Bryant 213R warranty Accessory Usage Guideline, ENT Applications Line Applications

Page 5

ACCESSORY USAGE GUIDELINE

 

REQUIRED FOR LOW---AMBI-

REQUIRED FOR LONG

REQUIRED FOR SEA

Accessory

ENT APPLICATIONS

LINE APPLICATIONS*

COAST APPLICATIONS

 

(Below 55° F)

(Over 80 Ft.)

(Within 2 miles)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Accumulator

No

No

No

Compressor Start Assist Capacitor and

Yes

Yes

No

Relay

 

 

 

Motor MasterControl

Yes

No

No

or Low---ambient Pressure Switch

 

 

 

Support Feet

Recommended

No

Recommended

Liquid Line Solenoid Valve

No

See Long--- Line Application

No

Guideline

 

 

 

Ball Bearing Fan Motor

Yes{

No

No

*For tubing line sets between 80 and 200 ft. and/or 20 ft. vertical differntial, refer to Residential Split---System Longline Application Guideline. { Required for Low---Ambient Controller (full modulation feature) and MotorMasterr Control only.

Accessory Description and Usage (Listed Alphabetically)

1. Ball-Bearing Fan Motor

6. Evaporator Freeze Thermostat

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.

Usage Guideline:

Required on all units when MotorMasterr is used.

2. Compressor Start Assist - Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the following applications:

Long line

Low ambient cooling

Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil

Required for single-phase scroll compressors in the following applications:

Long line

Low ambient cooling

Suggested for all compressors in areas with a history of low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the compressor at each start-up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications. Required in long line applications.

Suggested in all commercial applications.

5. Cycle Protector

The cycle protector is designed to prevent compressor short cycling. This control provides an approximate 5-minute delay after power to the compressor has been interrupted for any reason, including power outage, protector control trip, thermostat jiggling, or normal cycling.

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7. Isolation Relay

An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has been added.

8. Liquid-Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation. It is to be installed at the outdoor unit to control refrigerant off cycle migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump applications to control refrigerant off cycle migration in the heating mode. See Long Line Guideline.

9. Low-Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low-ambient temperatures down to 0_F when properly installed.

Usage Guideline:

ALow-Ambient Pressure Switch or MotorMasterr Low-Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).

10.MotorMasterr Low-Ambient Controller

Afan-speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to -20_F (-28.9_C), it maintains condensing temperature at 100_F ±10_F (37.8_C ± -12_C).

Usage Guideline:

A MotorMasterr Low Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).

Suggested for all commercial applications.

213R

5

Image 5
Contents Product Data Features / BenefitsModel Number Nomenclature Standard FeaturesUnit Size --- Series Physical DataAccessories Accessory ThermostatsENT Applications Line Applications Accessory Usage GuidelineOutdoor Air Temperature Sensor Weighted Sound Power DBA with Sound Hood Weighted Sound Power DBAElectrical Data Charging Subcooling TXV-TYPE Expansion DeviceDimensions 213RNA,G Balance Point Worksheet Series Combination RatingsCNRV*2414A 22,800 Unit Size CNRH*3617A 28,400 FK4DNB006 CAR**4224A 40,500 CSRH*4212A 41,000 CNRH*6024A 45,500 213RNA018---A Outdoor Section With FA4CNF018 Indoor Section Detailed Cooling Capacities213RNA024---A Outdoor Section With FA4CNC024 Indoor Section 875 213RNA030---A Outdoor Section With FA4CNF030 Indoor Section1000 11251050 213RNA036---A Outdoor Section With FC4DNF036 Indoor Section1200 1350213RNA042---A Outdoor Section With FC4DNF042 Indoor Section MBtuh† System Total Sens1225 1400213RNA048--A Outdoor Section With FC4DNF048 Indoor Section System MBtuh† Total Sens‡1600 18001750 213RNA060---A Outdoor Section With FC4DNF060 Indoor Section2000 2250FC4DNF018 FC4DNF024 FF1ENE018 FF1ENE024 FK4DNF001 FK4DNF002 Heat Pump Heating Performance213RNA018---A Outdoor Section With FA4CNF018 Indoor Section 213RNA024---A Outdoor Section With FA4CNC024 Indoor Section 213RNA030---A Outdoor Section With FA4CNF030 Indoor Section FK4DNF002 FK4DNF003 FK4DNF005 213RNA036---A Outdoor Section With FC4DNF036 Indoor SectionFK4DNB006 FK4DNF003 FK4DNF005 213RNA042---A Outdoor Section With FC4DNF042 Indoor SectionFK4DNB006 FK4DNF005 213RNA048-A Outdoor Section With FC4DNF048 Indoor SectionFK4DNB006 213RNA060---A Outdoor Section With FC4DNF060 Indoor SectionProducts Guide Specifications General