11. SERVICE PROCEDURES

2)Checking the Protective Devices

Disconnect the connector, which consists of P (plug) and S (socket) when you want to check the protective device.

Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 17.

Normality of the protective device can be judged by the following table.

The Protective Device is proved normal if there is a continuity between terminals.

socket

Multimeter

Ω

Fig. 17

0642_X_S

1Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit

Disconnect the connector which leads to the indoor fan motor (FMI).

Check the socket’s terminals.

2Compressor motor thermal protector . . . . . . Outdoor unit

Disconnect the wires from terminals of compressor.

Check the terminals of compressor.

3Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit

Disconnect both the connector which leads to the outdoor fan motor (FMO).

Check socket’s terminal.

SM830079

– 42 –

Image 42
Contents Technical Data Indoor Unit Outdoor Unit XS1852 C1852Please Read Before Starting If Necessary, Get HelpTable of Contents Introduction Read Me First Operating Range XS1852 / C1852XS1852 / CL1852 Specifications Unit SpecificationsData Subject to Change Without Notice Major Component Specifications Indoor Unit Fan motorMajor Component Specifications Outdoor Unit CompressorOther Component Specifications Indoor Unit Model No XS1852 Power TransformerOther Component Specifications Outdoor Unit Model No CL1852Dimensional Data Indoor Unit XS1852Outdoor Unit C1852, CL1852 Performance Charts 230VAIR Throw Distance Chart Model XS1852Refrigerant Flow Diagram Insulation of Refrigerant TubingTo prevent heat loss and wet floors due to dripping Installation Instructions Tubing LengthSelecting the Installation Site AvoidÃInstall the outdoor unit Choose a place that is well ventilatedBaffle Plates for the Outdoor Unit CL×× models only Electrical Wiring General Precautions on Wiring Wiring System Diagram ModelsElectrical Data Electric Wiring Diagram Electrical Wiring DiagramsSchematic Diagram Outdoor Unit C1852 Outdoor Unit CL1852 Room Temperature Control Processes and FunctionsFreeze Prevention Drain Pump ControlMedium Service Procedures 1334XS Check remote control unit There is a possibility of short circuitCheck Operation selector switch in the indoor unit Transformer in indoor unitCheck. auxiliary relay Check fuse on the P.C.B. Ass’y in the indoor unit FMICheck Cool / FAN selector switch in the remote control unit Check set temperatureOutdoor Unit does not Run Check float switch Refer to 11 Drain Pump Control Check compressor motor magnetic contactorSome Part does not Operate Indoor Unit does not RunIndoor fan and louver motor do not run Indoor fan does not runOutdoor Fan does not Run Outdoor Fan does not Run for CL1852Compressor does not Run Poor Cooling Excessive CoolingRoom temp. Sensor in the remote control unit is defective Operation of Major Electrical PartsPower Supply Wires Measurement of Insulation Re- sistance for Electrical partsChecking the Protective Devices Compressor motor thermal protector . . . . . . Outdoor unitIndoor fan motor FMI Indoor unit Measure the coil resistance Motor capacitor Both in indoor and outdoor unitThermistor Characteristic Curve Continuity of fuse on P.C.B. Ass’yMethod Used to Replace Fuse on PCB Ass’y Central Region