HP manual Burner Operation Record the Readings at Steady State, To light the SU-2A Gas Burner

Page 11

11

LIGHTING INSTRUCTIONS

To light the SU-2A Gas Burner

1.Set the thermostat to the lowest temperature

2.The control knob on the gas valve should be in the “OFF” position for at least five minutes.

3.Rotate the control knob counter- clockwise to the “ON” position and set the thermostat to the desired temperature settings

Reset, if Flame Lockout Occurs

1.Turn the thermostat off, or turn the main power off

2.Wait five minutes

3.Turn the main power on

To shut the burner off

1.Rotate the control knob on the gas valve to the “OFF” position

2.Set the thermostat to the lowest temperature

3.Turn Main Power Off.

BURNER OPERATION

Before turning the burner on, check for gas supply leaks. Check the wiring diagrams; install manometers before and after the gas valve. Keep the observation port of the boiler or furnace open. Follow the instructions on the nameplate of the burner to turn it on. Follow the sequence of operations for the control (see pages 9 and 10). Use a combustion analyzer and record the readings below.

BURNER OPERATION: Record the Readings at Steady State

Draft over fire at steady state (should be –0.02 “W.C. or zero)

NOTE: This may vary for OEM applications.

Natural Gas CO2 % = (9.0% to 9.8%) or O2 % = (5.0% to 3.5%)

LP Gas CO2 % = (10.5% to 11.5%) or O2 % = (5.0% to 3.5%)

Stack Temperature (300o F minimum, 550oF maximum)

Percentage of Carbon Monoxide (CO) in PPM

Incoming Gas/LP pressure = “W.C. (minimum 5”)

Natural Gas manifold gas pressure = “W.C. (3.5” required + - 0.3”)

NOTE: This may vary for OEM applications.

LP Gas manifold gas pressure = “W.C. (2.3” required + - 0.3”)

Carbon Monoxide in flue ( less than 100 PPM ideal; should not exceed 400 PPM Oxygen free)

Image 11
Contents Manual for SU-2A Gas Burner Burner Description Chart 1 Natural Gas and LPAIR for Combustion Chart 2 Minimum Firing Chamber DimensionsConverting OIL to GAS Converting Coal to GASChimney Requirements Chimney and Fresh Air DimensionsVent Pipe and Draft Hood Sizes Installing the BurnerGAS Service & Pipe Capacity Gas Burner Piping Chart 5 Burner Orifice Sizing For Natural Gas And LP Orifice InstallationInstalling the Chimney LINER, Draft Diverter Vent Pipe Fenwal 2466H Electric WiringHoneywell S89F Wiring Diagram for Honeywell S89FTo shut the burner off Reset, if Flame Lockout OccursBurner Operation Record the Readings at Steady State To light the SU-2A Gas BurnerWhen to adjust the Head When to adjust the AirPulsation at start CO content is too highBurner motor runs Burner locks out after 4 seconds5SAY To be FIXED/ATTACHED Near Burner