Sanyo CG1411 service manual Electric Wiring Diagrams, Indoor unit KGS1411

Page 26

6-2. Electric Wiring Diagrams

(1) Indoor unit

KGS1411

WARNING

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

Fan motor

PNK

BRN

WHT

RED

 

AC out

3 4

 

RV

 

 

 

Power relay

 

 

 

 

 

 

 

 

 

COM

 

1

1

 

Trans 1 1

1

3P (WHT) 3

3

 

Fan

 

 

 

 

33

Terminal base (4P)

1COM

2CM ON

3AC115V

4RV ON

BLU

BLK

G

GND

 

 

WHT

 

WHT

P

To outdoor unit

FM

GRN

BLU

55 5P (WHT) Controller (B)

Trans 2

1

1

2P (RED)

2

2

 

 

transformer

BRN

S

Power

BRN

 

 

 

RED

BLK

YEL

G

Connector

1

1

WHT

2

2

BLU

FLP 3 3

BLU

4

4

BLU

5

5

BLU

Flap motor

 

 

 

DC-CONT 11P (WHT)

 

 

 

1

2

3

4

5

6

7

8

9 10 11

 

 

 

1

2

3

4

5

6

7

8

9 10 11

 

 

 

 

DC-CONT 11P (WHT)

 

1

1

Hole IC

 

 

 

 

 

1

1

2

2

3P (WHT)

 

 

 

 

2

2

3

3

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

Lamp 4

4

 

 

 

 

 

 

 

 

8P (WHT) 5

5

 

 

 

 

Controller (A)

6

6

 

 

 

 

7

7

1

1

 

 

 

 

 

 

 

 

8

8

2

2

Flap

 

 

 

 

 

 

 

 

3

3

5P (GRN)

 

 

 

 

 

 

4

4

 

 

 

 

 

 

5

5

 

 

 

 

 

 

 

 

Coil 1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2P (WHT) 2

2

WHT

1

1

(WHT)Lamp

ASSYLAMPIND

GRY

2

2

 

 

GRY

3

3

 

 

GRY

4

4

 

 

WHT

5

5

 

 

GRY

6

6

 

 

GRY

7

7

 

 

GRY

8

8

 

 

 

 

 

BLK

BLK

Coil thermistor

22

Image 26
Contents GAS Heater AIR Conditioner When Transporting When Installing…Case of Improper Installation When Connecting Refrigerant TubingTable of Contents Troubleshooting IiiTemperature Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeKGS1411 SpecificationsUnit Specifications CG1411Safety Devices Dimensions & WeightGovernor Setting Pressure BurnerMajor Component Specifications Indoor UnitCompressor Outdoor UnitGas Connection External FinishCombination Gas Valve NozzleRefrigerant Heater IgniterThermistor Coil sensor Other Component SpecificationsTransformer ATR-1581T2-U Thermistor Room sensorTransformer TR 4FF4L510034000 Power Relay PRAuto Reset Temperature Limiting Thermistor 1 Discharge pressure PB3M-41EDimensional Data UnitLocation of Service Valves Internal Components PCB aPTC Gas Nozzle Major ComponentsCombination Gas Valve Proportional Control Valve Main Burner Combustion BlowerRefrigerant Heater Refrigerant Flow Diagram Refrigerant Flow DiagramHeating Characteristics Performance ChartsCooling Characteristics Performance DataHeating Air Throw Distance ChartsCooling Cooling Capacity Heating Capacity 100CG1411 Cooling Electrical CharacteristicsElectrical Data Electric Wiring Diagrams Indoor unit KGS1411BM RV1 RV2 GV1 GV2 Printed circuit board POW-CG1411 SD3Installation Instructions Installation Site SelectionHot air Heat source Outdoor unit Obstacle above Recommended Wire Length and Diameter Wiring System DiagramRemovable mounting Remote Control Unit Installation PositionMounting on a Wall Non-removable mountingHeating FunctionMotion Explanation CoolingCombustion Safety ControlsCombustion Control Room Temperature Control CoolingFreeze Prevention Cooling Heating Refrigerant Control ThermistorSave Function Reset FunctionCombustion Saving Function Cold Draft Prevention Function During Heating Operation Fan Speed Control During Cooling Operation Automatic fan speedDry Operation Dehumidification Changing fan speed Automatic Automatic OperationNormal During Cooling OperationDry B Zone Freeze PreventionCooling / Dry Cooling Zone Dry a Zone Overload Prevention Heating Operation Flowcharts Cooling, DryOperation starts Operation lamp How to remove grille Procedure for Dismantling the UnitProcedure for Dismantling the Indoor Unit How to remove PCBsHow to remove electrical component box How to remove drain panHow to detach heat exchanger How to detach fan and fan motorHow to detach the rear panel Procedure for Dismantling the Outdoor UnitHow to remove the external panels How to detach the combustion blowerHow to detach combination valve and gas conduit How to detach combination valveHow to detach gas nozzle How to detach ignition probe and flame sensor electrodeHow to detach burner unit Manifold Pressure Indoor Unit Alarm SignalPoints to Diagnose Checking Electrical Components Components11-3-2 Indoor Unit 11-3-3 Outdoor UnitTroubleshooting Check Before and After TroubleshootingIncorrect Wiring of Inter-unit Wiring Malfunction in Power SupplyAbnormalities in Power Transformer Thermistor Abnormality Indoor Unit Only Protective Circuit of Outdoor Burner Unit OperatedPower Circuit Wiring Error Indoor Fan is DefectiveOutdoor Unit Compressor Motor Overload Relay Has Operated Outdoor Unit Power Supply FailureOutdoor Unit Power Transformer Defective Outdoor Unit Fan Motor Defective Outdoor Unit Fan Does Not WorkOutdoor Unit Compressor Motor Defective Louver Motor Defective Flap Motor Does Not WorkHeating Operation Not Possible Thermistor 1 DefectiveIgnition Failure Safety Device OperatedErroneous Flame Detection Erroneous Flame-Out Condition Reversing Valve Failure Combustion Blower Motor Abnormal Revolution12-6-8. ON/OFF Valve Failure Reset Method When Error Occurs During Heating Operation Failure Display on Outdoor Unit and Correction Method DC0VSpecial Precautions When Servicing the Unit BLK/WHT Connector Attachment for ServicingEvacuation Using Vacuum Pump Refrigerant RecoveryService on Outdoor Unit Refer to Service Valve Construction shown in FigCharging Gradation Level before VolumeRefrigerant Charging ChargingReattaching BLK/WHT Connectors for Operation Appendix For Your Safety Read Before Operation What to do if YOU Smell GASProduct Information ContentsAlert Symbols Features Installation Location Electrical RequirementsSafety Instructions Air outlet Names of PartsAir intakes Outdoor Condensing UnitTimer lamp OFF position does not disconnect the power. Use the mainPower switch to turn off power completely ReceiverSET Temp Timer OFF button TEMP. setting buttonsButton Timer on button TransmitterGreen or red Auto HR. Timer buttonHour off timer Red HeatUsing the Remote Control Unit ACL button CoverUsing the Remote Control Unit Operation with the Remote Control Unit Press the ON/OFF operation buttonOperation with the Remote Control Unit Manual Operation Temperature is Automatic Cooling and DRY mode Heating mode ManualWhen difference between Room temperature and set Temperature is Over High Below 2 F MediumNight Setback Mode is used for saving energy Fan OnlySetting Temperature Press Hour Hours Setting Temperature Press Hour TimeButton Heating Mode Button TimeHeating performance Special RemarksHow it works? Clicking sound is heard from the air conditionerCancellation procedure Press the Cancel button Using the 12-Hour on and OFF TimerSetting procedure Using the 1-Hour OFF Timer Sweep function Adjusting the Airflow DirectionSetting the airflow manually Casing and Grille Indoor Unit Operation without the Remote Control UnitCare and Cleaning Air intake grille Anti-mold filter How to remove the anti-mold filterHow to replace the anti-mold filter Anti-mold filterArm AirFilter Operating Range TroubleshootingTips for Energy Saving For Parts or Service Contact

KGS1411, CG1411 specifications

Sanyo KGS1411 and CG1411 are notable solar panel models from Sanyo, a brand recognized for its innovation in photovoltaic technology. These models are particularly designed to deliver high efficiency and reliable performance for residential and commercial solar energy applications.

One of the standout features of the Sanyo KGS1411 is its use of HIT (Heterojunction with Intrinsic Thin layer) technology. This cutting-edge technology combines crystalline and thin-film solar cells, resulting in a unique structure that maximizes light absorption. The HIT technology results in higher conversion efficiency compared to traditional solar panels. The KGS1411 can achieve efficiencies of up to 20.4%, making it an excellent choice for those looking to maximize energy output from limited rooftop space.

The CG1411 model complements the KGS1411 by offering enhanced performance in low-light conditions. It is particularly effective in urban settings or regions with frequent overcast weather. This model also employs advanced cell design that improves performance during high temperatures, avoiding the efficiency loss typical in conventional solar panels.

Another significant characteristic of both models is their durable construction. Sanyo panels are designed to withstand severe weather conditions, including strong winds and heavy snow loads. This robustness is complemented by an extended warranty period, giving users peace of mind about their investment.

In terms of aesthetics, both the KGS1411 and CG1411 feature a sleek, all-black design, allowing them to blend seamlessly with various roofing materials. This visual appeal makes them an attractive option for homeowners who prioritize the appearance of their solar energy systems.

Furthermore, Sanyo panels come with integrated monitoring solutions that allow users to track energy production and system performance in real-time. This feature is invaluable for assessing the efficiency of the solar system and making informed decisions about energy consumption.

In conclusion, the Sanyo KGS1411 and CG1411 solar panels represent a synthesis of advanced technology and reliable performance. With their high efficiency, durability, and user-friendly monitoring solutions, these models are well-suited for consumers seeking sustainable energy solutions without compromising on quality or aesthetics. Whether for residential use or larger commercial projects, Sanyo’s offerings stand out in the competitive solar market.