Table 8 — Motor Nominal Horsepower

UNIT 48HJ

MOTOR

NOMINAL HORSEPOWER

004

All

1.00

005

All

1.00

006

Single Phase

1.50

Three Phase

2.00

 

007

All

2.00

Table 9 — Outdoor Sound Power (Total Unit)

UNIT

ARI

 

 

 

OCTAVE BANDS

 

 

 

48HJ

RATING

63

125

250

500

1000

2000

4000

8000

(Bels)

 

 

 

 

 

 

 

 

 

004,005

7.6

55.9

66.0

64.0

66.2

68.4

64.5

61.7

57.3

006,007

8.0

59.1

68.9

68.7

71.9

74.0

68.9

65.7

59.0

LEGEND

ARI — Air Conditioning and Refrigeration Institute

Bels — Sound Levels (1 bel = 10 decibels)

Table 10 — 48HJ004 Fan Performance — Vertical Discharge Units With Standard Motor

AIRFLOW

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

0.1

 

0.2

 

0.3

 

0.4

 

0.5

 

0.6

(Cfm)

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

581

 

0.12

673

 

0.18

736

 

0.22

805

 

0.25

865

 

0.29

911

 

0.34

1000

644

 

0.19

709

 

0.22

782

 

0.28

835

 

0.30

900

 

0.35

937

 

0.38

1100

687

 

0.22

746

 

0.26

806

 

0.30

867

 

0.35

929

 

0.40

964

 

0.40

1200

733

 

0.26

785

 

0.32

843

 

0.35

903

 

0.41

960

 

0.47

994

 

0.50

1300

754

 

0.29

826

 

0.38

891

 

0.43

942

 

0.48

991

 

0.53

1047

 

0.60

1400

810

 

0.35

868

 

0.45

937

 

0.51

984

 

0.57

1032

 

0.62

1067

 

0.67

1500

841

 

0.42

911

 

0.53

985

 

0.61

1029

 

0.66

1073

 

0.72

1109

 

0.77

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

0.7

 

0.8

 

0.9

 

1.0

 

1.1

 

1.2

(Cfm)

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

957

 

0.39

988

 

0.43

1039

 

0.47

1061

 

0.51

1083

 

0.54

1105

 

0.58

1000

992

 

0.44

1039

 

0.49

1061

 

0.55

1088

 

0.60

1111

 

0.66

1136

 

0.72

1100

1013

 

0.49

1068

 

0.55

1091

 

0.61

1109

 

0.66

1127

 

0.73

1145

 

0.80

1200

1045

 

0.56

1090

 

0.64

1109

 

0.68

1156

 

0.73

1203

 

0.81

1250

 

0.86

1300

1075

 

0.64

1122

 

0.70

1152

 

0.76

1190

 

0.82

1228

 

0.87

1266

 

0.94

1400

1110

 

0.73

1160

 

0.78

1181

 

0.83

1237

 

0.88

1293

 

0.94

1349

 

0.99

1500

1150

 

0.78

1190

 

0.84

1225

 

0.89

1271

 

0.95

1371

 

1.00

1383

 

1.05

Table 11 — 48HJ004 Fan Performance — Vertical Discharge Units With High-Static Motor

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

0.4

 

 

0.6

 

0.8

 

1.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

673

 

0.18

805

 

0.25

911

 

0.34

988

 

0.43

1061

 

0.47

1000

709

 

0.22

835

 

0.30

937

 

0.38

1039

 

0.49

1086

 

0.55

1100

746

 

0.28

867

 

0.35

964

 

0.40

1068

 

0.55

1109

 

0.61

1200

785

 

0.32

903

 

0.41

994

 

0.50

1090

 

0.64

1156

 

0.68

1300

826

 

0.38

942

 

0.48

1047

 

0.60

1122

 

0.70

1190

 

0.76

1400

868

 

0.45

984

 

0.57

1087

 

0.67

1160

 

0.84

1237

 

0.85

1500

911

 

0.53

1029

 

0.66

1109

 

0.77

1190

 

1.00

1271

 

0.95

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

1.4

 

 

1.6

 

1.8

 

2.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

900

1105

 

0.57

1140

 

0.63

1170

 

0.68

1198

 

0.73

1224

 

0.77

1000

1136

 

0.63

1172

 

0.69

1203

 

0.75

1232

 

0.80

1258

 

0.86

1100

1145

 

0.67

1181

 

0.73

1213

 

0.80

1242

 

0.85

1268

 

0.91

1200

1210

 

0.74

1248

 

0.81

1282

 

0.88

1312

 

0.94

1340

 

1.01

1300

1266

 

0.84

1306

 

0.92

1341

 

1.00

1373

 

1.07

1402

 

1.14

1400

1349

 

0.93

1391

 

1.02

1429

 

1.11

1463

 

1.19

1494

 

1.26

1500

1363

 

1.05

1406

 

1.15

1465

 

1.25

1500

 

1.34

1532

 

1.43

LEGEND AND NOTES FOR TABLES 10 AND 11

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 2.)

2.Motor drive range is 760 to 1090 rpm for standard motor; 1075 to 1455 rpm for high-static motor. All other rpms require a field-supplied drive.

3.Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.

4.Maximum continuous bhp is 1.20 for standard motor, 2.40 for high-static motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on page 20 for additional information.

5.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

6.Interpolation is permissible. Do not extrapolate.

21

Page 21
Image 21
Carrier 48HJD005-007 specifications Motor Nominal Horsepower, Outdoor Sound Power Total Unit, Bels