Thermo Products MG-1018 Evidence of Moisture, Perform Moisture Check, Don’T, Comfort Check

Page 9

All installations and services must be performed by qualified service personnel.

“Hunts” or “puffs” at high CFM (speed)

Does removing panel or filter reduce “puffing”?

 

 

 

!

Reduce restriction

 

 

 

!

Reduce max airflow

Evidence of Moisture

 

 

 

Motor failure or malfunction has occurred and

Replace motor and perform Moisture Check

 

moisture is present

 

 

 

Evidence of moisture present inside air mover

Perform Moisture Check

 

 

DO

 

DON’T

Check-out motor, controls, wiring and

Automatically assume the motor is bad.

 

connections thoroughly before replacing motor

 

 

Orient connectors down so water can’t get in

Locate connectors above 7 and 4 o’clock

 

!

Install “drip loops”

 

positions

Use authorized motor and control model #’s for

Replace one motor or control model # with

 

replacement

 

another (unless an authorized replacement)

Keep static pressure to a minimum:

Use high pressure drop filters – some have ½”

 

! Recommend high efficiency, low static

 

H2O drop!

 

 

filters

Use restricted returns

 

!

Recommend keeping filters clean

 

 

 

!

Design ductwork for min static, max

 

 

 

 

comfort

 

 

 

!

Look for and recommend ductwork

 

 

 

 

improvement, where necessary, in

 

 

 

 

replacement

 

 

Size the equipment wisely

Oversize system then compensate with low

 

 

 

 

airflow

Check orientation before inserting motor

Plug in power connector backwards

 

connectors

Force plugs

Moisture Check

Connectors are orientated “down” (or as recommended by equipment manufacturer)

Arrange harnesses with “drip loop” under motor

Is condensate drain plugged?

Check for low airflow (too much latent capacity)

Check for undercharged condition

Check and plug leaks in return ducts, cabinet

Comfort Check

Check proper airflow settings

Low static pressure for lowest noise

Set low continuous-fan CFM

T’stat in bad location?

7

Image 9
Contents MG-1018 FOR USE WITH MODELS CHX1-75N CDX1-75NCHX1-100N CDX1-100N CHX1-125N CDX1-125N INDEX SECTIONBEGINNING PAGE MODEL NO POWER CHOKESCHX1-75 CHX1-100CDX1-75 CDX1 SERIESCDX1-100 CDX1-125Figure 1 BLOWER WIRING II.BLOWER INFORMATION A. WIRINGB. CFM TABLES COOLING AND CONTINUOUS FAN SPEEDS SYMPTOM III.ECM TROUBLE SHOOTINGCAUSE/PROCEDURE Motor rocks slightly when startingPerform Moisture Check Evidence of MoistureDON’T Moisture CheckFigure 2 ECM PIN CONNECTORS B. TROUBLESHOOTING CHARTS