Table 5A — 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor

Table 5A — 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor

STANDARD MOTOR*

UNIT

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

48HJ

0

1/2

1

11/2

2

21/2

3

31/2

4

41/2

5

51/2

6

004

1090

1055

1025

990

960

925

890

860

825

795

760

005

1185

1150

1115

1080

1045

1015

980

945

910

875

840

006

1460

1425

1385

1350

1315

1275

1240

1205

1165

1130

1095

1055

1020

(single-phase)

 

 

 

 

 

 

 

 

 

 

 

 

 

006 (3-phase)

1585

1540

1490

1445

1400

1350

1305

1260

1210

1165

1120

and 007

 

 

 

 

 

 

 

 

 

 

 

 

 

*Approximate fan rpm shown (standard motor/drive).

Table 5B — 48HJ Fan Rpm at Motor Pulley Setting With High Static Motor

HIGH-STATIC MOTOR

UNIT

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

48HJ

0

1/2

1

11/2

2

 

21/2

3

31/2

 

4

41/2

5

51/2

6

004

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

005

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

006

1685

1589

1557

1525

1493

 

1460

1428

1396

 

1364

1332

1300

007

1685

1589

1557

1525

1493

 

1460

1428

1396

 

1364

1332

1300

Table 6 — Evaporator-Fan Motor Data — Standard Motor

UNIT

UNIT

MAXIMUM

MAXIMUM

UNIT VOLTAGE

MAXIMUM

48HJ

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

 

 

Single

1.20

1000

208/230

5.4

004

 

 

 

208/230

5.4

Three

1.20

1000

460

2.4

 

 

 

 

 

575

2.4

 

Single

1.20

1000

208/230

5.4

005

 

 

 

208/230

5.4

Three

1.20

1000

460

2.4

 

 

 

 

 

575

2.4

 

Single

1.30

1650

208/230

9.7

006

 

 

 

208/230

6.4

Three

2.40

2120

460

2.9

 

 

 

 

 

575

2.9

 

 

 

 

208/230

6.4

007

Three

2.40

2120

460

2.9

 

 

 

 

575

2.9

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected.

Table 7 — Evaporator-Fan Motor Data — High-Static Motors

UNIT

UNIT

MAXIMUM

MAXIMUM

UNIT VOLTAGE

MAXIMUM

48HJ

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

 

 

 

 

 

208/230

6.4

004

Three

2.40

2120

460

2.9

 

 

 

 

575

2.9

 

 

 

 

208/230

6.4

005

Three

2.40

2120

460

2.9

 

 

 

 

575

2.9

 

 

 

 

208/230

7.9

006

Three

2.90

2615

460

3.6

 

 

 

 

575

3.6

 

 

 

 

208/230

6.4

007

Three

2.90

2615

460

3.6

 

 

 

 

575

3.6

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected.

20

Page 20
Image 20
Carrier 48HJD005-007 specifications A - 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor