Carrier 48HJD005-007 48HJ005 Fan Performance - Horizontal Discharge Units With Standard Motor

Models: 48HJD005-007

1 48
Download 48 pages 50.36 Kb
Page 26
Image 26
Table 20 — 48HJ005 Fan Performance — Horizontal Discharge Units With Standard Motor

Table 20 — 48HJ005 Fan Performance — Horizontal Discharge Units With Standard Motor

AIRFLOW

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

0.1

 

0.2

 

0.3

 

0.4

0.6

 

 

0.7

 

0.8

(Cfm)

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

569

 

0.18

641

 

0.23

701

 

0.29

761

 

0.34

859

 

0.46

901

 

0.52

943

 

0.58

1300

604

 

0.22

673

 

0.28

731

 

0.34

788

 

0.39

887

 

0.52

928

 

0.59

968

 

0.65

1400

640

 

0.27

705

 

0.33

761

 

0.39

817

 

0.45

914

 

0.59

955

 

0.66

996

 

0.72

1500

676

 

0.32

738

 

0.38

793

 

0.45

847

 

0.51

940

 

0.65

982

 

0.73

1024

 

0.81

1600

713

 

0.38

772

 

0.44

825

 

0.51

877

 

0.58

967

 

0.73

1009

 

0.81

1051

 

0.89

1700

750

 

0.45

806

 

0.51

857

 

0.59

908

 

0.66

997

 

0.81

1037

 

0.90

1077

 

1.01

1800

788

 

0.52

841

 

0.59

890

 

0.67

939

 

0.75

1026

 

0.91

1065

 

1.01

1104

 

1.07

1900

826

 

0.60

876

 

0.68

924

 

0.76

971

 

0.84

1056

 

1.01

1094

 

1.10

1132

 

1.18

2000

864

 

0.70

912

 

0.77

958

 

0.86

1004

 

0.94

1087

 

1.12

 

 

 

 

 

 

1125

 

1.21

1162

 

1.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

0.9

 

1.0

 

1.1

 

1.2

1.4

 

 

1.6

 

1.8

(Cfm)

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

987

 

0.64

1030

 

0.70

1068

 

0.79

1106

 

0.87

1134

 

0.98

1189

 

1.12

1245

 

1.21

1300

1006

 

0.71

1044

 

0.77

1086

 

0.84

1128

 

0.91

1183

 

1.10

 

 

 

1297

 

1.35

 

1226

 

1.23

1400

1033

 

0.79

1069

 

0.86

1104

 

0.93

1139

 

1.01

1218

 

1.14

1286

 

1.34

1320

 

1.48

1500

1060

 

0.88

1095

 

0.95

1129

 

1.02

1162

 

1.09

1228

 

1.24

1303

 

1.40

1343

 

1.60

1600

1087

 

1.01

1123

 

1.05

1156

 

1.13

1185

 

1.20

1250

 

1.35

1319

 

1.51

1382

 

1.68

1700

1114

 

1.07

1151

 

1.15

1183

 

1.23

1215

 

1.31

1276

 

1.48

1334

 

1.64

1398

 

1.80

1800

1141

 

1.17

1178

 

1.26

1211

 

1.35

1243

 

1.43

1303

 

1.61

1359

 

1.78

1418

 

1.95

1900

 

 

 

1204

 

1.37

1238

 

1.47

1271

 

1.56

1330

 

1.74

1386

 

1.93

1439

 

2.11

1168

 

1.28

 

2000

1197

 

1.39

1231

 

1.48

1265

 

1.59

1298

 

1.69

1358

 

1.89

1413

 

2.08

1466

 

2.27

Table 21 — 48HJ005 Fan Performance — Horizontal Discharge Units With High-Static Motor

AIRFLOW

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

0.2

0.4

 

 

 

0.6

 

 

0.8

 

1.0

(Cfm)

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

 

Bhp

Rpm

 

 

Bhp

Rpm

 

Bhp

1200

641

 

0.23

761

 

 

0.34

 

859

 

 

0.46

 

943

 

 

0.58

1030

 

0.70

1300

673

 

0.28

788

 

 

0.39

 

887

 

 

0.52

 

968

 

 

0.65

1044

 

0.77

1400

705

 

0.33

817

 

 

0.45

 

914

 

 

0.59

 

996

 

 

0.72

1069

 

0.86

1500

738

 

0.38

847

 

 

0.51

 

940

 

 

0.65

 

1024

 

 

0.81

1095

 

0.95

1600

772

 

0.44

877

 

 

0.58

 

967

 

 

0.73

 

1051

 

 

0.89

1123

 

1.05

1700

806

 

0.51

908

 

 

0.66

 

997

 

 

0.81

 

1077

 

 

1.01

1151

 

1.15

1800

841

 

0.59

939

 

 

0.75

 

1026

 

 

0.91

 

1104

 

 

1.07

1178

 

1.26

1900

876

 

0.68

971

 

 

0.84

 

1056

 

 

1.01

 

1132

 

 

1.18

1204

 

1.37

2000

912

 

0.77

1004

 

 

0.94

 

1087

 

 

1.12

 

1162

 

 

1.30

1231

 

1.48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

1.2

1.4

 

 

 

1.6

 

 

1.8

 

 

2.0

(Cfm)

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

 

Rpm

 

 

Bhp

 

Rpm

 

 

Bhp

Rpm

 

Bhp

1200

1106

 

0.87

1134

 

 

0.98

 

1189

 

1.12

 

1245

 

1.21

1292

 

1.35

1300

1128

 

0.91

1183

 

 

1.10

 

1226

 

1.23

 

1297

 

1.35

1346

 

1.51

1400

1139

 

1.01

1218

 

 

1.14

 

1286

 

1.34

 

1320

 

1.48

1370

 

1.65

1500

1162

 

1.09

1228

 

 

1.24

 

1303

 

1.40

 

1343

 

1.60

1393

 

1.79

1600

1185

 

1.20

1250

 

 

1.35

 

1319

 

1.51

 

1382

 

1.68

1434

 

1.88

1700

1215

 

1.31

1276

 

 

1.48

 

1334

 

1.64

 

1398

 

1.80

1451

 

2.01

1800

1243

 

1.43

1303

 

 

1.61

 

1359

 

1.78

 

1418

 

1.95

1471

 

2.18

1900

1271

 

1.56

1330

 

 

1.74

 

1386

 

1.93

 

1439

 

2.11

1493

 

2.36

2000

1298

 

1.69

1358

 

 

1.89

 

1413

 

2.08

 

1466

 

2.27

15.21

 

2.54

LEGEND AND NOTES FOR TABLES 20 AND 21

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates field-supplied motor and drive required.

3.Motor drive range is 840 to 1185 rpm for standard units; 1075 to 1455 rpm for high-static motors. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 1.20 for standard motors; 2.40 for high-static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or pre- mature motor failure. Unit warranty will not be affected. See Evaporator- Fan Motor Data tables on page 20 for additional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

7.Interpolation is permissible. Do not extrapolate.

26

Page 26
Image 26
Carrier 48HJD005-007 specifications 48HJ005 Fan Performance - Horizontal Discharge Units With Standard Motor