4-5. Electrical Service Guide

NOTICE − INCORRECT INPUT POWER can damage this welding power source. Phase to ground voltage shall not exceed +10% of rated input voltage.

NOTICE − Actual input voltage should not be 10% less than minimum and/or 10% more than maximum input voltages listed in table. If actual input voltage is outside this range, output may not be be available.

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda- tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.

 

 

 

Single-Phase

 

 

 

 

 

 

 

 

 

 

Input Voltage

208

230

 

400

 

460

575

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

60.8

54.6

 

29.7

 

25.4

19.9

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

 

 

 

 

Time-Delay 2

70

60

35

 

30

25

Normal Operating 3

80

80

45

 

40

30

Min Input Conductor Size In AWG/Kcmil 4

8

8

 

10

 

12

12

Max Recommended Input Conductor Length In Feet (Meters)

72

89

 

176

 

140

219

(22)

(27)

 

(54)

 

(43)

(67)

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil 4

8

8

 

10

 

12

12

 

 

 

Three-Phase

 

 

 

 

 

 

 

 

 

 

Input Voltage

208

230

 

400

 

460

575

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

40.4

36.1

 

20.6

 

17.8

14.1

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

 

 

 

 

Time-Delay 2

45

40

25

 

20

15

Normal Operating 3

60

50

30

 

25

20

Min Input Conductor Size In AWG/Kcmil 4

8

10

 

12

 

14

14

Max Recommended Input Conductor Length In Feet (Meters)

119

96

 

175

 

150

234

(36)

(29)

 

(53)

 

(46)

(71)

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil 4

10

10

 

12

 

14

14

Reference: 2005 National Electrical Code (NEC) (includes article 630)

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” (65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

OM-2251 Page 16

Image 20
Contents OM-2251217 661J ProcessesDescription File MultiprocessFrom Miller to You Table of Contents Page Symbol Usage Arc Welding HazardsElectric Shock can kill HOT Parts can cause severe burnsFumes and Gases can be hazardous ARC Rays can burn eyes and skinWelding can cause fire or explosion Flying Metal or Dirt can injure eyesWelding Wire can cause injury Fire or Explosion hazardFalling Unit can cause injury Moving Parts can cause injuryPrincipal Safety Standards California Proposition 65 WarningsEMF Information About Implanted Medical DevicesSymboles utilisés UNE Décharge Électrique peut entraîner la mortLE Soudage peut provoquer un in cendie ou une explosion DES Pièces Chaudes peuvent provoquer des brûlures gravesLES Fumées ET LES GAZ peuvent être dangereux LE Bruit peut endommager l’ouïe LES Bouteilles peuvent exploser si elles sont endommagéesRisque D’INCENDIE OU D’EXPLO- Sion LA Chute DE L’APPAREIL peut blesserLE Soudage À L’ARC risque de provoquer des interférences Proposition californienne 65 AvertissementsLES Fils DE Soudage peuvent provoquer des blessures En ce qui concerne les implants médicaux Principales normes de sécuritéInformation EMF OM-2251 Specifications CC ModeCV Mode − IntroductionDuty Cycle And Overheating 60% Duty CycleMinutes Welding Minutes Resting OverheatingSelecting a Location − InstallationDimensions And Weight Connecting 1-Phase Input Power =GND/PE Earth GroundConnecting 3-Phase Input Power Electrical Service Guide Single-Phase Input VoltageInput Amperes At Rated Output Min Grounding Conductor Size In AWG/KcmilWeld Output Terminals And Selecting Cable Sizes ARC Welding can cause Electromagnetic Interference350 ft 400 ft Put terminals Output ReceptaclesOptional Gas Valve Operation And Shielding Gas Connection Operation− Operation Front Panel ControlsMode Switch Settings Mode Meter Reading At Idle Meter Reading While WeldingMode Switch Setting Process Output Control Meter FunctionsLow OCV Stick Lift-Arc TIG ProcedureStick Start Procedure Blowing Out Inside Of Unit − Maintenance & TroubleshootingDo not remove case when blowing out inside of unit Troubleshooting Voltmeter/Ammeter Help Displays− Electrical Diagram Circuit Diagram219 863-C Parts Assembly MODPLG1 PLG13 Page Start Your Professional Welding Career Now Support ServiceYour distributor also gives To locate a Distributor or Service Agency visit Miller Electric Mfg. CoFor assistance in filing or settling claims, contact Your distributor and/or equipment manufacturer’s