TUBULAR UNIT HEATER
HIGH ALTITUDE DERATION
This Tubular Unit Heater has been manufactured utilizing standard burner orifices and a normal manifold pressure setting as per the specifications shown on your unit rating plate.
All unit deration must be done through field adjustments by a qualified technician. Once the proper adjustments are made in the field, attach label
Refer to Installation Instruction section on Adjustments- Gas Input Rate for adjusting the manifold pressure.
Table 5A
|
| NATURAL GAS | PROPANE (LP) GAS | ||
|
|
|
|
|
|
|
| Heating* | Manifold | Heating* | Manifold |
Altitude | Value | Pressure | Value | Pressure | |
(Feet) | BTU/Cu. ft. | (In. W.C.) | BTU/Cu. ft. | (In. W.C.) | |
|
|
|
|
|
|
2,000 |
| 948 | 3.5 | 2,278 | 8.6 |
|
|
|
|
|
|
2,500 |
| 931 | 3.5 | 2,237 | 8.5 |
|
|
|
|
|
|
3,000 |
| 914 | 3.3 | 2,196 | 8.4 |
|
|
|
|
|
|
3,500 |
| 897 | 3.2 | 2,156 | 8.4 |
|
|
|
|
|
|
4,000 |
| 881 | 3.2 | 2,116 | 8.3 |
|
|
|
|
|
|
4,500 |
| 865 | 3.2 | 2,077 | 8.2 |
|
|
|
|
|
|
5,000 |
| 849 | 3.1 | 2,039 | 8.1 |
|
|
|
|
|
|
5,500 |
| 833 | 3.1 | 2,000 | 8.0 |
|
|
|
|
|
|
6,000 |
| 818 | 3.0 | 1,964 | 7.9 |
|
|
|
|
|
|
6,500 |
| 802 | 3.0 | 1,927 | 7.7 |
|
|
|
|
|
|
7,000 |
| 787 | 2.9 | 1,891 | 7.6 |
|
|
|
|
|
|
7,500 |
| 771 | 2.9 | 1,853 | 7.5 |
|
|
|
|
|
|
8,000 |
| 756 | 2.8 | 1,817 | 7.4 |
|
|
|
|
|
|
8,500 |
| 741 | 2.8 | 1,781 | 7.2 |
|
|
|
|
|
|
9,000 |
| 726 | 2.7 | 1,745 | 7.1 |
|
|
|
|
|
|
9,500 |
| 711 | 2.7 | 1,709 | 6.9 |
|
|
|
|
|
|
10,000 |
| 696 | 2.6 | 1,673 | 6.8 |
|
|
|
|
|
|
*Notes:
1.Consult local utility for actual heating value.
2.Tables based on heating value of 1,050 BTU/Cu. ft. at sea level.
19