Thermo Products MG-1018 operation manual B. Cfm Tables

Page 6
B. CFM TABLES

All installations and services must be performed by qualified service personnel.

B. CFM TABLES

The following tables contain blower speed settings and their respective air flowrates for the ECM blower motor. To change air flowrates from that of the shipped settings, use the respective S3 and S4 dipswitches on the furnace’s integrated control board (see Figure 1).

HEATING SPEEDS

CDX1-75

Dip

 

 

 

 

switch

 

Rise (oF)

High Fire

Rise (oF)

settings

Low fire CFM

CFM

7-OFF

 

 

 

 

8-OFF

760

64

931

70

7-ON

 

 

 

 

8-OFF

708

69

867

75

7-OFF

 

 

 

 

8-ON

826

59

1012

65

7-ON

 

 

 

 

8-ON

909

54

1114

59

CHX1-75

Dip

 

 

 

 

switch

 

Rise (oF)

High Fire

Rise (oF)

settings

Low fire CFM

CFM

7-OFF

 

 

 

 

8-OFF

760

60

931

70

7-ON

 

 

 

 

8-OFF

708

65

867

75

7-OFF

 

 

 

 

8-ON

826

55

1012

65

7-ON

 

 

 

 

8-ON

909

50

1114

59

CDX1-100

Dip

 

 

 

High Fire

 

switch

 

Rise (oF)

 

Rise (oF)

settings

Low fire CFM

 

CFM

7-OFF

 

 

 

 

 

8-OFF

1015

64

 

1243

70

7-ON

 

 

 

 

 

8-OFF

947

69

 

1160

75

7-OFF

 

 

 

 

 

8-ON

1094

60

 

1340

65

7-ON

 

 

 

 

 

8-ON

1184

55

 

1450

60

 

 

 

 

 

 

 

 

CDX1-125

 

 

Dip

 

 

 

 

 

switch

 

Rise (oF)

 

High Fire

Rise (oF)

settings

Low fire CFM

 

CFM

7-OFF

 

 

 

 

 

8-OFF

1270

64

 

1556

70

7-ON

 

 

 

 

 

8-OFF

1185

69

 

1452

75

7-OFF

 

 

 

 

 

8-ON

1366

60

 

1673

65

7-ON

 

 

 

 

 

8-ON

1480

55

 

1813

60

CHX1-100

Dip

 

 

 

 

 

switch

 

Rise (oF)

 

High Fire

Rise (oF)

settings

Low fire CFM

 

CFM

7-OFF

 

 

 

 

 

8-OFF

1015

60

 

1243

70

7-ON

 

 

 

 

 

8-OFF

947

64

 

1160

75

7-OFF

 

 

 

 

 

8-ON

1094

56

 

1340

65

7-ON

 

 

 

 

 

8-ON

1184

51

 

1450

60

 

 

 

 

 

 

 

 

CHX1-125

 

 

Dip

 

 

 

 

 

switch

 

Rise (oF)

 

High Fire

Rise (oF)

settings

Low fire CFM

 

CFM

7-OFF

 

 

 

 

 

8-OFF

1270

60

 

1556

70

7-ON

 

 

 

 

 

8-OFF

1185

64

 

1452

75

7-OFF

 

 

 

 

 

8-ON

1366

56

 

1673

65

7-ON

 

 

 

 

 

8-ON

1480

51

 

1813

60

Manual backgroundManual backgroundManual background =FACTORY SHIPPED SETTINGS

4

Image 6
Contents MG-1018 FOR USE WITH MODELS CHX1-75N CDX1-75NCHX1-100N CDX1-100N CHX1-125N CDX1-125N INDEX SECTIONBEGINNING PAGE CHX1-75 POWER CHOKESMODEL NO CHX1-100CDX1-100 CDX1 SERIESCDX1-75 CDX1-125II.BLOWER INFORMATION A. WIRING Figure 1 BLOWER WIRINGB. CFM TABLES COOLING AND CONTINUOUS FAN SPEEDS CAUSE/PROCEDURE III.ECM TROUBLE SHOOTINGSYMPTOM Motor rocks slightly when startingDON’T Evidence of MoisturePerform Moisture Check Moisture CheckFigure 2 ECM PIN CONNECTORS B. TROUBLESHOOTING CHARTS