Carrier 48HJD005-007 48HJ005 Fan Performance - Vertical Discharge Units With Standard Motor

Models: 48HJD005-007

1 48
Download 48 pages 50.36 Kb
Page 22
Image 22
Table 12 — 48HJ005 Fan Performance — Vertical Discharge Units With Standard Motor

Table 12 — 48HJ005 Fan Performance — Vertical Discharge Units With Standard Motor

AIRFLOW

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

0.1

 

0.2

 

0.3

 

0.4

0.6

 

 

0.7

 

0.8

(Cfm)

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

596

 

0.20

665

 

0.25

722

 

0.31

779

 

0.36

872

 

0.48

915

 

0.54

957

 

0.60

1300

633

 

0.24

699

 

0.30

754

 

0.36

809

 

0.42

902

 

0.55

943

 

0.61

984

 

0.67

1400

672

 

0.30

735

 

0.36

788

 

0.42

840

 

0.48

933

 

0.62

972

 

0.69

1011

 

0.75

1500

711

 

0.35

770

 

0.42

822

 

0.49

873

 

0.55

963

 

0.69

1002

 

0.77

1041

 

0.84

1600

751

 

0.42

835

 

0.49

871

 

0.56

907

 

0.63

993

 

0.77

1033

 

0.85

1072

 

0.93

1700

791

 

0.49

873

 

0.57

907

 

0.65

941

 

0.72

1024

 

0.87

1064

 

0.96

1103

 

1.04

1800

831

 

0.58

881

 

0.66

929

 

0.74

976

 

0.81

1057

 

0.97

1095

 

1.06

1132

 

1.14

1900

872

 

0.67

919

 

0.75

965

 

0.84

1011

 

0.92

1091

 

1.08

1127

 

1.17

 

 

 

 

1162

 

1.25

2000

913

 

0.77

958

 

0.86

1002

 

0.95

1046

 

1.03

1125

 

1.21

1160

 

1.30

1195

 

1.38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

0.9

 

1.0

 

1.1

 

1.2

1.4

 

 

1.6

 

1.8

(Cfm)

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

993

 

0.65

1028

 

0.69

1056

 

0.72

1083

 

0.74

1134

 

0.80

1185

 

0.88

1331

 

0.99

1300

1021

 

0.74

1058

 

0.80

1090

 

0.85

1121

 

0.89

1171

 

0.94

1219

 

1.00

1268

 

1.10

1400

1049

 

0.82

1086

 

0.89

1120

 

0.96

1153

 

1.00

1210

 

1.12

1257

 

1.17

1307

 

1.25

1500

1077

 

0.92

1113

 

0.99

1147

 

1.06

1180

 

1.13

 

 

 

 

 

 

1339

 

1.43

1241

 

1.27

1295

 

1.37

1600

1107

 

1.00

1141

 

1.09

1174

 

1.17

 

 

 

1269

 

1.40

1326

 

1.54

1376

 

1.65

1207

 

1.25

 

1700

1137

 

1.12

1171

 

1.20

1203

 

1.29

1235

 

1.37

1296

 

1.53

1354

 

1.70

1407

 

1.84

1800

 

 

 

 

 

 

1233

 

1.41

1263

 

1.49

1323

 

1.67

1381

 

1.85

1436

 

2.02

1167

 

1.23

1202

 

1.32

 

1900

1197

 

1.35

1232

 

1.45

1263

 

1.54

1294

 

1.63

1351

 

1.81

1408

 

2.00

1463

 

2.19

2000

1229

 

1.48

1262

 

1.58

1294

 

1.68

1325

 

1.78

1362

 

1.97

1436

 

2.16

1489

 

2.36

Table 13 — 48HJ005 Fan Performance — Vertical Discharge Units With High-Static Motor

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

0.4

 

 

0.6

 

0.8

 

1.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

665

 

0.25

779

 

0.36

872

 

0.48

957

 

0.60

1028

 

0.69

1300

699

 

0.30

809

 

0.42

902

 

0.55

984

 

0.67

1058

 

0.80

1400

735

 

0.36

840

 

0.48

933

 

0.62

1011

 

0.75

1086

 

0.89

1500

770

 

0.42

873

 

0.55

963

 

0.69

1041

 

0.84

1113

 

0.99

1600

835

 

0.49

907

 

0.63

993

 

0.77

1072

 

0.93

1141

 

1.09

1700

873

 

0.57

941

 

0.72

1024

 

0.87

1103

 

1.04

1171

 

1.20

1800

881

 

0.66

976

 

0.81

1057

 

0.97

1132

 

1.14

1202

 

1.32

1900

919

 

0.75

1011

 

0.92

1091

 

1.08

1162

 

1.25

1232

 

1.45

2000

958

 

0.86

1046

 

1.03

1125

 

1.21

1195

 

1.38

1262

 

1.58

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

1.4

 

 

1.6

 

1.8

 

2.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1200

1083

 

0.74

1134

 

0.80

1185

 

0.88

1331

 

0.99

1374

 

1.09

1300

1121

 

0.89

1171

 

0.94

1219

 

1.00

1268

 

1.10

1309

 

1.21

1400

1153

 

1.00

1210

 

1.12

1257

 

1.17

1307

 

1.25

1349

 

1.37

1500

1180

 

1.13

1241

 

1.27

1295

 

1.37

1339

 

1.43

1382

 

1.57

1600

1207

 

1.25

1269

 

1.40

1326

 

1.54

1376

 

1.65

1420

 

1.81

1700

1235

 

1.37

1296

 

1.53

1354

 

1.70

1407

 

1.84

1452

 

2.02

1800

1263

 

1.49

1323

 

1.67

1381

 

1.85

1436

 

2.02

1482

 

2.22

1900

1294

 

1.63

1351

 

1.81

1408

 

2.00

1463

 

2.19

 

2000

1325

 

1.78

1362

 

1.97

1436

 

2.16

1489

 

2.36

 

LEGEND AND NOTES FOR TABLES 12 AND 13

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates field-supplied motor and drive required.

3.Motor drive range is 840 to 1185 rpm for standard motor; 1075 to 1455 rpm for high-static motor. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 1.2 for standard motor, 2.4 for high-static motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evapora- tor-Fan Motor Data tables on page 20 for additional information.

6.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

7.Interpolation is permissible. Do not extrapolate.

22

Page 22
Image 22
Carrier 48HJD005-007 specifications 48HJ005 Fan Performance - Vertical Discharge Units With Standard Motor