3-Phase Units

Table 22 — 48HJ006 Fan Performance — Horizontal Discharge Units With Standard Motor

Single-Phase Units

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

0.1

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

 

1.2

 

1.4

 

1.6

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Bhp

 

Rpm

Bhp

 

Rpm

Bhp

 

Rpm

1500

741

 

0.38

798

 

0.43

895

 

0.54

990

 

0.67

1073

 

0.80

1154

 

0.95

1218

 

1.12

1295

 

1.36

1360

 

1.40

1600

783

 

0.45

838

 

0.51

933

 

0.63

1016

 

0.75

1102

 

0.90

1182

 

1.04

1251

 

1.20

1310

 

1.40

1385

 

1.49

1700

825

 

0.53

878

 

0.60

969

 

0.72

1049

 

0.84

1134

 

1.00

1206

 

1.14

1281

 

1.31

1342

 

1.48

1398

 

1.53

1800

885

 

0.63

942

 

0.73

1047

 

0.90

1139

 

1.05

1193

 

1.14

1276

 

1.30

1341

 

1.40

1413

 

1.55

1474

 

1.58

1900

928

 

0.73

982

 

0.83

1084

 

1.02

1160

 

1.11

1223

 

1.24

1301

 

1.38

1374

 

1.53

1437

 

1.62

1490

 

1.67

2000

971

 

0.84

1022

 

0.94

1121

 

1.12

1188

 

1.22

1254

 

1.36

1329

 

1.44

1396

 

1.66

1460

 

1.68

1509

 

1.77

2100

1015

 

0.97

1063

 

1.10

1140

 

1.18

1196

 

1.27

1272

 

1.45

1354

 

1.58

1413

 

1.75

1475

 

1.73

1529

 

1.92

2200

1060

 

1.10

1104

 

1.20

1159

 

1.23

1229

 

1.41

1306

 

1.53

1363

 

1.70

1434

 

1.81

1487

 

1.85

1554

 

2.07

2300

1104

 

1.25

1130

 

1.27

1196

 

1.37

1264

 

1.56

1340

 

1.66

1397

 

1.86

1459

 

1.88

1520

 

2.07

1576

 

2.24

2400

1138

 

1.30

 

 

 

1245

 

1.57

1305

 

1.63

1373

 

1.84

1440

 

1.95

1502

 

2.06

1552

 

2.24

1604

 

2.42

 

1174

 

1.37

2500

1183

 

1.43

1201

 

1.50

1284

 

1.65

1338

 

1.75

1402

 

1.99

1469

 

2.04

1524

 

2.24

1585

 

2.42

1638

 

2.60

 

 

 

 

 

 

 

 

 

 

 

3-Phase Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

0.1

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

 

1.2

 

1.4

 

1.6

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Bhp

 

Rpm

Bhp

 

Rpm

Bhp

 

Rpm

1500

741

 

0.38

798

 

0.43

895

 

0.54

990

 

0.67

1073

 

0.80

1154

 

0.95

1218

 

1.12

1295

 

1.36

1360

 

1.40

1600

783

 

0.45

838

 

0.51

933

 

0.63

1016

 

0.75

1102

 

0.90

1182

 

1.04

1251

 

1.20

1310

 

1.40

1385

 

1.49

1700

825

 

0.53

878

 

0.60

969

 

0.72

1049

 

0.84

1134

 

1.00

1206

 

1.14

1281

 

1.31

1342

 

1.48

1398

 

1.53

1800

885

 

0.63

942

 

0.73

1047

 

0.90

1139

 

1.05

1193

 

1.14

1276

 

1.30

1341

 

1.40

1413

 

1.55

1474

 

1.58

1900

928

 

0.73

982

 

0.83

1084

 

1.02

1160

 

1.11

1223

 

1.24

1301

 

1.38

1374

 

1.53

1437

 

1.62

1490

 

1.67

2000

971

 

0.84

1022

 

0.94

1121

 

1.12

1188

 

1.22

1254

 

1.36

1329

 

1.44

1396

 

1.66

1460

 

1.68

1509

 

1.77

2100

1015

 

0.97

1063

 

1.10

1140

 

1.18

1196

 

1.27

1272

 

1.45

1354

 

1.58

1413

 

1.75

1475

 

1.73

1529

 

1.92

2200

1060

 

1.10

1104

 

1.20

1159

 

1.23

1229

 

1.41

1306

 

1.53

1363

 

1.70

1434

 

1.81

1487

 

1.85

1554

 

2.07

2300

1104

 

1.25

1130

 

1.27

1196

 

1.37

1264

 

1.56

1340

 

1.66

1397

 

1.86

1459

 

1.88

1520

 

2.07

1576

 

2.24

2400

1138

 

1.30

1174

 

1.37

1245

 

1.57

1305

 

1.63

1373

 

1.84

1440

 

1.95

1502

 

2.06

1552

 

2.24

1604

 

2.42

2500

1183

 

1.43

1201

 

1.50

1284

 

1.65

1338

 

1.75

1402

 

1.99

1469

 

2.04

1524

 

2.24

1585

 

2.42

1638

 

2.60

Table 23 — 48HJ006 Fan Performance — Horizontal Discharge Units With High-Static Motor

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

0.4

 

 

0.6

 

0.8

 

1.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1500

789

 

0.40

896

 

0.53

990

 

0.67

1072

 

0.83

1153

 

1.00

1600

826

 

0.46

931

 

0.61

1020

 

0.75

1101

 

0.91

1178

 

1.09

1700

865

 

0.54

966

 

0.69

1051

 

0.84

1133

 

1.01

1205

 

1.18

1800

905

 

0.62

1002

 

0.78

1084

 

0.93

1163

 

1.10

1235

 

1.29

1900

945

 

0.72

1037

 

0.88

1119

 

1.04

1194

 

1.21

1266

 

1.40

2000

984

 

0.82

1072

 

0.98

1154

 

1.16

1226

 

1.33

1297

 

1.53

2100

1024

 

0.93

1108

 

1.10

1192

 

1.29

1259

 

1.47

1327

 

1.66

2200

1064

 

1.05

1145

 

1.22

1225

 

1.43

1294

 

1.62

1359

 

1.80

2300

1104

 

1.18

1183

 

1.36

1260

 

1.57

1330

 

1.78

1392

 

1.97

2400

1145

 

1.32

1222

 

1.45

1296

 

1.73

1365

 

1.94

1426

 

2.15

2500

1186

 

1.48

1262

 

1.68

1331

 

1.89

1400

 

2.12

1461

 

2.34

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

1.4

 

 

1.6

 

1.8

 

2.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1500

1221

 

1.17

1256

 

1.30

1283

 

1.32

1303

 

1.22

1345

 

1.34

1600

1252

 

1.27

1311

 

1.45

1340

 

1.58

1330

 

1.61

1373

 

1.77

1700

1278

 

1.37

1345

 

1.57

1397

 

1.76

1424

 

1.89

1470

 

2.08

1800

1303

 

1.48

1371

 

1.69

1433

 

1.90

1480

 

2.09

1528

 

2.30

1900

1330

 

1.59

1396

 

1.80

1460

 

2.03

1517

 

2.25

1566

 

2.47

2000

1362

 

1.73

1422

 

1.94

1485

 

2.16

1544

 

2.40

1594

 

2.64

2100

1393

 

1.87

1452

 

2.08

1510

 

2.31

1570

 

2.55

1620

 

2.80

2200

1423

 

2.02

1483

 

2.24

1538

 

2.46

1594

 

2.71

1645

 

2.98

2300

1454

 

2.18

1515

 

2.41

1571

 

2.64

1623

 

2.88

1676

 

3.17

2400

1485

 

2.36

1544

 

2.59

1604

 

2.84

1657

 

3.07

1710

 

3.38

2500

1518

 

2.55

1574

 

2.78

1633

 

3.03

1692

 

3.28

1746

 

3.61

LEGEND AND NOTES FOR TABLES 22 AND 23

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates field-supplied motor and drive required.

3.Motor drive range is 1020 to 1460 rpm for single-phase standard units, 1120 to 1585 for 3-phase standard units, and 1300 to 1685 for high-static units. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 1.30 for single-phase standard units, 2.40 for 3-phase standard motors, and 2.90 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on page 20 for additional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

7.Interpolation is permissible. Do not extrapolate.

27

Page 27
Image 27