13-2. Refrigerant Recovery

13-2-1.Open service valve to recover refrigerant into refrigerant recovery unit.

CAUTION

Refrigerant released into the air contributes to destruction of our planet’s ozone layer. You should always use the refrigerant recovery unit to help protect the environment.

13-3. Service on Outdoor Unit

13-3-1.After making sure that the refrigerant in the circuit has been completely discharged, perform required servicing, such as replacing the compressor or repairing refrigerant leaks.

13-3-2.Before going on to the next step, leak test all joints where welding has been done.

NOTE

Nitrogen gas is best when pressurizing the system for a leak test. However, if it is necessary to instead test with refrigerant gas, be sure to recover all gas into the refriger- ant recovery unit after completing the leak test.

Outdoor unit

 

Manifold valve

 

Pressure

Lo

Hi

gauge

 

 

13-4. Evacuation Using Vacuum Pump

13-4-1.Using a hex wrench, set the valve stems of the narrow and wide tube service valves as indicated in the table below.

Service Valve

Valve Position

Narrow

Position – a –

Wide

Vacuum pump

Fig. 2

NOTE

Refer to Service Valve Construction shown in Fig. 3.

Action

Narrow Tube Service

Wide Tube Service

Valve (2-Way)

Valve (3-way)

 

 

Fully OPEN

 

Position – a –

 

*

CLOSED

Position – b –

*

Fig. 3

* Hose

66

Image 70
Contents GAS Heater AIR Conditioner When Transporting When Installing…Case of Improper Installation When Connecting Refrigerant TubingTable of Contents Troubleshooting IiiTemperature Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeKGS1411 SpecificationsUnit Specifications CG1411Safety Devices Dimensions & WeightGovernor Setting Pressure BurnerMajor Component Specifications Indoor UnitCompressor Outdoor UnitGas Connection External FinishCombination Gas Valve NozzleRefrigerant Heater IgniterThermistor Coil sensor Other Component SpecificationsTransformer ATR-1581T2-U Thermistor Room sensorTransformer TR 4FF4L510034000 Power Relay PRAuto Reset Temperature Limiting Thermistor 1 Discharge pressure PB3M-41EDimensional Data UnitLocation of Service Valves Internal Components PCB aPTC Combination Gas Valve Proportional Control Valve Major ComponentsGas Nozzle Main Burner Combustion BlowerRefrigerant Heater Refrigerant Flow Diagram Refrigerant Flow DiagramHeating Characteristics Performance ChartsCooling Characteristics Performance DataCooling Air Throw Distance ChartsHeating Cooling Capacity Heating Capacity 100Electrical Data Electrical CharacteristicsCG1411 Cooling Electric Wiring Diagrams Indoor unit KGS1411BM RV1 RV2 GV1 GV2 Printed circuit board POW-CG1411 SD3Installation Instructions Installation Site SelectionHot air Heat source Outdoor unit Obstacle above Recommended Wire Length and Diameter Wiring System DiagramRemovable mounting Remote Control Unit Installation PositionMounting on a Wall Non-removable mountingHeating FunctionMotion Explanation CoolingCombustion Control Safety ControlsCombustion Room Temperature Control CoolingFreeze Prevention Cooling Heating Refrigerant Control ThermistorCombustion Saving Function Reset FunctionSave Function Cold Draft Prevention Function During Heating Operation Fan Speed Control During Cooling Operation Automatic fan speedDry Operation Dehumidification Changing fan speed Automatic Automatic OperationNormal During Cooling OperationCooling / Dry Cooling Zone Dry a Zone Freeze PreventionDry B Zone Overload Prevention Heating Operation Flowcharts Cooling, DryOperation starts Operation lamp How to remove grille Procedure for Dismantling the UnitProcedure for Dismantling the Indoor Unit How to remove PCBsHow to remove electrical component box How to remove drain panHow to detach heat exchanger How to detach fan and fan motorHow to detach the rear panel Procedure for Dismantling the Outdoor UnitHow to remove the external panels How to detach the combustion blowerHow to detach combination valve and gas conduit How to detach combination valveHow to detach burner unit How to detach ignition probe and flame sensor electrodeHow to detach gas nozzle Points to Diagnose Indoor Unit Alarm SignalManifold Pressure Checking Electrical Components Components11-3-2 Indoor Unit 11-3-3 Outdoor UnitTroubleshooting Check Before and After TroubleshootingAbnormalities in Power Transformer Malfunction in Power SupplyIncorrect Wiring of Inter-unit Wiring Thermistor Abnormality Indoor Unit Only Protective Circuit of Outdoor Burner Unit OperatedPower Circuit Wiring Error Indoor Fan is DefectiveOutdoor Unit Power Transformer Defective Outdoor Unit Power Supply FailureOutdoor Unit Compressor Motor Overload Relay Has Operated Outdoor Unit Compressor Motor Defective Outdoor Unit Fan Does Not WorkOutdoor Unit Fan Motor Defective Louver Motor Defective Flap Motor Does Not WorkHeating Operation Not Possible Thermistor 1 DefectiveErroneous Flame Detection Safety Device OperatedIgnition Failure Erroneous Flame-Out Condition 12-6-8. ON/OFF Valve Failure Combustion Blower Motor Abnormal RevolutionReversing Valve Failure Reset Method When Error Occurs During Heating Operation Failure Display on Outdoor Unit and Correction Method DC0VSpecial Precautions When Servicing the Unit BLK/WHT Connector Attachment for ServicingEvacuation Using Vacuum Pump Refrigerant RecoveryService on Outdoor Unit Refer to Service Valve Construction shown in FigCharging Gradation Level before VolumeRefrigerant Charging ChargingReattaching BLK/WHT Connectors for Operation Appendix For Your Safety Read Before Operation What to do if YOU Smell GASAlert Symbols ContentsProduct Information Features Installation Location Electrical RequirementsSafety Instructions Air outlet Names of PartsAir intakes Outdoor Condensing UnitTimer lamp OFF position does not disconnect the power. Use the mainPower switch to turn off power completely ReceiverSET Temp Timer OFF button TEMP. setting buttonsButton Timer on button TransmitterGreen or red Auto HR. Timer buttonHour off timer Red HeatUsing the Remote Control Unit ACL button CoverUsing the Remote Control Unit Operation with the Remote Control Unit Press the ON/OFF operation buttonOperation with the Remote Control Unit Manual Operation Temperature is Automatic Cooling and DRY mode Heating mode ManualWhen difference between Room temperature and set Temperature is Over High Below 2 F MediumNight Setback Mode is used for saving energy Fan OnlySetting Temperature Press Hour Hours Setting Temperature Press Hour TimeButton Heating Mode Button TimeHeating performance Special RemarksHow it works? Clicking sound is heard from the air conditionerSetting procedure Using the 12-Hour on and OFF TimerCancellation procedure Press the Cancel button Using the 1-Hour OFF Timer Setting the airflow manually Adjusting the Airflow DirectionSweep function Care and Cleaning Operation without the Remote Control UnitCasing and Grille Indoor Unit Air intake grille Anti-mold filter How to remove the anti-mold filterHow to replace the anti-mold filter Anti-mold filterFilter AirArm Tips for Energy Saving TroubleshootingOperating Range For Parts or Service Contact

KGS1411, CG1411 specifications

Sanyo KGS1411 and CG1411 are notable solar panel models from Sanyo, a brand recognized for its innovation in photovoltaic technology. These models are particularly designed to deliver high efficiency and reliable performance for residential and commercial solar energy applications.

One of the standout features of the Sanyo KGS1411 is its use of HIT (Heterojunction with Intrinsic Thin layer) technology. This cutting-edge technology combines crystalline and thin-film solar cells, resulting in a unique structure that maximizes light absorption. The HIT technology results in higher conversion efficiency compared to traditional solar panels. The KGS1411 can achieve efficiencies of up to 20.4%, making it an excellent choice for those looking to maximize energy output from limited rooftop space.

The CG1411 model complements the KGS1411 by offering enhanced performance in low-light conditions. It is particularly effective in urban settings or regions with frequent overcast weather. This model also employs advanced cell design that improves performance during high temperatures, avoiding the efficiency loss typical in conventional solar panels.

Another significant characteristic of both models is their durable construction. Sanyo panels are designed to withstand severe weather conditions, including strong winds and heavy snow loads. This robustness is complemented by an extended warranty period, giving users peace of mind about their investment.

In terms of aesthetics, both the KGS1411 and CG1411 feature a sleek, all-black design, allowing them to blend seamlessly with various roofing materials. This visual appeal makes them an attractive option for homeowners who prioritize the appearance of their solar energy systems.

Furthermore, Sanyo panels come with integrated monitoring solutions that allow users to track energy production and system performance in real-time. This feature is invaluable for assessing the efficiency of the solar system and making informed decisions about energy consumption.

In conclusion, the Sanyo KGS1411 and CG1411 solar panels represent a synthesis of advanced technology and reliable performance. With their high efficiency, durability, and user-friendly monitoring solutions, these models are well-suited for consumers seeking sustainable energy solutions without compromising on quality or aesthetics. Whether for residential use or larger commercial projects, Sanyo’s offerings stand out in the competitive solar market.