Carrier 48HJD005-007 specifications Physical Data cont

Models: 48HJD005-007

1 48
Download 48 pages 50.36 Kb
Page 6
Image 6

Table 1 — Physical Data (cont)

BASE UNIT 48

HJE/F/H/K/M/N004

HJD/E/F/G/H/K/L/M/N005

 

HJD/E/F/G/H/K/L/M/N006

HJD/HJE/HJF007

FURNACE SECTION

 

 

 

 

 

 

 

 

Rollout Switch Cutout Temp (F)†

195

 

195

 

 

195

 

195

Burner Orifice Diameter (in. ...drill size)**

 

 

 

 

 

 

 

 

Natural Gas — Std

HJE .113...33

HJD .113...33

 

HJD .113...33

HJD .113...33

 

HJF .113...33

HJE .113...33

 

HJE .113...33

HJE .113...33

 

HJF .129...30

 

HJF .129...30

HJF .129...30

 

HJH .113...33

HJG .113...33

 

HJG .113...33

 

 

HJK .113...33

HJH .113...33

 

HJH .113...33

 

 

HJK .129...30

 

HJK .129...30

 

 

HJM .102...38

HJL .102...38

 

HJL .102...38

 

 

HJN .102...38

HJM .102...38

 

HJM .102...38

 

 

HJN .116...32

 

HJN .116...32

 

Liquid Propane — Alt††

HJE .089...43

HJD .089...43

 

HJD .089...43

HJD .089...43

 

HJF .089...43

HJE .089...43

 

HJE .089...43

HJE .089...43

 

HJF .102...38

 

HJF .102...38

HJF .102...38

 

HJH .082...45

HJG .089...43

 

HJG .089...43

 

 

HJK .082...45

HJH .089...43

 

HJH .089...43

 

 

HJK .102...38

 

HJK .102...38

 

 

HJM .082...45

HJL .082...45

 

HJL .082...45

 

 

HJN .082...45

HJM .082...45

 

HJM .082...45

 

Thermostat Heat Anticipator Setting (amps) 208/230/460 v

HJN .094...42

 

HJN .094...42

 

 

 

 

 

 

 

 

 

First Stage

.14

 

.14

 

 

.14

 

.14

Second Stage

.14

 

.14

 

 

.14

 

.14

Gas Input (Btuh)

 

 

 

 

 

 

 

 

First Stage/Second Stage

HJE 50,000/ 72,000

HJD

50,000/ 72,000

 

HJD

50,000/ 72,000

HJD

50,000/ 72,000

 

HJF 82,000/115,000

HJE

82,000/115,000

 

HJE

82,000/115,000

HJE

82,000/115,000

 

HJF 120,000/150,000

 

HJF 120,000/150,000

HJF 120,000/150,000

 

HJH*** —/ 72,000

HJG*** —/ 72,000

 

HJG*** —/ 72,000

 

 

HJK***—/115,000

HJH*** —/115,000

 

HJH*** —/115,000

 

 

HJK*** —/150,000

 

HJK*** —/150,000

 

 

HJM††† —/ 60,000

HJL††† —/ 60,000

 

HJL††† —/ 60,000

 

 

HJN††† —/ 90,000

HJM††† —/ 90,000

 

HJM†††—/ 90,000

 

 

HJN††† —/120,000

 

HJN††† —/120,000

 

Efficiency (Steady State) (%)

HJE 82

HJD 82

 

HJD 82

HJD 82

 

HJF 81

HJE 81

 

HJE 81

HJE 81

 

HJF 80

 

HJF 80

HJF 80

 

HJH 82

HJG 82

 

HJG 82

 

 

HJK 81

HJH 81

 

HJH 81

 

 

HJK 80

 

HJK 80

 

 

HJM 81

HJL 81

 

HJL 81

 

 

HJN 81

HJM 81

 

HJM 81

 

 

HJN 82

 

HJN 82

 

Temperature Rise Range

HJE 15-45

HJD 15-45

 

HJD 15-45

HJD 15-45

 

HJF 55-85

HJE 35-65

 

HJE 35-65

HJE 35-65

 

HJF 50-80

 

HJF 50-80

HJF 50-80

 

HJH 15-45

HJG 15-45

 

HJG 15-45

 

 

HJK 55-85

HJH 35-65

 

HJH 35-65

 

 

HJK 50-80

 

HJK 50-80

 

 

HJM 20-50

HJL 20-50

 

HJL 20-50

 

 

HJN 30-60

HJM 30-60

 

HJM 30-60

 

Manifold Pressure (in. wg)

HJN 40-70

 

HJN 40-70

 

 

 

 

 

 

 

 

 

Natural Gas — Std

3.5

 

3.5

 

 

3.5

 

3.5

Liquid Propane — Alt††

3.5

 

3.5

 

 

3.5

 

3.5

Maximum Static Pressure (in. wg)

1.0

 

1.0

 

 

1.0

 

1.0

Field Gas Connection Size (in.)

1/2

 

1/2

 

 

1/2

 

1/2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

Standard Compressor Internal Relief

 

 

450 ± 50

 

 

 

Cutout

 

 

 

428

 

 

 

Reset (Auto.)

 

 

 

320

 

 

 

LOSS-OF-CHARGE SWITCH/LOW-PRESSURE

 

 

 

 

 

 

 

 

SWITCH (Liquid LIne) (psig)

 

 

 

 

 

 

 

 

Cutout

 

 

 

7 ± 3

 

 

 

Reset (Auto.)

 

 

22 ± 5

 

 

 

FREEZE PROTECTION THERMOSTAT

 

 

 

 

 

 

 

 

Opens (F)

 

 

30 ± 5

 

 

 

Closes (F)

 

 

45 ± 5

 

 

 

OUTDOOR-AIR INLET SCREENS

 

 

Cleanable

 

 

 

Quantity...Size (in.)

 

 

1...20 x 24 x 1

 

 

 

RETURN-AIR FILTERS

 

 

Throwaway

 

 

 

Quantity...Size (in.)

 

 

2...16 x 25 x 2

 

 

 

LEGEND

Bhp — Brake Horsepower

*Single phase/three phase. †Indicates automatic reset.

**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners. 48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005- 007 (150,000 Btuh Heat input) units have 3 burners.

††An LP kit is available as an accessory.

Three-phase standard models have heating inputs as shown. Single-phase standard models have one-stage heating with heating input values as follows:

48HJE004, 48HJD005,006 — 72,000 Btuh

48HJF004, 48HJE005,006 — 115,000 Btuh 48HJF005,006 — 150,000 Btuh

***California compliant three-phase models.

†††California SCAQMD compliant low NOx models have combustion products that are controlled to 40 nanograms per joule or less.

6

Page 6
Image 6