Carrier 48HJD005-007 specifications Make Electrical Connections

Models: 48HJD005-007

1 48
Download 48 pages 50.36 Kb
Page 4
Image 4
Step 7 — Make Electrical Connections

NOTES:

1.

Place unit on curb as close as possible to the duct end.

2.

Dimension in ( ) is in millimeters.

3.Hook rigging shackles through holes in base rail as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit cen- ter of gravity. Use wooden top skid when rigging to prevent rig- ging straps from damaging unit.

4.Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.

All panels must be in place when rigging.

UNIT

MAX

“A”

“B”

“C”

WEIGHT

48HJ

 

 

 

 

 

 

lb

kg

in.

mm

in.

mm

in.

mm

 

004

530

240

73.69

1872

35.50

902

33.31

847

005

540

245

73.69

1872

35.50

902

33.31

847

006

560

254

73.69

1872

35.50

902

33.31

847

007

615

279

73.69

1872

35.50

902

33.31

847

Fig. 4 — Rigging Details

Step 5 — Install Flue Hood — Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood in location shown in Fig. 5 and 6.

For units being installed in California Air Quality Manage- ment Districts which require NOx emissions of 40 nanograms/ joule or less, kit CRLOWNOX001A00 must be installed.

Step 6 — Install Gas Piping — Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 instal- lation codes for gas burning appliances.

For natural gas applications, gas pressure at unit gas con- nection must not be less than 4 in. wg or greater than 13 in. wg while the unit is operating. On 48HJ005-007 high-heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.

Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

Support gas piping as shown in the table in Fig. 7. For ex- ample, a 3/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 3 support beams, and a 48-ft long pipe would have a minimum of 6 support beams.

See Fig. 7 for typical pipe guide and locations of external manual gas shutoff valve.

Step 7 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electri- cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com- partment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Associa- tion), latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for per- sonal injury of others.

FIELD POWER SUPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power sup- ply, the transformer must be rewired by moving the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformer.

Refer to unit label diagram for additional information. Pigtails are provided for field service. Use factory-supplied splices or UL (Underwriters’ Laboratories) approved copper connector.

When installing units, provide a disconnect per NEC.

All field wiring must comply with NEC and local requirements.

4

Page 4
Image 4
Carrier 48HJD005-007 specifications Make Electrical Connections