature too low in conditioned area.

Reset thermostat.

 

Field-installed filter drier restricted.

Replace.

 

Outdoor ambient temperature below 25 F.

Install low-ambient kit.

Compressor no. 2

Unit in economizer mode.

Proper operation; no remedy necessary.

will not run.

 

 

34

Image 34
Contents Installation ContentsSafety Considerations Provide Unit SupportRoof Curb Details IV. RIG and Place Unit III. Install Condensate Drain Line and External TrapII. Field Fabricate Ductwork PositioningUnit MAX Dimensions Weight Base Unit Dimensions Physical Data Unit Size 548D575-3-60 Field Power SupplyMake Electrical Connections 460-3-60Type Electrical Data Units Without Electrical Convenience OutletSIZE† RLA LRA FLAMin Electrical Data Units With Electrical Convenience Outlet81/2 Tons FLA VI. Adjust FACTORY-INSTALLED Options 208/230 460 575 Unit VoltageStage Durablade Economizer Installation Durablade Economizer Damper Minimum Position Setting EconoMi$er Component Locations Rear EconoMi$er Flange Installation EconoMi$er Wiring Wiring Diagram for Power Exhaust System VII. Adjust INDOOR-FAN Speed Default Potentiometer SettingsChangeover Set Points Typical Belt-Drive Motor Mounting for Size Unit INDOOR-FAN Maximum Acceptable Fan Rpm at Motor Pulley SettingsIndoor-Fan Motor Performance Continuous BHPFan Performance 548D090 Vertical Discharge Units Standard Motor Belt DriveFan Performance 548D102 Vertical Discharge Units Fan Performance 548D120 Vertical Discharge Units 548D120 10 Tons Standard and Alternate Motors Belt DriveFan Performance 548D090 Horizontal Discharge Units Fan Performance 548D102 Horizontal Discharge Units Fan Performance 548D120 Horizontal Discharge Units Standard and Alternate Motors Belt DrivePRE-START-UP Internal WiringVI. Refrigerant Service Ports START-UP Unit PreparationCooling IX. Adjust GAS InputXII. Safety Relief XI. HeatingDefrost Service CleaningCooling, Units With EconoMi$er Indoor CoilII. Lubrication IV. Economizer Adjustment Refrigerant ChargeCooling Charging Chart 548D102 Heating and Cooling Troubleshooting TroubleshootingProblem Cause Remedy IFO Durablade Economizer TroubleshootingIFC OATTo minimum position Damper does not openEconoMi$er operation limited Damper positionTypical Wiring Diagram Must Voltage Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical

548D specifications

The Bryant 548D heat pump stands out in the HVAC market for its robust performance, energy efficiency, and advanced technology. Known for its reliability, this particular model is designed to provide optimal heating and cooling for both residential and light commercial applications.

One of the standout features of the Bryant 548D is its variable-speed compressor, which allows for precise temperature control and enhances comfort levels in any environment. This technology enables the 548D to operate efficiently at different speeds, adjusting its output based on the heating or cooling demand. As a result, homeowners can enjoy consistent temperature regulation without the wide fluctuations typical of single-stage systems.

In addition to the variable-speed compressor, the Bryant 548D utilizes advanced refrigerant technology. It employs the environmentally friendly Puron refrigerant, which not only improves the unit's efficiency but also reduces its carbon footprint. This makes the 548D a sustainable choice for those looking to minimize their environmental impact while still enjoying superior heating and cooling performance.

Another key characteristic of the Bryant 548D is its impressive energy efficiency rating, often exceeding the minimum requirements set by the Department of Energy. With a high Seasonal Energy Efficiency Ratio (SEER) for cooling in warmer months and an excellent Heating Seasonal Performance Factor (HSPF), the 548D minimizes energy consumption while maximizing comfort.

The 548D also features Quiet Operation technology, ensuring that the system runs quietly in the background without disrupting daily activities. This is particularly beneficial for light commercial spaces or homes where noise can be a concern. The sleek design and compact size make the unit easy to install in various settings without occupying excessive space.

Furthermore, Bryant incorporates advanced smart technology within the 548D model. The system can be integrated with smart thermostats, allowing users to monitor and control their heating and cooling settings remotely. This feature not only enhances convenience but also enables homeowners to program their systems for maximum efficiency.

In conclusion, the Bryant 548D heat pump is an exceptional choice for those seeking a reliable, efficient, and technologically advanced heating and cooling solution. Its combination of variable-speed compression, eco-friendly refrigerant, high energy efficiency, and quiet operation positions it well in the competitive HVAC market, making it a top choice for both residential and light commercial applications. By investing in the Bryant 548D, consumers can enjoy superior comfort and lower energy bills year-round.