Table 33 — EconoMi$er Flash Code Identification

 

 

FLASH CODE

CAUSE

ACTION TAKEN BY ECONOMI$ER

 

 

Constant On

Normal operation

Normal operation.

 

 

Constant Off

No power

No operation.

 

 

Continuous

CONFIG button pushed and held

Outdoor air damper is stroked fully open, then closed

 

 

Flash

between 3 and 9 seconds

(automatic test procedure takes 3 minutes to complete).

Fault

 

Flash One

Control board fault

System shutdown.

 

Flash Two

Thermostat fault (i.e., Y2 without Y1)

System shutdown until corrected.

 

Flash Three

Actuator fault

Revert to mechanical cooling only.

Critical

 

 

 

Continue operation with damper at minimum position.

 

 

Flash Four

Supply air temperature sensor fault

Continue operation with damper at minimum position.

 

 

Revert to mechanical cooling only.

 

 

 

 

 

 

Flash Five

Outdoor air temperature sensor fault

Disable mechanical cooling lockout.

 

 

 

 

 

 

Flash Six

Outdoor air humidity sensor fault

Continue operation with dry bulb or dry bulb differential switchover.

Fault

Flash Seven

 

Continue operation with single enthalpy EconoMi$er

Return air temperature sensor fault

switchover or dry bulb EconoMi$er switchover (without

Critical

 

 

humidity sensor).

 

 

 

 

 

 

Flash Eight

Return air humidity sensor fault

Continue operation with single enthalpy, differential dry

 

 

bulb, or dry bulb EconoMi$er switchover.

Non-

 

 

 

 

Flash Nine

Carbon Dioxide (CO2) sensor fault

Continue operation without ventilation control.

 

Flash Ten

Onboard adjustment potentiometer fault

Continue operation with default potentiometer settings.

 

 

 

 

 

 

 

Table 34 — EconoMi$er Troubleshooting

 

PROBLEM

POTENTIAL CAUSE

REMEDY

Damper Does Not

Indoor (Evaporator) Fan is

Check to ensure that 24 vac is present at Terminal C1 (Common Power)

Open

Off

on the IFC (Indoor Evaporator Fan Contactor) or that 24 vac is present at

 

 

 

the IFO (Indoor Evaporator Fan On) terminal. Check whether 24 vac is

 

 

 

present at PL 6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is

 

 

 

not present, check wiring (see unit label diagram).

 

 

 

Check proper thermostat connection to G on the connection board.

 

 

No Power to EconoMi$er

Check to ensure that 24 vac is present across Terminals 24 VAC and

 

 

Controller

24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring

 

 

 

(see unit label diagram). If 24 vac is present, STATUS light should be on

 

 

 

constantly.

 

 

No Power to G Terminal

If IFM is on, check to ensure 24 vac is present on G Terminal of the

 

 

 

EconoMi$er controller. If 24 vac is not present, check wiring (see unit

 

 

 

label diagram).

 

 

Controller Fault

If STATUS light is flashing one flash, the EconoMi$er controller is

 

 

 

experiencing a fault condition. Cycle power to the controller. If condition

 

 

 

continues, replace the EconoMi$er controller.

 

 

Thermostat Fault

If STATUS light is flashing two flashes, the EconoMi$er controller senses

 

 

 

the thermostat is wired incorrectly. Check wiring between the thermostat

 

 

 

and the connection board in the electrical panel. The fault condition is

 

 

 

caused by Y2 being energized before Y1.

 

 

Actuator Fault

Check the wiring between the EconoMi$er controller and the actuator.

 

 

 

Hold CONFIG button between 3 and 10 seconds to verify the

 

 

 

actuator’s operation. (This process takes 3 minutes to complete.)

EconoMi$er

Minimum Position Set

Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)

Operation Limited to

Incorrectly

to 100% to verify operation, and then set to correct setting.

Minimum Position

EconoMi$er Changeover

Set at correct value. See Table 3.

 

 

Set Point Set Too High or

 

 

 

Too Low

 

 

 

Supply Air Temperature

If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is

 

 

Sensor Faulty

faulty. Check wiring or replace sensor.

 

 

Outdoor Air Temperature

If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is

 

 

Sensor Faulty

faulty. Check wiring or replace sensor.

Damper Position

Supply Air Low Limit

The supply-air temperature is less than 45 F, causing the minimum

Less than Minimum

Strategy Controlling

position to be decreased. Refer to the Start-Up instructions. Verify correct

Position Set Point

 

setting of MIN POS (%). If correct, EconoMi$er is operating correctly.

Damper Does Not

CO2 Ventilation Strategy

If a CO2 sensor is being used, and the damper position is greater than

Return to Minimum

Controlling

minimum position, the ventilation control strategy is controlling. Refer to

Position

 

the Start-Up instructions. EconoMi$er is operating correctly.

Damper Does Not

Damper Travel is

Check to ensure the damper is not blocked.

Close on Power Loss

Restricted

 

 

LEGEND

 

 

IFM

Indoor Fan Motor

 

 

PL

Plug

 

 

41

Page 41
Image 41
Carrier 48HJD005-007 specifications EconoMi$er Flash Code Identification, EconoMi$er Troubleshooting, Critical