Bryant 265A warranty Accessory Usage Guideline, Applications

Page 5

ACCESSORY USAGE GUIDELINE

 

 

 

 

 

REQUIRED FOR LOW---AMBIENT

REQUIRED FOR

REQUIRED FOR

 

LONG LINE

SEA COAST

ACCESSORY

COOLING APPLICATIONS

APPLICATIONS*

APPLICATIONS

 

(Below 55° F)

 

(Over 80 Ft.)

(Within 2 miles)

 

 

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Accumulator

Standard

Standard

Standard

Compressor Start Assist Capacitor and Relay

Yes

Yes

No

Motor MasterControl or

Standard

Standard

Standard

Low---ambient Pressure Switch

 

 

 

 

 

 

 

Support Feet

Recommended

No

Recommended

Liquid Line Solenoid Valve

No

See Long--- Line Ap-

No

plication Guideline

 

 

 

 

 

 

 

Ball Bearing Fan Motor

Standard

Standard

Standard

* For tubing line sets between 80 and 200 ft. and/or 20 ft. vertical differential (250 ft. Total Equivalent Length), refer to Long---Line Application Guideline.

Accessory Description and Usage (Listed Alphabetically)

1. Ball-Bearing Fan Motor

6. Isolation Relay

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.

Usage Guideline:

Required on all units when MotorMasterr is used.

2. Compressor Start Assist - Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the following applications:

Long line

Low ambient cooling

Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil

Required for single-phase scroll compressors in the following applications:

Long line

Low ambient cooling

Suggested for all compressors in areas with a history of low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the compressor at each start-up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications. Required in long line applications.

Suggested in all commercial applications.

5. Evaporator Freeze Thermostat

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has been added.

7. Liquid-Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation. It is to be installed at the outdoor unit to control refrigerant off cycle migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump applications to control refrigerant off cycle migration in the heating mode. See Long Line Guideline.

8. Low-Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits. The control will maintain working head pressure at low-ambient temperatures down to 0_F when properly installed.

Usage Guideline:

ALow-Ambient Pressure Switch or MotorMasterr Low-Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).

9.MotorMasterr Low-Ambient Controller

Afan-speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to -20_F (-28.9_C), it maintains condensing temperature at 100_F ±10_F (37.8_C ± -12_C).

Usage Guideline:

A MotorMasterr Low Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).

Suggested for all commercial applications.

265A

5

Image 5
Contents Product Data Industry Leading Features / BenefitsISO Model Number NomenclatureUnit Size Series Physical DataAccessory Thermostats AccessoriesApplications Accessory Usage GuidelineOutdoor Air Temperature Sensor Charging Subcooling TXV-TYPE Expansion Device Electrical DataDimensions 265A Balance Point Worksheet Capacity Factory Standard Combination RatingsFurnace Model Enhance Rating030--B CAP**3017A 28,800 FV4BNB006 FE4ANB006FY4ANF042 036--B042--B FY4ANF048CAP**4821A 41,500 FY4ANB060 048--B060--B Detailed Cooling Capacities Cooling Indoor Model Capacity Power Furnace Model900 700800 FY4ANF030 FY4ANF036 1050 FY4ANF036 FY4ANF0421200 13501225 FY4ANF042 FY4ANF0481400 1575FY4ANB060 FY4ANF048 FE4ANB006 FE4ANF005 FV4BNB006 FV4BNF0051600 18001750 FE4ANB006 FV4BNB006 FY4ANB0602000 2250Heat Pump Heating Performance Total Integ Outdoor Coil Entering AIR Temperatures deg FFX4CNF030 CSPH*3612A 315A,JAV048090 FX4CNB,F042 CNPH*4221A 315A,JAV060110 FX4CNB,F048 CAP**4224A 315A,JAV066135 265ANA048-- B Outdoor Section With FX4CNF060 Indoor Section 265ANA060-- B Outdoor Section With FX4CNF060 Indoor Section Products Guide Specifications General