ORIFICE INSTALLATION

All burners are equipped with an orifice set at the minimum firing rate (except for OEM packaged units). Drilling the orifice increases the firing rate. To drill the orifice, first open the union and then unscrew the orifice from inside the union. Determine the proper orifice size for the desired firing rate and drill the orifice (see Chart 5). Replace the orifice in the union and tighten the union so that it is gas tight. Once installed, a higher or lower firing rate can be achieved by raising or lowering the manifold pressure by +/- 0.3”. Pressure changes can only be made when the burner is running. The typical working manifold pressure for natural gas is 3.5” W.C. (2.3” W.C. for LP). The maximum inlet pressure at the gas valve is 11” W.C.; the minimum is 5” W.C. (for the purpose of input adjustment).

Note: The manifold pressure may vary for OEM packaged units.

Chart 5: Burner Orifice Sizing For Natural Gas And LP*

Orifice Size

Drill

Manifold Pressure at 3.5”

Manifold Pressure at 2.3”

Approximate

Approximate

(inches)

Size

W.C. for Nat Gas (BTU)

W.C. for L.P. (BTU)

Head Setting

Air Setting

5/32

0.156

50,000

50,000

21

0

3/16

0.188

80,000

80,000

18

2

7/32

0.219

90,000

90,000

12

6

15/64

0.234

122,000

122,000

18

14

9/32

0.281

146,000

146,000

14

11

19/64

0.297

160,000

160,000

10

10

27/64

0.422

200,000

200,000

3

15

1/2

no

250,000

250,000

1

20

 

orifice

 

 

 

 

* Assumes 0” to –0.02” Draft over fire

INSTALLING THE CHIMNEY LINER, DRAFT DIVERTER AND

VENT PIPE

Some utilities require new chimney liners for all gas installations. Use a corrosion resistant chimney liner (approved for gas service) of the same size as the vent pipe. Use an CSA or U.L. listed draft diverter only if you can maintain draft over fire. Otherwise, it is better to use a double swing draft regulator, listed by CSA or U.L. When the burner is used as a conversion burner, draft over fire should be maintained as –0.02” W.C. by adjusting the regulator when the burner is fired. The installer should follow the barometric draft regulator manufacturer’s instructions for complete details for installations and adjustments. The vent pipe should extend only to (but not beyond) the inside wall of the chimney.

Image 8
Contents Manual for SU-2A Gas Burner Chart 1 Natural Gas and LP Burner DescriptionChart 2 Minimum Firing Chamber Dimensions Converting OIL to GASConverting Coal to GAS AIR for CombustionChimney and Fresh Air Dimensions Chimney RequirementsInstalling the Burner Vent Pipe and Draft Hood SizesGAS Service & Pipe Capacity Gas Burner Piping Chart 5 Burner Orifice Sizing For Natural Gas And LP Orifice InstallationInstalling the Chimney LINER, Draft Diverter Vent Pipe Electric Wiring Fenwal 2466HWiring Diagram for Honeywell S89F Honeywell S89FReset, if Flame Lockout Occurs Burner Operation Record the Readings at Steady StateTo light the SU-2A Gas Burner To shut the burner offWhen to adjust the Air When to adjust the HeadCO content is too high Burner motor runsBurner locks out after 4 seconds Pulsation at start5SAY To be FIXED/ATTACHED Near Burner