HP Class SMF, MMS and MRS Magnetic Motor Starters Full Voltage Non Reversing, Key Features Cont’d

Page 16

AC Controls

Magnetic Motor Starters — Full Voltage Non Reversing

Starters

Size 0–134

With ESP100 Solid State Overload

Key Features (Cont’d)

JRugged Industrial Design

JDual Voltage, Dual Frequency Coils

JOverload Test Feature

JFront Removable Auxiliary Contacts

JWide Range of Accessories

JEasy Coil Access

JWidest Selection of Overloads in the Industry

JSolid State, Melting Alloy, Bimetal, or Bimetal Ambient Compensated Overload Protection

JExclusive Half Sizes

JStraight Through Wiring

JGravity Dropout

JLarge Silver Cadmium Contacts

JUL Listed 508 File #E14900

JCSA Certified File #LR6535

JUniversal Mounting Plate

Application

Class 14 industrial magnetic starters are designed for across-the-line starting of single-phase and polyphase motors.

ESP100 starters combine the rugged characteristics of a NEMA rated contac- tor with a solid state overload which provides phase loss protection. It offers the industrial user greater protection and added life for motors in heavy duty applications. The inherent benefits of the ESP100 result in cost savings as well.

Starter with thermal overload relays (together with the proper heater ele- ments) help provide protection to motor windings from harmful currents and the resultant temperature rise that may be caused by overloading the motor, sus- tained low line voltage, or stalled rotor.

Size 0–134

With Melting Alloy Overload

These controls are available in NEMA sizes 00 through 6. ESP100 starters are available in NEMA sizes 0 through 6. In addition to the usual NEMA starter sizes, four exclusive Half Sizes—134, 212, 312, and 412—are offered. These integral sizes offer the same rugged, industrial construction as NEMA sizes, and ensure efficient operating performance. Half Sizes provide a real cost savings by cut- ting down on over capacity when NEMA sizes exceed the motor ratings.

Across the line or full voltage starting is used when motor starting torque can be applied safely and current inrush does not produce an objectional voltage drop. All starters are supplied with a NO hold- ing contact that in conjunction with an appropriate pilot device will provide low voltage protection or release.

Features

Size 0–6 Magnetic Starters include the following standard features:

Molded Coil — Magnetic coils are care- fully wound and then sealed in epoxy. Encapsulation helps seal out moisture, promotes heat transfer, and resists elec- trical, mechanical, and thermal stresses.

Dual Voltage / Dual Frequency Coil — Starters are available with dual voltage, dual frequency coils. They are designed to operate on either 50 or 60 Hertz.

ESP100 Solid State Overload Relays — These standard features of the ESP100 provide Extra Starter Performance.

JTrue phase loss protection; trips within 3 seconds.

JHigh accuracy trip curves; ±2% repeat trip accuracy.

JEase of use. Mount, wire and set FLA.

JOverload is self protected against short circuits.

Size 0–134

With Bimetal Overload

JOverload is self powered and requires no hard wiring or separate power source.

JSimple, versatile adjustment; over a 2:1 FLA adjustment range. Extendable to 4:1 with looping option.

JHeaterless construction minimizes energy costs and the costs of cabinet ventilation or cooling.

JClass 20 protection is standard. Class 10 and 30 protection are available.

JProvides motor protection to 50 / 60 Hertz.

Thermal Overload Relays — Melting alloy is supplied as standard; optional bimetal overload relay is available.

Ambient compensated bimetal version is also available. Bimetal types are convert- ible from manual to automatic reset and can be furnished with standard or quick trip heater elements. Melting alloy over- loads include a trip indicator and manual test feature. An isolated normally open or normally closed contact is available for

use on melting alloy overloads. Bimetal 15 overloads are also available with NC and

NO (SPDT) Form C contacts.

AC Controls

CSI Section 16160

Siemens Electrical Products and Systems

299

 

Specification Guide

 

Image 16
Contents Typical Wiring Diagrams Manual Starters and SwitchesGeneral AC Controls Manual Starters and Switches Features Horsepower RatingsClass SMF Heater Elements Dimensions General Purpose Flush MountingTwo Unit Devices Nema Type 1 General Purpose Enclosure General Purpose Flush Mounting for Two Unit DevicesManual Motor Starter Switches Dimension / Wiring DiagramsGeneral / Dimensions 3VU13 Enclosure DimensionsTechnical Data Manual Motor Starter ProtectorManual Motor Starters and Contactors General / Wiring DiagramsClass 11 Manual Motor Starters Motor Starters Magnetic Contactors ApplicationsCoil Data 14 Reference LiteratureLighting and Heating Contactors 21 2-12 Pole Dimensions Wiring Diagrams TypicalCompact Magnetic Contactors Lighting 21WE 2-12 PoleCLM Contactors 300 and 400 Amperes, 2- and 3-Pole Combination Lighting and Heating Features DescriptionMagnetic Latch Operation Ballast LoadDimensions Combination Starters Nema Sizes27 Contactor Technical Data Key FeaturesContactors Non-Reversing Magnetic Motor Starters Full Voltage Non Reversing Key Features Cont’dStarters Auxiliary Equipment Magnetic Motor Starters-Full Voltage Non ReversingSize 0 through Dimensions / Wiring Diagrams Contactor DimensionsPole Single Phase Magnetic Contactors Size Sizes 2-31/2 Pole 3 Phase Magnetic Contactors Size 4 1/ 2Enclosure Dimensions Enclosures303 Full Voltage, Non-Reversing Starters Nema Sizes RatingsTorque Characteristics 33 3-Phase Multi-Speed StarterMulti-Speed Starters Nema Sizes Combination Multi-Speed StarterAuto Transformer Starter Wye Delta StarterPart Winding Starter OperationPhase Loss Solid-State Reduced Voltage StartersShorted SCRa Pump Stopa36 Solid-State Reduced Voltage Starters Pilot Device Units and Indicator Lights Type 3SBO Pilot Device UnitsEnclosed Pilot Device Stations Enclosed Pilot Device StationsGuide Form Specifications SpecificationsReduced Voltage Autotransformer Starters Multi-Speed StartersReduced Voltage Wye Delta Starters Reduced Voltage, Part Winding Starters