Thermo Products MG-1018 CDX1 SERIES, CDX1-75, CDX1-100, CDX1-125, Heating Input Rate In Btu/Hr

Page 4

All installations and services must be performed by qualified service personnel.

CDX1 SERIES

MODEL NO.

CDX1-75

CDX1-100

CDX1-125

HEATING INPUT RATE IN BTU/HR

75,000 / 56,250

100,000 / 75,000

125,000 / 93,750

(High fire / Low fire)

HEATING CAPACITY IN BTU/HR

69,750 / 52,312

93,000 / 69,750

116,250 / 87,187

(High fire / Low fire)

 

 

 

 

HEIGHT OF CASING

46-1/4”

46-1/4”

46-1/4”

WIDTH OF CASING

17”

21”

24”

DEPTH OF CASING

27-1/2”

27-1/2”

27-1/2”

WARM AIR OUTLET

15 x 18

19 x 18

22 x 18

RETURN AIR INLET

15 x 22

19 x 22

22 x 22

 

 

 

 

DIA. OF FLUE

2”

3”

3”

DIA. OF COMBUSTION

2”

3”

3”

AIR INTAKE

 

 

 

 

 

 

 

FLOWRATE from .2” & .5” w.c.

COOLING

COOLING

COOLING

EXTERNAL STATIC PRESSURE

 

 

 

 

 

 

 

@COOLING TAP A (CFM)

1000

1200

1400

@COOLING TAP B (CFM)

800

1000

1200

@COOLING TAP C (CFM)

1200

1400

1600

@COOLING TAP D (CFM)

1400

1600

2000

 

 

 

 

 

HEATING

HEATING

HEATING

@HEATING TAP C

1012 / 826

1340 / 1094

1673 / 1366

(CFM @ High fire / Low fire)

 

 

 

 

TEMPERATURE RISE (°F)

65 / 60

65 / 60

65 / 60

BLOWER MOTOR HP

.5

.75

1

 

 

 

 

POWER CHOKES

-

2.65Mh

2.1Mh

LARGEST RECOMMENDED

3.5 Ton

4 Ton

5 Ton

AIR CONDITIONER

 

 

 

SIZE OF FILTERS

21-3/4” x 14”(2)

21-3/4” x 14”(2)

21-3/4” x 14”(2)

NOTES:

 

 

 

1.Heating capacity based on annual fuel utilization efficiency rated by manufacturer.

2.On all outlet and inlet dimensions, the first dimension is width.

3.To permit largest recommended air conditioning (at .5 static pressure), selection of the highest motor speed is required.

4.Electrical characteristics at 115 volts, 60 Hz., 1 phase (less than 15 amps. for all models).

5.All specifications are subject to change without notice.

2

Image 4
Contents FOR USE WITH MODELS CHX1-75N CDX1-75N MG-1018CHX1-100N CDX1-100N CHX1-125N CDX1-125N SECTION INDEXBEGINNING PAGE POWER CHOKES MODEL NOCHX1-75 CHX1-100CDX1 SERIES CDX1-75CDX1-100 CDX1-125II.BLOWER INFORMATION A. WIRING Figure 1 BLOWER WIRINGB. CFM TABLES COOLING AND CONTINUOUS FAN SPEEDS III.ECM TROUBLE SHOOTING SYMPTOMCAUSE/PROCEDURE Motor rocks slightly when startingEvidence of Moisture Perform Moisture CheckDON’T Moisture CheckFigure 2 ECM PIN CONNECTORS B. TROUBLESHOOTING CHARTS