HP SU-2A manual Electric Wiring, Fenwal 2466H

Page 9

9

ELECTRIC WIRING

These gas burners are manufactured for use with 120 volt, 60 cycle, single-phase electric current. The installation must comply and be grounded in accordance with the National Board of Fire Underwriters and National Electric Code ANSI/NFPA No. 70-1987 (or the latest addition). All applicable local codes should be followed as well.

Installation wiring should be wired through each limit control or interlock, while operating controls (like the thermostat) should be treated as 24-Volt wiring. The burner has its own 24 Volt AC power supply. Do not add a 24 Volt AC transformer for the burner wiring. Do not use the 24 Volt transformer found on the burner to power other items in the heating system, such spill switches, etc. Follow the wiring diagrams provided below:

Fig. 4 Wiring Diagram for Fenwal 2466H

SEQUENCE OF OPERATIONS

Fenwal 2466H 036-111

1.All limits are closed and 120-volt power is on for the burner.

2.T-T terminals are closed (24-volt power carrying lines; do not power this.) Sometimes, T-T terminals are jumped with a wire nut for burners not set for post-purge.

3.Burner motor starts and pre-purge begins

4.Burner housing pressurizes and proves air flow - contacts closed. {Note: if the contacts are closed before the motor starts, blower motor runs continuously. Diagnostic light flashes once every 3 seconds.}

5.At the end of pre-purge, ignition spark starts (audible sound) and the redundant gas valve opens for 4 seconds. (Trial for ignition)

6.Within 4 seconds, gas flame is established and the flame rod carries current to prove the flame {Note: a minimum of 0.7 micro amps are required; 5 micro amps is not uncommon.}

7.Flame remains till operating limit is open. If T-T is used to fire the burner (field wired for post- purge), the burner will go into post-purge once the thermostat is satisfied (T-T open). These burners have 60 seconds post purge.

8.If the flame is not established, the control will attempt ignition two more times before locking out for 60 minutes. The control will then attempt to re-establish the flame every 60 minutes. To reset the control, interrupt power for five minutes to start the sequence again.

Image 9
Contents Manual for SU-2A Gas Burner Burner Description Chart 1 Natural Gas and LPConverting OIL to GAS Chart 2 Minimum Firing Chamber DimensionsConverting Coal to GAS AIR for CombustionChimney Requirements Chimney and Fresh Air DimensionsVent Pipe and Draft Hood Sizes Installing the BurnerGAS Service & Pipe Capacity Gas Burner Piping Orifice Installation Installing the Chimney LINER, Draft Diverter Vent PipeChart 5 Burner Orifice Sizing For Natural Gas And LP Fenwal 2466H Electric WiringHoneywell S89F Wiring Diagram for Honeywell S89FBurner Operation Record the Readings at Steady State Reset, if Flame Lockout OccursTo light the SU-2A Gas Burner To shut the burner offWhen to adjust the Head When to adjust the AirBurner motor runs CO content is too highBurner locks out after 4 seconds Pulsation at start5SAY To be FIXED/ATTACHED Near Burner