Miller Electric Intellifire 250 Operation, Electrical Service Guide, Controls, Hz Three Phase

Page 14

3-6. Electrical Service Guide

 

60 Hz Three Phase

 

 

Input Voltage

460

 

 

Input Amperes At Rated Output

39

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

Time-Delay 2

45

Normal Operating 3

60

Min Input Conductor Size In AWG 4

8

Max Recommended Input Conductor Length In Feet (Meters)

287

(87)

 

 

 

Min Grounding Conductor Size In AWG 4

10

Reference: 2005 National Electrical Code (NEC) (including article 630)

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

SECTION 4 − OPERATION

4-1. Controls

3

4

1 Power Adjust Control

Use control to select power between the mini- mum and maximum output of the power source. The numbers around the control are in kilowatts (kW).

2 Remote Power Control Switch

Use switch to select way of controlling unit out- put.

For front panel control, place switch in Panel position.

12

For remote control, place switch in Remote 14 position. Connect controller or pendant control to Remote 14 receptacle (see Section 3-3).

The remote control functions as a slave to the front panel Power Adjust control. For example, if the front panel control is set to 12.5 kW and the remote control is set to maximum, output will be 12.5 kW. To obtain maximum output from the unit using a remote control, the front panel control must be set to maximum.

Ref. ST-801 826-C

3 Power Switch With Indicator Light

Use switch to turn unit, fan motor, and indica- tor light On and Off.

Unit is ready to heat 10 seconds after Power switch is placed in On position.

4 Ground Fault Test Switch

Use switch to test ground fault circuitry.

OM-184 227 Page 10

Image 14
Contents 2006−05 Induction Heating Power SourceVisit our website at Induction HeatingFrom Miller to You Table of Contents Page Marks a special safety message − Safety Precautions − Read Before UsingSymbol Usage Induction Heating HazardsCalifornia Proposition 65 Warnings Principal Safety StandardsUse only genuine Miller/Hobart replacement parts Flying Metal or Adhesive can injure eyesEMF Information About Pacemakers− Mesures DE Securite Pour LE Chauffage PAR Induction AvertissementDES Organes Mobiles peuvent provoquer des blessures Porteurs de stimulateur cardiaque, restez à distanceEn ce qui concerne les stimulateurs cardiaques Connecting Head/Coil to Power Source − InstallationSpecifications Socket Information Remote 14 Receptacle RC14 Information and ConnectionsRemote 14 Socket Information = GND/PE Earth Ground Tools Needed 5/16 Welding Power Source Input Power ConnectionsDisconnect Device Input Power Connections − Operation Electrical Service GuideHz Three Phase ControlsSafety Interlock Switch − Maintenance & TroubleshootingRoutine Maintenance OverheatingMeasuring Tuning Capacitor Voltage Ground Fault Protection Power Source Receptacle PlugMeasuring Input Capacitor Voltage Diagnostic LED’s Trouble Remedy TroubleshootingTuning Chart OM-184 227 − Electrical Diagram Circuit Diagram204 963-A − Parts List Main AssemblyFM2 Center Baffle Assembly -1 Item 180 Page Page Page Support ServiceYour distributor also gives Your distributor and/or equipment manufacturer’s To locate a Distributor or Service Agency visitFor assistance in filing or settling claims, contact Transportation Department