(5) Recharging

Be sure to charge the specified amount of refrigerant in liquid state using the service port of the wide tube service valve. The proper amount is listed on the unit's nameplate.

When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation.

CAUTION

Never charge a large amount

of liquid refrigerant at once to

 

 

 

the unit. This may cause

 

damage to the compressor.

When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change. Thus, do not use the refrigerant if

the amount in the charging cylinder is less than 20%.

Also, charge the minimum necessary amount to the charging cylinder before using it to charge the air conditioning unit.

Example:

In case of charging refrigerant to a unit requiring 0.76Kg using a capacity of a 10Kg cylinder, the minimum necessary amount for the cylinder is:

0.76 + 10 0.20 = 2.76Kg

For the remaining refrigerant, refer to the instructions of the refrigerant manufacturer.

If using a charging cylinder, transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder.

Prepare an evacuated charging cylinder beforehand.

CAUTION

To prevent the composition

of R410A from changing,

 

 

 

never bleed the refrigerant

 

gas into the atmosphere

 

while transferring the

 

refrigerant. (Fig. 3)

Do not use the refrigerant if the amount in the charging cylinder is less than 20%.

Configuration and characteristics of cylinders

Valve

Liquid

Single valve

Charge liquid refrigerant with cylinder in up-side-down position.

Fig. 1

Valve

Liquid

Single valve (with siphon tube)

Charge with cylinder in normal position.

Fig. 2

NO!

Charging

cylinder

Liquid

OpenRefrigerant cylinder

Fig. 3

57

Image 57
Contents DC Inverter Split System AIR Conditioner Table of Contents Checking Electrical Components Please Read Before Starting For safe installation and trouble-free operation, you MustOperating Range Indoor Unit SAP-KRV94EHDX Unit SpecificationsOutdoor Unit SAP-CRV124EHDX SAP-KRV124EHDXSAP-KRV94EHDX Major Component SpecificationsCB-KRV124EHDX Outdoor Unit CB-CRV124EHDX Other Component Specifications Dimensional Data Dia .35 1/4 Refrigerant Flow Diagram Refrigerant Flow DiagramInsulation of Refrigerant Tubing Indoor Unit SAP-KRV94EHDX Outdoor Unit SAP-CRV94EHDXPerformance Data Temperature ChartsIndoor Unit SAP-KRV124EHDX Outdoor Unit SAP-CRV124EHDX Air Throw Distance Charts Indoor Unit SAP-KRV124EHDX Electrical Characteristics CoolingHeating Electric Wiring Diagrams Outdoor Unit Indoor UnitSAP-CRV94EHDX SAP-KRV94EHDX SAP-CRV124EHDX SAP-KRV124EHDX Installation Site Selection About Wiring System Diagram Recommended Wire Length and DiameterMounting on a Wall Remote Control Unit Installation PositionON/OFF How to Test Run the Air ConditionerRemove the Grille to Install the Indoor Unit How to remove the grilleHow to replace the grille Maintenance Address Setting of the Remote Control UnitSwitching the remote controller address Removing and Mounting the Drain Hose Removing the Electrical Component Box Page Removing the Panel Motor Removing the Drain Pan Air Outlet Assy Removing and Mounting the Drain Pan Air Outlet AssyWater in the drain pan Mounting the Drain Pan Air Outlet AssyRemoving the Negative Ion Generator Removing and Mounting the Fan Motor Removing the Fan MotorMounting the Fan Motor Removing the Fan How to Connect How to DisconnectOperation Functions FunctionsEmergency operation Auto cooling/heating operationLamp colors Timer backupProtective Functions Compressor discharge temperature controlOverload prevention during heating Freeze preventionMode Cooling Mode HeatingNon-Stop Defrosting Troubleshooting Precautions before Performing Inspection or RepairMethod of Self-Diagnostics ION Timer Operation Self-diagnostics LampsChecking the Indoor and Outdoor Units Diagnostic results Diagnostic procedureRemedy for symptom 3 to Trouble Diagnosis of Indoor and Outdoor Fan MotorOutdoor Fan Motor Noise Malfunction and Electromagnetic Interference Noise malfunctionElectromagnetic interference Upper right screw Grille Screw Flap Screw cover Making a Diagnosis of the Panel Motor Measurement of Insulation Resistance Checking Electrical ComponentsChecking Continuity of Fuse on PCB Assy Characteristics of New Refrigerant R410A Refrigerant R410A Special Precautions When Servicing UnitChecklist before Servicing Size of flareNo addition of compressor oil for R410A Tubing precautionsNo use of refrigerant other than R410A If refrigerant R410A is exposed to fireTools Specifically for R410A Tubing Installation ProceduresFor servicing, use the following tools for R410A Tool Distinction Tool NameCase of Compressor Malfunction Procedure for Replacing CompressorRecharging Configuration and characteristics of cylindersNever charge a large amount Unit. This may causeWelding leaking points Case Refrigerant is LeakingCharging Additional Refrigerant When Tubes are ExtendedRetro-Fitting Existing Systems Use of Existing UnitsOI-852-6-4180-791-00-0 Child Lock FeaturesContents Alert SymbolsProduct Information Installation Location Safety InstructionsElectrical Requirements Names of Parts Unit Display and Operation Button Remote Control Unit Display Remote Control Unit Heat AutoDRY CoolONE TIME/EVERYDAY Using the Remote Control UnitUsing the Remote Control Unit Remote control unit mount Mounting screws 4 x 16 includedControl Unit Step Operation with the Remote Control UnitStep Press the ON/OFF operation buttonCover closed Cover opened Step Operation with the Remote Control UnitAdjusting the Fan Speed Night Setback Mode is used for saving energy Cooling and DRY ModeSetting Setting TemperatureQuiet Mode Special Remarks Setting the Timer Example To set toOperation Indication To cancel a timer program Press the Cancel button Setting the Timer2230 610 2000 Present time OFFSetting procedure Using the 1.2.3.5-Hour OFF TimerCancellation procedure Operation together with the Daily ON/OFF Repeat TimerAdjusting the Airflow Direction SweepFAN Heat Indoor Unit Care and CleaningHow to replace the anti-mold Care and CleaningRemounting the front panel FilterNegative ion generator metal electrodes inside plastic case How to clean the air clean filterTroubleshooting Operating RangeTrouble Possible Cause Remedy Osaka, Japan Sept

SAP-KRV94EHDX specifications

The Sanyo SAP-KRV94EHDX is a cutting-edge split-type air conditioning unit that exemplifies advanced technology and efficiency. Designed for both residential and commercial spaces, this model is equipped with features that cater to various cooling and heating needs.

One of the main highlights of the Sanyo SAP-KRV94EHDX is its energy efficiency. With a high Energy Efficiency Ratio (EER), this unit minimizes energy consumption while maximizing cooling performance. This not only results in lower electricity bills but also contributes to a reduced carbon footprint, making it an environmentally friendly choice for users.

The SAP-KRV94EHDX employs inverter technology, which allows the compressor to adjust its speed dynamically based on the temperature requirements of the environment. This means that the unit operates more quietly and uses less energy when maintaining a consistent temperature. The inverter system ensures that the air conditioner can quickly reach the desired cooling or heating temperature and maintain it without the frequent on-off cycles typical of traditional units.

Additionally, the air conditioning unit comes with a powerful cooling capacity, effectively managing larger spaces. It can easily handle varying ambient conditions while providing rapid cooling in extremely warm weather, making it perfect for areas with hot climates.

Other notable features include a user-friendly remote control, allowing users to adjust settings from a distance effortlessly. The unit also incorporates a multi-stage air filtration system designed to remove dust, allergens, and other airborne particles, contributing to better indoor air quality.

The Sanyo SAP-KRV94EHDX is not just about functionality; it also boasts a sleek and modern design that blends seamlessly with various interior aesthetics. Its quiet operation ensures that it does not disturb daily activities, making it suitable for bedrooms, offices, and living spaces.

Moreover, the unit comes with various operational modes, including cooling, dehumidification, and a heating function. This versatility makes the SAP-KRV94EHDX an all-season solution for climate control.

In summary, the Sanyo SAP-KRV94EHDX is a top-tier air conditioning unit that combines efficiency, advanced technology, and user convenience. Its inverter technology, multi-stage air filtration, and modern design make it a reliable choice for anyone seeking comfort throughout the year.