Carrier 48HJD005-007 C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet

Models: 48HJD005-007

1 48
Download 48 pages 50.36 Kb
Page 11
Image 11
Table 2C — 48HJ High-Static Motor Units Without Electrical Convenience Outlet

Table 2C — 48HJ High-Static Motor Units Without Electrical Convenience Outlet

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

OFM

IFM

DISCONNECT

VOLTAGE

RANGE

(each)

FAN MOTOR

SUPPLY

48HJ

 

 

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

 

LRA

 

 

 

 

208/230-3-60

187

254

10.3

77.0

0.7

5.8

0.6

19.4/19.4

25/25

19/19

 

120/120

004

460-3-60

414

508

5.1

39.0

0.4

2.6

0.3

9.4

15

9

 

60

 

575-3-60

518

632

4.2

31.0

0.4

2.6

0.3

7.7

15

8

 

48

 

208/230-3-60

187

254

13.5

99.0

0.7

5.8

0.6

23.4/23.4

30/30

23/23

 

142/142

005

460-3-60

414

508

7.4

49.5

0.4

2.6

0.3

12.3

15

12

 

71

 

575-3-60

518

632

5.8

40.0

0.4

2.6

0.3

9.7

15

9

 

57

 

208/230-3-60

187

254

17.3

123.0

1.5

7.5

0.6

30.6/30.6

35/35

30/30

 

187/187

006

460-3-60

414

508

9.0

62.0

0.8

3.4

0.3

15.5

20

15

 

94

 

575-3-60

518

632

7.1

50.0

0.8

3.4

0.3

12.2

15

12

 

76

 

208/230-3-60

187

254

20.5

156.0

1.4

7.5

0.6

30.6/30.6

35/35

30/30

 

187/187

007

460-3-60

414

508

9.6

70.0

0.6

3.4

0.3

15.5

20

15

 

94

 

575-3-60

518

632

7.7

56.0

0.6

3.4

0.3

12.2

15

12

 

76

Table 2D — 48HJ High-Static Motor Units With Electrical Convenience Outlet

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

OFM

IFM

DISCONNECT

VOLTAGE

RANGE

(each)

FAN MOTOR

SUPPLY

48HJ

 

 

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

LRA

 

 

 

208/230-3-60

187

254

10.3

77.0

0.7

5.8

0.6

25.4/25.4

30/30

25

124/124

004

460-3-60

414

508

5.1

39.0

0.4

2.6

0.3

12.1

15

12

63

 

575-3-60

518

632

4.2

31.0

0.4

2.6

0.3

9.8

15

10

50

 

208/230-3-60

187

254

13.5

99.0

0.7

5.8

0.6

29.4/29.4

35/35

29

146/146

005

460-3-60

414

508

7.4

49.5

0.4

2.6

0.3

15.0

20

14

73

 

575-3-60

518

632

5.8

40.0

0.4

2.6

0.3

11.8

15

11

59

 

208/230-3-60

187

254

17.3

123.0

1.5

7.5

0.6

36.6/36.6

40/40

36

192/192

006

460-3-60

414

508

9.0

62.0

0.8

3.4

0.3

18.2

20

18

96

 

575-3-60

518

632

7.1

50.0

0.8

3.4

0.3

14.4

20

14

77

 

208/230-3-60

187

254

20.5

156.0

1.4

7.5

0.6

40.5/40.5

45/45

39

224/224

007

460-3-60

414

508

9.6

70.0

0.6

3.4

0.3

18.7

25

18

104

 

575-3-60

518

632

7.7

56.0

0.6

3.4

0.3

15.0

20

15

89

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance= 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

11

Page 11
Image 11
Carrier 48HJD005-007 specifications C - 48HJ High-Static Motor Units Without Electrical Convenience Outlet