Type 3VU13 Manual Motor Starter Protector

Siemens 3VU13 is a 3-phase manual starter providing adjustable overload protection, optional field installed under- voltage protection, and short circuit protection.

Features

JBuilt-in Short Circuit Protection. Short circuit protection provided by the usual branch circuit protection device feeding a manual starter (fuse or cir- cuit breaker in accordance with NEC 430-52) may not protect a common manual starter. The factory built-in instantaneous trip of the Motor Starter Protector will protect the starter as well as the cable and motor during low level faults.

3VU13 Enclosure Dimensions

JThe Manual Starters Meet or Exceed Requirements of NEMA, EEMAC, UL, CSA, IEC, VDE and Other International Standards. The built-in instantaneous magnetic trip (similar to a circuit breaker with arc chamber) provides self protection against low-level short circuits.

JMotor Ratings — Up to 25 HP 3- Phase and 10 HP Single Phase.

JClass 10 Adjustable Ambient Compensated Overload Protection.

JPhase Loss Sensitivity.

JUndervoltage Protection — UV trip module may be added in field.

JShunt Trip Module is also field adda- ble.

JAvailable in Open Styles, NEMA 1 and 3R, watertight, dusttight, under table, and flush mount enclosures.

J1 NO and 1 NC Auxiliary Contacts Standard.

JGroup Installation - UL 508. The 3VU13 is suitable for Group Installation at 5kA 600 volts maximum with any fuse up to 1200 amperes or any inverse time circuit breaker up to 1200 amperes. The 3VU13 can be installed with or without Siemens con- tactors type 3TF2 or 3TF30 to 3TF34 in series. For higher interrupting rat- ings, consult Siemens.

Overlead and Magnetic Trip Tripping Characteristics

Table 15.10

Technical Data

 

 

Manual Motor Starter Protector

 

 

Type

 

3VU13

Maximum Rated Continuous

25

 

Current (Amperes)

 

 

 

Rated Operating Voltage AC

 

 

—Power Circuit

 

600V

—Control Circuit

 

 

 

Ambient Temperature

– 20 +

55

Compensation °C

 

 

Maximum Rated HP of

 

 

3-phase Motors At:

 

 

—AC 200V

 

5

 

—AC 240V

 

7 12

—AC 460V

 

15

 

—AC 575V

 

20

 

15

AC Controls

CSI Section 16160

Siemens Electrical Products and Systems

289

 

Specification Guide

 

Image 6
Contents Manual Starters and Switches Typical Wiring DiagramsGeneral AC Controls Horsepower Ratings Manual Starters and Switches FeaturesClass SMF Heater Elements Two Unit Devices Nema Type 1 General Purpose Enclosure DimensionsGeneral Purpose Flush Mounting General Purpose Flush Mounting for Two Unit DevicesManual Motor Starter Switches Dimension / Wiring DiagramsTechnical Data General / Dimensions3VU13 Enclosure Dimensions Manual Motor Starter ProtectorGeneral / Wiring Diagrams Manual Motor Starters and ContactorsClass 11 Manual Motor Starters Motor Starters Coil Data Magnetic ContactorsApplications 14 Reference LiteratureLighting and Heating Contactors Compact Magnetic Contactors Lighting 21 2-12 Pole DimensionsWiring Diagrams Typical 21WE 2-12 PoleCLM Contactors 300 and 400 Amperes, 2- and 3-Pole Magnetic Latch Operation Combination Lighting and Heating FeaturesDescription Ballast LoadDimensions Combination Starters Nema SizesKey Features 27 Contactor Technical DataContactors Non-Reversing Key Features Cont’d Magnetic Motor Starters Full Voltage Non ReversingStarters Magnetic Motor Starters-Full Voltage Non Reversing Auxiliary EquipmentSize 0 through Pole Single Phase Magnetic Contactors Size Dimensions / Wiring DiagramsContactor Dimensions Sizes 2-31/2 Pole 3 Phase Magnetic Contactors Size 4 1/ 2Enclosure Dimensions Enclosures303 Full Voltage, Non-Reversing Starters Nema Sizes RatingsMulti-Speed Starters Nema Sizes Torque Characteristics33 3-Phase Multi-Speed Starter Combination Multi-Speed StarterPart Winding Starter Auto Transformer StarterWye Delta Starter OperationShorted SCRa Phase LossSolid-State Reduced Voltage Starters Pump Stopa36 Solid-State Reduced Voltage Starters Pilot Device Units and Indicator Lights Type 3SBO Pilot Device UnitsEnclosed Pilot Device Stations Enclosed Pilot Device StationsGuide Form Specifications SpecificationsReduced Voltage Wye Delta Starters Reduced Voltage Autotransformer StartersMulti-Speed Starters Reduced Voltage, Part Winding Starters