Carrier 48HJD005-007 specifications Physical Data

Models: 48HJD005-007

1 48
Download 48 pages 50.36 Kb
Page 5
Image 5

Table 1 — Physical Data

BASE UNIT 48

 

HJE/F/H/K/M/N004

 

HJD/E/F/G/H/K/L/M/N005

 

HJD/E/F/G/H/K/L/M/N006

 

HJD/HJE/HJF007

NOMINAL CAPACITY

 

3

 

4

 

5

 

6

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

Unit

 

530

 

540

 

560

 

615

With Durablade Economizer

 

564

 

574

 

594

 

649

With EconoMi$er

 

577

 

587

 

607

 

662

With MoistureMiser Dehumidification Package

 

548

 

558

 

578

 

633

Roof Curb

 

115

 

115

 

115

 

115

COMPRESSOR

 

 

 

 

 

Scroll

 

Quantity

 

1

 

1

 

1

 

1

 

 

 

 

Oil (oz)

 

42

 

53

 

50

 

60

REFRIGERANT TYPE

 

 

 

 

 

R-22

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

Standard Unit

 

5- 8

 

8-6

 

10- 0

 

9-10

 

 

 

 

Unit With MoistureMizer Dehumidification Package

 

8-13

 

11-2

 

12-13

 

13- 6

CONDENSER FAN

 

 

 

 

Propeller

 

Quantity...Diameter (in.)

 

1...22

 

1...22

 

1..22

 

1...22

 

 

 

 

Nominal Cfm

 

3500

 

3500

 

4100

 

4100

Motor Hp...Rpm

 

1/4...825

 

1/4...825

 

1/4...1100

 

1/4...1100

Watts Input (Total)

 

180

 

180

 

320

 

320

CONDENSER COIL

 

 

 

Enhanced Copper Tubes, Aluminum Lanced Fins

 

Standard Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

1...17

 

2..17

 

2...17

 

2...17

Total Face Area (sq ft)

 

14.6

 

16.5

 

16.5

 

16.5

Unit with MoistureMiser Dehumidification Package

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

1...17

 

1...17

 

1...17

 

1...17

Total Face Area (sq ft)

 

3.9

 

3.9

 

3.9

 

3.9

EVAPORATOR FAN

 

 

 

Centrifugal Type, Belt Drive

 

Quantity...Size (in.)

 

1...10 x 10

 

1...10 x 10

 

1...10 x 10

 

1...10 x 10

 

 

 

 

Nominal Cfm

 

1200

 

1600

 

2000

 

2400

Maximum Continuous Bhp

Std

1.20

 

1.20

 

1.30/2.40*

 

2.40

 

Hi-Static

2.40

 

2.40

 

2.90

 

2.90

Motor Frame Size

Std

48

 

48

 

48/56*

 

56

 

Hi-Static

56

 

56

 

56

 

56

Fan Rpm Range

Std

760-1090

 

840-1185

 

1020-1460/1120-1585*

 

1120-1585

Motor Bearing Type

Hi-Static

1075-1455

 

1075-1455

 

1300-1685

 

1300-1685

 

Ball

 

Ball

 

Ball

 

Ball

Maximum Fan Rpm

 

2100

 

2100

 

2100

 

2100

Motor Pulley Pitch Diameter

Std

1.9/2.9

 

1.9/2.0

 

2.4/3.4

 

2.4/3.4

A/B (in.)

Hi-Static

2.8/3.8

 

2.8/3.8

 

3.4/4.4

 

3.4/3.4

Nominal Motor Shaft Diameter (in.)

Std

1/2

 

1/2

 

5/8

 

5/8

Fan Pulley Pitch Diameter (in.)

Hi-Static

5/8

 

5/8

 

5/8

 

5/8

Std

4.5

 

4.0

 

4.0

 

4.0

 

Hi-Static

4.5

 

4.0

 

4.5

 

4.5

Belt — Type...Length (in.)

Std

1...A...33

 

1...A...33

 

1....4...40

 

1...A...38

Pulley Center Line Distance (in.)

Hi-Static

1...A...39

 

1...A...39

 

1...A...40

 

1...A...40

 

10.0-12.4

 

10.0-12.4

 

14.7-15.5

 

14.7-15.5

Speed Change per Full Turn of

Std

65

 

70

 

75

 

95

Movable Pulley Flange (rpm)

Hi-Static

65

 

65

 

60

 

60

Movable Pulley Maximum Full

Std

5

 

5

 

6

 

5

Turns from Closed Position

Hi-Static

6

 

6

 

5

 

5

Factory Setting — Full Turns Open

Std

3

 

3

 

3

 

3

Factory Speed Setting (rpm)

Hi-Static

31/2

 

31/2

 

31/2

 

31/2

Std

890

 

980

 

1240

 

1304

Fan Shaft Diameter at Pulley (in.)

Hi-Static

1233

 

1233

 

1396

 

1396

 

5/8

 

5/8

 

5/8

 

5/8

EVAPORATOR COIL

 

Enhanced

Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Metering Device

Rows...Fins/in.

 

2...15

 

2...15

 

4...15

 

4...15

 

 

 

 

Total Face Area (sq ft)

 

5.5

 

5.5

 

5.5

 

5.5

LEGEND

 

 

 

*Single phase/three phase.

 

Bhp — Brake Horsepower

 

 

 

†Indicates automatic reset.

 

 

 

 

**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners.

 

 

 

 

48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005- 007 (150,000 Btuh Heat input) units have 3 burners.

††An LP kit is available as an accessory.

Three-phase standard models have heating inputs as shown. Single-phase standard models have one-stage heating with heating input values as follows:

48HJE004, 48HJD005,006 — 72,000 Btuh

48HJF004, 48HJE005,006 — 115,000 Btuh 48HJF005,006 — 150,000 Btuh

***California compliant three-phase models.

†††California SCAQMD compliant low NOx models have combustion products that are controlled to 40 nanograms per joule or less.

5

Page 5
Image 5
Carrier 48HJD005-007 specifications Physical Data