Bryant 265A warranty Electrical Data, Charging Subcooling TXV-TYPE Expansion Device

Page 7

ELECTRICAL DATA

 

 

 

 

 

 

 

 

MIN

MIN

MAX

MAX

MAX

 

 

 

 

 

 

 

 

WIRE

WIRE

FUSE**

 

 

OPER VOLTS*

COMPR

FAN

 

LENGTH

LENGTH

UNIT SIZE

V/PH

MCA

SIZE

SIZE

or CKT

 

 

 

 

 

(FT)}

(FT)}

 

 

 

 

 

 

 

 

{

{

BRK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AMPS

 

 

MAX

MIN

LRA

RLA

FLA

 

60° C

75° C

60° C

75° C

018---B

 

 

 

48

9

0.7

12

14

14

66

62

20

024---B

 

 

 

58.3

12.8

0.7

16.7

14

14

46

44

25

030---B

 

 

 

73

14.1

1.1

18.7

14

14

41

39

30

036---B

208/230/1

253

197

79

17.9

1.1

23.4

12

12

55

52

35

042---B

 

 

 

109

21.3

1.1

27.7

10

10

71

68

40

048---B

 

 

 

117

21.8

1.3

28.5

10

10

69

66

40

060---B

 

 

 

134

26.4

1.3

34.3

8

10

91

56

50

* Permissible limits of the voltage range at which the unit will operate satisfactorily

{If wire is applied at ambient greater than 30° C (86° F), consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60° C (140° F) conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60

or 75° C (140 or 167° C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time---Delay fuse.

FLA

--- Full Load Amps

LRA

--- Locked Rotor Amps

MCA

--- Minimum Circuit Amps

RLA

--- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

A-WEIGHTED SOUND LEVEL (dBA)

UNIT SIZE

STANDARD

 

TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

 

RATING

125

250

500

1000

2000

4000

8000

 

018---B

70

57

57

63

62.5

61

56.5

47.5

024---B

69

56.5

57.5

63.5

61.5

61.5

57

48.5

030---B

71

59.5

60

65

64.5

61.5

58

55.5

036---B

71

60

62

66

65

63

58

51.5

042---B

71

60.5

59.5

63

64

62

58.5

50.5

048---B

72

58.5

62.5

64.5

67

65

61

54.5

060---B

75

59

61

67

69.5

64

59

54.5

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---SERIES

REQUIRED SUBCOOLING (F)

018---B

12

024---B

11

030---B

11

036---B

11

042---B

10

048---B

10

060---B

11

265A

7

Image 7
Contents Product Data Industry Leading Features / BenefitsISO Model Number NomenclatureUnit Size Series Physical DataAccessory Thermostats AccessoriesApplications Accessory Usage GuidelineOutdoor Air Temperature Sensor Charging Subcooling TXV-TYPE Expansion Device Electrical DataDimensions 265A Balance Point Worksheet Enhance Rating Combination RatingsCapacity Factory Standard Furnace Model030--B CAP**3017A 28,800 036--B FE4ANB006FV4BNB006 FY4ANF042042--B FY4ANF048CAP**4821A 41,500 FY4ANB060 048--B060--B Detailed Cooling Capacities Cooling Indoor Model Capacity Power Furnace Model800 700900 FY4ANF030 FY4ANF036 1350 FY4ANF036 FY4ANF0421050 12001575 FY4ANF042 FY4ANF0481225 14001800 FE4ANB006 FE4ANF005 FV4BNB006 FV4BNF005FY4ANB060 FY4ANF048 16002250 FE4ANB006 FV4BNB006 FY4ANB0601750 2000Heat Pump Heating Performance Total Integ Outdoor Coil Entering AIR Temperatures deg FFX4CNF030 CSPH*3612A 315A,JAV048090 FX4CNB,F042 CNPH*4221A 315A,JAV060110 FX4CNB,F048 CAP**4224A 315A,JAV066135 265ANA048-- B Outdoor Section With FX4CNF060 Indoor Section 265ANA060-- B Outdoor Section With FX4CNF060 Indoor Section Products Guide Specifications General