Table 33 — EconoMi$er Flash Code Identification
|
| FLASH CODE | CAUSE | ACTION TAKEN BY ECONOMI$ER |
|
| Constant On | Normal operation | Normal operation. |
|
| Constant Off | No power | No operation. |
|
| Continuous | CONFIG button pushed and held | Outdoor air damper is stroked fully open, then closed |
|
| Flash | between 3 and 9 seconds | (automatic test procedure takes 3 minutes to complete). |
Fault |
| Flash One | Control board fault | System shutdown. |
| Flash Two | Thermostat fault (i.e., Y2 without Y1) | System shutdown until corrected. | |
| Flash Three | Actuator fault | Revert to mechanical cooling only. | |
Critical |
|
|
| Continue operation with damper at minimum position. |
|
| Flash Four | Supply air temperature sensor fault | Continue operation with damper at minimum position. |
|
| Revert to mechanical cooling only. | ||
|
|
|
| |
|
| Flash Five | Outdoor air temperature sensor fault | Disable mechanical cooling lockout. |
|
|
|
| |
|
| Flash Six | Outdoor air humidity sensor fault | Continue operation with dry bulb or dry bulb differential switchover. |
Fault | Flash Seven |
| Continue operation with single enthalpy EconoMi$er | |
Return air temperature sensor fault | switchover or dry bulb EconoMi$er switchover (without | |||
Critical |
|
| humidity sensor). | |
|
|
|
| |
|
| Flash Eight | Return air humidity sensor fault | Continue operation with single enthalpy, differential dry |
|
| bulb, or dry bulb EconoMi$er switchover. | ||
Non- |
|
|
| |
| Flash Nine | Carbon Dioxide (CO2) sensor fault | Continue operation without ventilation control. | |
| Flash Ten | Onboard adjustment potentiometer fault | Continue operation with default potentiometer settings. | |
|
| |||
|
|
|
|
|
Table 34 — EconoMi$er Troubleshooting
| PROBLEM | POTENTIAL CAUSE | REMEDY |
Damper Does Not | Indoor (Evaporator) Fan is | Check to ensure that 24 vac is present at Terminal C1 (Common Power) | |
Open | Off | on the IFC (Indoor Evaporator Fan Contactor) or that 24 vac is present at | |
|
|
| the IFO (Indoor Evaporator Fan On) terminal. Check whether 24 vac is |
|
|
| present at PL |
|
|
| not present, check wiring (see unit label diagram). |
|
|
| Check proper thermostat connection to G on the connection board. |
|
| No Power to EconoMi$er | Check to ensure that 24 vac is present across Terminals 24 VAC and |
|
| Controller | 24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring |
|
|
| (see unit label diagram). If 24 vac is present, STATUS light should be on |
|
|
| constantly. |
|
| No Power to G Terminal | If IFM is on, check to ensure 24 vac is present on G Terminal of the |
|
|
| EconoMi$er controller. If 24 vac is not present, check wiring (see unit |
|
|
| label diagram). |
|
| Controller Fault | If STATUS light is flashing one flash, the EconoMi$er controller is |
|
|
| experiencing a fault condition. Cycle power to the controller. If condition |
|
|
| continues, replace the EconoMi$er controller. |
|
| Thermostat Fault | If STATUS light is flashing two flashes, the EconoMi$er controller senses |
|
|
| the thermostat is wired incorrectly. Check wiring between the thermostat |
|
|
| and the connection board in the electrical panel. The fault condition is |
|
|
| caused by Y2 being energized before Y1. |
|
| Actuator Fault | Check the wiring between the EconoMi$er controller and the actuator. |
|
|
| Hold CONFIG button between 3 and 10 seconds to verify the |
|
|
| actuator’s operation. (This process takes 3 minutes to complete.) |
EconoMi$er | Minimum Position Set | Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%) | |
Operation Limited to | Incorrectly | to 100% to verify operation, and then set to correct setting. | |
Minimum Position | EconoMi$er Changeover | Set at correct value. See Table 3. | |
|
| Set Point Set Too High or |
|
|
| Too Low |
|
|
| Supply Air Temperature | If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is |
|
| Sensor Faulty | faulty. Check wiring or replace sensor. |
|
| Outdoor Air Temperature | If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is |
|
| Sensor Faulty | faulty. Check wiring or replace sensor. |
Damper Position | Supply Air Low Limit | The | |
Less than Minimum | Strategy Controlling | position to be decreased. Refer to the | |
Position Set Point |
| setting of MIN POS (%). If correct, EconoMi$er is operating correctly. | |
Damper Does Not | CO2 Ventilation Strategy | If a CO2 sensor is being used, and the damper position is greater than | |
Return to Minimum | Controlling | minimum position, the ventilation control strategy is controlling. Refer to | |
Position |
| the | |
Damper Does Not | Damper Travel is | Check to ensure the damper is not blocked. | |
Close on Power Loss | Restricted |
| |
| LEGEND |
|
|
IFM | — Indoor Fan Motor |
|
|
PL | — Plug |
|
|