Table 16 — 48HJ007 Fan Performance — Vertical Discharge Units With Standard Motor

Table 16 — 48HJ007 Fan Performance — Vertical Discharge Units With Standard Motor

AIRFLOW

 

 

 

 

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

0.1

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1800

942

 

0.70

978

 

0.66

1063

 

0.82

1147

 

0.97

1248

 

1.20

1322

 

1.33

1395

 

1.46

1475

 

1.56

1542

 

1.71

1900

982

 

0.80

1023

 

0.78

1097

 

0.91

1175

 

1.11

1266

 

1.29

1356

 

1.47

1430

 

1.58

1504

 

1.69

1556

 

1.82

2000

1022

 

0.91

1068

 

0.90

1132

 

1.01

1218

 

1.23

1303

 

1.41

1397

 

1.52

1459

 

1.67

1532

 

1.82

1588

 

1.97

2100

1063

 

0.99

1115

 

1.00

1180

 

1.17

1261

 

1.35

1340

 

1.53

1428

 

1.66

1489

 

1.80

1567

 

1.99

1626

 

2.16

2200

1104

 

1.13

1159

 

1.15

1214

 

1.28

1310

 

1.52

1375

 

1.63

1459

 

1.80

1528

 

1.95

1603

 

2.17

1666

 

2.37

2300

1130

 

1.26

1202

 

1.29

1248

 

1.38

1358

 

1.69

1410

 

1.72

1488

 

1.93

1561

 

2.13

1637

 

2.35

1710

 

2.54

2400

1174

 

1.37

1237

 

1.41

1292

 

1.55

1392

 

1.81

1460

 

1.90

1532

 

2.14

1584

 

2.28

1671

 

2.55

1756

 

2.70

2500

1201

 

1.48

1272

 

1.53

1335

 

1.71

1427

 

1.94

1518

 

2.16

1575

 

2.35

1633

 

2.53

1698

 

2.72

 

2600

1246

 

1.62

1320

 

1.68

1368

 

1.81

1458

 

2.06

1562

 

2.42

1620

 

2.59

1675

 

2.77

 

 

2700

1285

 

1.75

1361

 

1.82

1400

 

1.91

1490

 

2.19

1602

 

2.64

1666

 

2.85

 

 

 

2800

1304

 

1.87

1402

 

1.95

1439

 

2.08

1543

 

2.43

1642

 

2.86

 

 

 

 

2900

1345

 

2.07

1446

 

2.16

1477

 

2.16

1585

 

2.65

 

 

 

 

 

3000

1378

 

2.26

1489

 

2.36

1529

 

2.52

1598

 

2.73

 

 

 

 

 

Table 17 — 48HJ007 Fan Performance — Vertical Discharge Units With High-Static Motor

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

0.4

 

 

0.6

 

0.8

 

1.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1800

978

 

0.66

1063

 

0.82

1147

 

0.97

1248

 

1.20

1322

 

1.33

1900

1023

 

0.78

1097

 

0.91

1175

 

1.11

1266

 

1.29

1356

 

1.47

2000

1068

 

0.90

1132

 

1.01

1218

 

1.23

1303

 

1.41

1397

 

1.52

2100

1115

 

1.00

1180

 

1.17

1261

 

1.35

1340

 

1.53

1428

 

1.66

2200

1159

 

1.15

1214

 

1.28

1310

 

1.52

1375

 

1.63

1459

 

1.80

2300

1202

 

1.29

1248

 

1.38

1358

 

1.69

1410

 

1.72

1488

 

1.93

2400

1237

 

1.41

1292

 

1.55

1392

 

1.81

1460

 

1.90

1532

 

2.14

2500

1272

 

1.53

1335

 

1.71

1427

 

1.94

1518

 

2.16

1575

 

2.35

2600

1320

 

1.68

1368

 

1.81

1458

 

2.06

1562

 

2.42

1620

 

2.59

2700

1361

 

1.82

1400

 

1.91

1490

 

2.19

1602

 

2.64

1666

 

2.85

2800

1402

 

1.95

1439

 

2.08

1543

 

2.43

1642

 

2.86

1775

 

3.62

2900

1446

 

2.16

1477

 

2.16

1585

 

2.65

1753

 

3.58

 

3000

1489

 

2.36

1529

 

2.52

1598

 

2.73

1767

 

3.69

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

1.4

 

 

1.6

 

1.8

 

2.0

(Cfm)

 

 

 

 

 

 

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

Rpm

 

Bhp

1800

1395

 

1.46

1475

 

1.56

1542

 

1.71

1607

 

1.94

1667

 

2.16

1900

1430

 

1.58

1504

 

1.69

1556

 

1.82

1621

 

2.06

1682

 

2.30

2000

1459

 

1.67

1532

 

1.82

1588

 

1.97

1655

 

2.23

1717

 

2.49

2100

1489

 

1.80

1567

 

1.99

1626

 

2.16

1694

 

2.44

1758

 

2.73

2200

1528

 

1.95

1603

 

2.17

1666

 

2.37

1736

 

2.68

 

2300

1561

 

2.13

1637

 

2.35

1710

 

2.54

1782

 

2.87

 

2400

1584

 

2.28

1671

 

2.55

1756

 

2.70

 

 

2500

1633

 

2.53

1698

 

2.72

1779

 

3.13

 

 

2600

1675

 

2.77

1768

 

3.26

 

 

 

2700

1776

 

3.45

 

 

 

 

2800

 

 

 

 

 

2900

 

 

 

 

 

3000

 

 

 

 

 

LEGEND AND NOTES FOR TABLES 16 AND 17

LEGEND

Bhp — Brake Horsepower Input to Fan

FIOP — Factory-Installed Option

NOTES:

1.Boldface indicates field-supplied drive required. (See Note 3.)

2.Manual backgroundManual background indicates field-supplied motor and drive required.

3.Motor drive range is 1120 to 1585 rpm for standard motors, 1130 to 1685 rpm for high-static motors. All other rpms require a field-supplied drive.

4.Values include losses for filters, unit casing, and wet coils. See page 28 for accessory/FIOP static pressure information.

5.Maximum continuous bhp is 2.40 for standard motors, 2.90 for high- static motors. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on page 20 for additional infor- mation.

6.Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.

7.Interpolation is permissible. Do not extrapolate.

24

Page 24
Image 24
Carrier 48HJD005-007 specifications 48HJ007 Fan Performance - Vertical Discharge Units With Standard Motor