Table 31 — Heating Service Analysis

PROBLEM

CAUSE

REMEDY

Burners will not

Misaligned spark electrodes.

Check flame ignition and sensor electrode positioning. Adjust as

ignite.

 

needed.

 

No gas at main burners.

Check gas line for air purge as necessary. After purging gas line of

 

 

air, allow gas to dissipate for at least 5 minutes before attempting to

 

 

relight unit.

 

 

Check gas valve.

 

Water in gas line.

Drain water and install drip leg to trap water.

 

No power to furnace.

Check power supply, fuses, wiring, and circuit breaker.

 

No 24 v power supply to control circuit.

Check transformer. Transformers with internal overcurrent protection

 

 

require a cool-down period before resetting. Check 24-v circuit

 

 

breaker; reset if necessary.

 

Miswired or loose connections.

Check all wiring and wirenut connections.

 

Burned-out heat anticipator in thermostat.

Replace thermostat.

 

Broken thermostat wires.

Run continuity check. Replace wires, if necessary.

Inadequate heating.

Dirty air filter.

Clean or replace filter as necessary.

 

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for input. If too low,

 

 

increase manifold pressure or replace with correct orifices.

 

Unit undersized for application.

Replace with proper unit or add additional unit.

 

Restricted airflow.

Clean filter, replace filter, or remove any restrictions.

 

Blower speed too low.

Use high speed tap, increase fan speed, or install optional blower, as

 

 

suitable for individual units, Adjust pulley.

 

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator settings, and

 

 

temperature rise of unit. Adjust as needed.

 

Too much outdoor air.

Adjust minimum position.

 

 

Check economizer operation.

Poor flame

Incomplete combustion (lack of

Check all screws around flue outlets and burner compartment.

characteristics.

combustion air) results in:

Tighten as necessary.

 

Aldehyde odors, CO (carbon monoxide),

Cracked heat exchanger.

 

sooting flame, or floating flame.

Overfired unit — reduce input, change orifices, or adjust gas line or

 

 

 

 

manifold pressure.

 

 

Check vent for restriction. Clean as necessary.

 

 

Check orifice to burner alignment.

Burners will not

Unit is locked into Heating mode for a

Wait until mandatory one minute time period has elapsed or reset

turn off.

one minute minimum.

power to unit.

Table 32 — Durablade Economizer Service Analysis

PROBLEM

CAUSE

 

REMEDY

Damper does not

Evaporator fan not on.

Check wiring between G on connection board and evaporator-fan

open.

 

contactor.

 

 

No power to economizer motor.

1.

Check that SW3 is making proper contact with the damper blade.

 

 

 

2.

Check continually across R1 coil. If not connect, replace relay R1.

 

 

 

3.

Check diode D18. If diode is not functioning properly, replace D18.

 

 

 

4.

Check wiring in economizer relay pack. (See unit label diagram.)

 

 

Economizer motor failure.

If there is 24 vac power at the motor terminals, but motor is not operat-

 

 

 

ing, replace motor.

Economizer

OAT or EC set too high.

1.

Set at correct temperature (3 F below indoor space temperature).

operation limited to

 

2.

Check OAT or EC by setting set point above outdoor temperature or

minimum position.

 

 

humidity level. If switch does not close, replace OAT or EC.

 

 

Check wiring of economizer relay packs.

1.

Check continuity across relay R2 coil. If not connected, replace R2

 

 

 

 

relay.

 

 

 

2.

Check continuity across relay R3 coil. If not connected, replace R3

 

 

 

 

relay.

 

 

Check SAT.

If supply-air temperature is over 57 F, switch T2 should be closed. If

 

 

 

not, replace SAT.

Damper does not

Incorrect wiring or wiring defects.

1.

Check switches 2 and 4. If non-operational, replace.

close.

 

2.

Check diode D19. If diode D19 is not functioning properly, replace.

 

 

 

3.

Check wiring on economizer and on economizer relay pack. (See

 

 

 

 

unit label diagram.)

 

 

Check SAT.

If supply-air thermostat is below 52 F, switch T1 should be closed. If

 

 

 

not, replace SAT.

 

 

Economizer motor failure.

If there is 24 vac power at motor terminals, but motor is not operating,

 

 

 

replace the motor.

LEGEND

 

 

 

EC — Enthalpy Control

 

 

OAT — Outdoor-Air Thermostat

 

 

SAT — Supply-Air Thermostat

 

 