HEAT PUMP HEATING PERFORMANCE - CONTINUED
INDOOR AIR |
|
|
|
|
|
|
|
|
|
|
| OUTDOOR COIL ENTERING AIR TEMPERATURES deg F |
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
| 7 |
|
|
| 17 |
|
| 27 |
|
| 37 |
|
| 47 |
|
| 57 |
|
| 67 |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Capacity | Total |
| Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total | ||||||||||
EDB |
| CFM | MBtuh | Sys- |
| MBtuh | Sys- | MBtuh | Sys- | MBtuh | Sys- | MBtuh | Sys- | MBtuh | Sys- | MBtuh | Sys- | MBtuh | Sys- | ||||||||||
|
|
| Total | In- | tem |
| Total | In- | tem | Total | In- | tem | Total | In- | tem | Total | In- | tem | Total | In- | tem | Total | In- | tem | Total | In- | tem | ||
|
|
| teg* | KW† |
| teg* | KW† | teg* | KW† | teg* | KW† | teg* | KW† | teg* | KW† | teg* | KW† | teg* | KW† | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
| 1750 | 25.42 | 23.39 | 3.96 |
| 30.92 | 28.42 | 4.10 | 36.95 | 33.69 | 4.27 | 43.61 | 38.73 | 4.45 | 51.09 | 46.49 | 4.67 | 59.02 | 59.02 | 4.84 | 66.24 | 66.24 | 5.05 | 65.65 | 65.65 | 5.01 | ||
65 |
| 2000 | 25.81 | 23.75 | 4.00 |
| 31.33 | 28.79 | 4.14 | 37.39 | 34.09 | 4.29 | 44.11 | 39.18 | 4.46 | 51.73 | 47.08 | 4.63 | 58.54 | 58.54 | 4.78 | 61.87 | 61.87 | 4.86 | 59.50 | 59.50 | 4.78 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2250 | 26.18 | 24.08 | 4.06 |
| 31.71 | 29.14 | 4.18 | 37.79 | 34.46 | 4.33 | 44.55 | 39.57 | 4.48 | 51.85 | 47.18 | 4.61 | 57.18 | 57.18 | 4.74 | 58.08 | 58.08 | 4.75 | 55.04 | 55.04 | 4.67 | ||
|
| 1750 | 24.91 | 22.92 | 4.11 |
| 30.49 | 28.02 | 4.28 | 36.53 | 33.30 | 4.46 | 43.11 | 38.29 | 4.65 | 50.48 | 45.93 | 4.87 | 58.78 | 58.78 | 5.06 | 66.16 | 66.16 | 5.29 | 67.06 | 67.06 | 5.30 | ||
70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2000 | 25.31 | 23.28 | 4.16 |
| 30.90 | 28.39 | 4.31 | 36.97 | 33.71 | 4.47 | 43.61 | 38.73 | 4.65 | 51.10 | 46.50 | 4.86 | 58.50 | 58.50 | 5.00 | 63.00 | 63.00 | 5.12 | 61.80 | 61.80 | 5.07 | |||
|
| 2250 | 25.67 | 23.62 | 4.22 |
| 31.26 | 28.73 | 4.35 | 37.37 | 34.07 | 4.51 | 44.05 | 39.12 | 4.67 | 51.64 | 46.99 | 4.83 | 58.08 | 58.08 | 4.98 | 60.16 | 60.16 | 5.02 | 57.77 | 57.77 | 4.95 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1750 | 24.36 | 22.41 | 4.27 |
| 30.00 | 27.57 | 4.45 | 36.07 | 32.89 | 4.64 | 42.61 | 37.85 | 4.85 | 49.92 | 45.43 | 5.08 | 58.19 | 58.19 | 5.31 | 66.02 | 66.02 | 5.54 | 68.87 | 68.87 | 5.63 | ||
75 |
| 2000 | 24.76 | 22.78 | 4.32 |
| 30.42 | 27.96 | 4.49 | 36.52 | 33.30 | 4.66 | 43.09 | 38.27 | 4.85 | 50.48 | 45.93 | 5.06 | 58.37 | 58.37 | 5.23 | 64.89 | 64.89 | 5.42 | 64.86 | 64.86 | 5.40 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2250 | 25.13 | 23.12 | 4.38 |
| 30.81 | 28.31 | 4.53 | 36.93 | 33.67 | 4.69 | 43.54 | 38.67 | 4.87 | 51.04 | 46.44 | 5.06 | 58.07 | 58.07 | 5.20 | 61.75 | 61.75 | 5.29 | 60.03 | 60.03 | 5.24 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Heating Indoor Model | Capacity |
|
| Power |
|
| Furnace Model |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
| *FC4DN(F,B)060 |
|
| 1.00 |
|
| 1.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| FK4DNB006 |
|
| 1.02 |
|
| 1.06 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| CAR**6024A** |
|
| 1.00 |
|
| 1.03 |
|
| 315(A,J)AV066135 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| CSRH*6012A** |
|
| 1.01 |
|
| 1.02 |
|
| 315(A,J)AV066135 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| CAR**6024A** |
|
| 1.00 |
|
| 1.02 |
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| CNRH*6024A** |
|
| 1.01 |
|
| 1.04 |
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| CNRV*6024A** |
|
| 1.01 |
|
| 1.04 |
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| CSRH*6012A** |
|
| 1.01 |
|
| 1.01 |
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
*The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.
{The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to obtain total system kilowatts.
EDB — Entering Dry Bulb
213R