213R
DETAILED COOLING CAPACITIES - CONTINUED
EVAPORATOR |
|
|
|
|
|
|
|
|
| CONDENSER ENTERING AIR TEMPERATURES deg F |
|
|
|
|
|
| |||||||||
| AIR |
| 75 |
|
|
|
| 85 |
|
|
| 95 |
|
| 105 |
|
| 115 |
|
| 125 |
| |||
|
|
| Capacity |
| Total | Capacity | Total |
| Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total | |||||||||
CFM |
| EWB | MBtuh† |
| MBtuh† |
| MBtuh† | MBtuh† | MBtuh† | MBtuh† | |||||||||||||||
| System | System |
| System | System | System | System | ||||||||||||||||||
|
|
| Total | Sens |
| KW** | Total | Sens | KW** |
| Total | Sens | KW** | Total | Sens | KW** | Total | Sens | KW** | Total | Sens | KW** | |||
|
|
| ‡ |
| ‡ |
|
| ‡ | ‡ | ‡ | ‡ | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
| 72 | 69.61 | 35.82 |
| 4.46 |
| 67.00 | 34.80 | 4.88 |
| 64.31 | 33.76 | 5.34 | 61.53 | 32.71 | 5.85 | 58.62 | 31.62 | 6.41 | 55.59 | 30.48 | 7.02 | ||
|
| 67 | 63.45 | 44.44 |
| 4.39 |
| 61.04 | 43.40 | 4.81 |
| 58.55 | 42.34 | 5.27 | 55.98 | 41.25 | 5.78 | 53.30 | 40.13 | 6.33 | 50.49 | 38.96 | 6.93 | ||
1750 |
| 63 | 58.99 | 42.98 |
| 4.34 |
| 56.74 | 41.94 | 4.76 |
| 54.40 | 40.87 | 5.21 | 51.98 | 39.77 | 5.72 | 49.46 | 38.64 | 6.27 | 46.83 | 37.46 | 6.87 | ||
|
| 62 | 57.89 | 52.98 |
| 4.33 |
| 55.72 | 51.90 | 4.74 |
| 53.47 | 50.76 | 5.20 | 51.16 | 49.56 | 5.71 | 48.78 | 48.25 | 6.26 | 46.47 | 46.47 | 6.87 | ||
|
| 57 | 56.07 | 56.07 |
| 4.31 |
| 54.33 | 54.33 | 4.73 |
| 52.50 | 52.50 | 5.19 | 50.59 | 50.59 | 5.70 | 48.58 | 48.58 | 6.26 | 46.47 | 46.47 | 6.87 | ||
|
| 72 | 70.84 | 37.47 |
| 4.56 |
| 68.11 | 36.44 | 4.98 |
| 65.32 | 35.40 | 5.44 | 62.44 | 34.33 | 5.95 | 59.43 | 33.22 | 6.51 | 56.30 | 32.08 | 7.12 | ||
|
| 67 | 64.59 | 47.19 |
| 4.49 |
| 62.08 | 46.14 | 4.91 |
| 59.50 | 45.06 | 5.36 | 56.84 | 43.96 | 5.87 | 54.05 | 42.81 | 6.43 | 51.16 | 41.61 | 7.03 | ||
2000 |
| 63 | 60.09 | 45.56 |
| 4.44 |
| 57.75 | 44.51 | 4.85 |
| 55.31 | 43.42 | 5.31 | 52.80 | 42.30 | 5.82 | 50.19 | 41.14 | 6.37 | 47.48 | 39.94 | 6.97 | ||
|
| 62 | 59.16 | 56.66 |
| 4.43 |
| 56.93 | 55.47 | 4.84 |
| 54.66 | 54.15 | 5.30 | 52.43 | 52.43 | 5.81 | 50.30 | 50.30 | 6.37 | 48.06 | 48.06 | 6.98 | ||
|
| 57 | 58.28 | 58.28 |
| 4.42 |
| 56.43 | 56.43 | 4.84 |
| 54.48 | 54.48 | 5.30 | 52.44 | 52.44 | 5.81 | 50.31 | 50.31 | 6.37 | 48.06 | 48.06 | 6.98 | ||
|
| 72 | 71.75 | 39.04 |
| 4.66 |
| 68.93 | 38.00 | 5.07 |
| 66.06 | 36.95 | 5.53 | 63.10 | 35.87 | 6.05 | 60.01 | 34.75 | 6.61 | 56.79 | 33.60 | 7.21 | ||
|
| 67 | 65.44 | 49.83 |
| 4.58 |
| 62.86 | 48.76 | 5.00 |
| 60.20 | 47.66 | 5.46 | 57.46 | 46.53 | 5.97 | 54.61 | 45.35 | 6.52 | 51.65 | 44.13 | 7.13 | ||
2250 |
| 63 | 60.91 | 48.02 |
| 4.53 |
| 58.49 | 46.94 | 4.95 |
| 55.99 | 45.83 | 5.40 | 53.41 | 44.69 | 5.91 | 50.74 | 43.50 | 6.46 | 47.96 | 42.27 | 7.06 | ||
|
| 62 | 60.29 | 59.79 |
| 4.53 |
| 58.14 | 58.14 | 4.94 |
| 56.08 | 56.08 | 5.41 | 53.95 | 53.95 | 5.92 | 51.71 | 51.71 | 6.48 | 49.36 | 49.36 | 7.09 | ||
|
| 57 | 60.11 | 60.11 |
| 4.53 |
| 58.14 | 58.14 | 4.94 |
| 56.09 | 56.09 | 5.41 | 53.95 | 53.95 | 5.92 | 51.72 | 51.72 | 6.48 | 49.36 | 49.36 | 7.09 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
Cooling Indoor Model | Capacity |
| Power |
|
| Furnace Model |
|
|
|
|
|
|
|
|
|
|
|
| |||||||
*FC4DN(F,B)060 | 1.00 |
|
| 1.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| FK4DNB006 |
| 0.98 |
|
| 0.97 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CAR**6024A** | 0.97 |
|
| 0.97 |
|
| 315(A,J)AV066135 |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
CSRH*6012A** | 0.97 |
|
| 0.97 |
|
| 315(A,J)AV066135 |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
CAR**6024A** | 0.97 |
|
| 0.97 |
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
CNRH*6024A** | 0.97 |
|
| 0.97 |
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
CNRV*6024A** | 0.97 |
|
| 0.97 |
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
| ||||||
CSRH*6012A** | 0.97 |
|
| 0.97 |
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard
{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).
** System kw is total of indoor and outdoor unit kilowatts.
{{At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb. EWB — Entering Wet Bulb