Table 5A — 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor
STANDARD MOTOR*
UNIT |
|
|
|
| MOTOR PULLEY TURNS OPEN |
|
|
|
| |||||
48HJ | 0 | 1/2 | 1 | 11/2 | 2 | 21/2 | 3 | 31/2 | 4 | 41/2 | 5 | 51/2 | 6 | |
004 | 1090 | 1055 | 1025 | 990 | 960 | 925 | 890 | 860 | 825 | 795 | 760 | — | — | |
005 | 1185 | 1150 | 1115 | 1080 | 1045 | 1015 | 980 | 945 | 910 | 875 | 840 | — | — | |
006 | 1460 | 1425 | 1385 | 1350 | 1315 | 1275 | 1240 | 1205 | 1165 | 1130 | 1095 | 1055 | 1020 | |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
006 | 1585 | 1540 | 1490 | 1445 | 1400 | 1350 | 1305 | 1260 | 1210 | 1165 | 1120 | — | — | |
and 007 | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
*Approximate fan rpm shown (standard motor/drive).
Table 5B — 48HJ Fan Rpm at Motor Pulley Setting With High Static Motor
UNIT |
|
|
|
|
| MOTOR PULLEY TURNS OPEN |
|
|
|
|
| ||||
48HJ | 0 | 1/2 | 1 | 11/2 | 2 |
| 21/2 | 3 | 31/2 |
| 4 | 41/2 | 5 | 51/2 | 6 |
004 | 1455 | 1423 | 1392 | 1360 | 1328 |
| 1297 | 1265 | 1233 |
| 1202 | 1170 | 1138 | 1107 | 1075 |
005 | 1455 | 1423 | 1392 | 1360 | 1328 |
| 1297 | 1265 | 1233 |
| 1202 | 1170 | 1138 | 1107 | 1075 |
006 | 1685 | 1589 | 1557 | 1525 | 1493 |
| 1460 | 1428 | 1396 |
| 1364 | 1332 | 1300 | — | — |
007 | 1685 | 1589 | 1557 | 1525 | 1493 |
| 1460 | 1428 | 1396 |
| 1364 | 1332 | 1300 | — | — |
Table 6 — Evaporator-Fan Motor Data — Standard Motor
UNIT | UNIT | MAXIMUM | MAXIMUM | UNIT VOLTAGE | MAXIMUM | |
48HJ | PHASE | CONTINUOUS BHP* | OPERATING WATTS* | AMP DRAW | ||
| ||||||
| Single | 1.20 | 1000 | 208/230 | 5.4 | |
004 |
|
|
| 208/230 | 5.4 | |
Three | 1.20 | 1000 | 460 | 2.4 | ||
| ||||||
|
|
|
| 575 | 2.4 | |
| Single | 1.20 | 1000 | 208/230 | 5.4 | |
005 |
|
|
| 208/230 | 5.4 | |
Three | 1.20 | 1000 | 460 | 2.4 | ||
| ||||||
|
|
|
| 575 | 2.4 | |
| Single | 1.30 | 1650 | 208/230 | 9.7 | |
006 |
|
|
| 208/230 | 6.4 | |
Three | 2.40 | 2120 | 460 | 2.9 | ||
| ||||||
|
|
|
| 575 | 2.9 | |
|
|
|
| 208/230 | 6.4 | |
007 | Three | 2.40 | 2120 | 460 | 2.9 | |
|
|
|
| 575 | 2.9 |
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected.
Table 7 — Evaporator-Fan Motor Data — High-Static Motors
UNIT | UNIT | MAXIMUM | MAXIMUM | UNIT VOLTAGE | MAXIMUM | |
48HJ | PHASE | CONTINUOUS BHP* | OPERATING WATTS* | AMP DRAW | ||
| ||||||
|
|
|
| 208/230 | 6.4 | |
004 | Three | 2.40 | 2120 | 460 | 2.9 | |
|
|
|
| 575 | 2.9 | |
|
|
|
| 208/230 | 6.4 | |
005 | Three | 2.40 | 2120 | 460 | 2.9 | |
|
|
|
| 575 | 2.9 | |
|
|
|
| 208/230 | 7.9 | |
006 | Three | 2.90 | 2615 | 460 | 3.6 | |
|
|
|
| 575 | 3.6 | |
|
|
|
| 208/230 | 6.4 | |
007 | Three | 2.90 | 2615 | 460 | 3.6 | |
|
|
|
| 575 | 3.6 |
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected.
20