Table 7 - Tubular Propeller Troubleshooting Guide

SYMPTOMS

 

POSSIBLE CAUSE(S)

 

CORRECTIVE ACTION

 

 

 

 

Q. Cold air is delivered during

1. Incorrect manifold pressure or input.

1.

Refer to “Operation”.

heater operation.

2. Air throughput too high.

2.

Refer to “Operation”.

 

 

 

 

R. High limit tripping.

1. Unit is over fired.

1.

Burner orifices may be too large, verify

 

 

 

 

and replace.

 

2.

Air flow is low.

2.

Check for proper voltage, ensure fan

 

 

 

 

blade is correct.

 

3.

Defective switch.

3.

Check operation of switch, did the switch

 

 

 

 

open when unit is running or is the switch

 

 

 

 

open during start-up.

 

4.

Defective control board.

4.

Check for 24v on line side of the high limit.

 

 

 

 

Constant voltage should be recorded if not

 

 

 

 

control board is suspect. Check flash code.

 

 

 

 

S. Power ventor will not run.

1. Loose wiring or connections.

1.

Check all wring in the power vent circuit to

 

 

 

 

ensure good connection, including “Neutral”.

 

2.

Motor overload is tripped or bad motor.

2.

Check for 115v between motor leads and

 

3.

Bad control board.

 

check amp draw of motor. Replace if needed.

 

3.

Check for continuous 115v on terminal

 

 

 

 

“CBM Blower” and neutral during call for

 

 

 

 

heat. If not present and all checks are

 

 

 

 

normal, replace.

 

 

 

 

T. Power ventor turns on and off

1. Power ventor improperly wired.

1.

Check power ventor circuit per wiring

during operation.

2.

Motor overload cycling or defective motor.

 

diagram.

 

2.

Check motor voltage and amp draw to motor

 

3.

Defective control board.

 

name plate, replace if motor found defective.

 

3.

Check for continuous 115v on terminal

 

 

 

 

“CMB Blower” during call for heat, replace

 

 

 

 

board if found defective.

 

 

 

 

U. Power ventor will not stop.

1. Power ventor improperly wired.

1.

Check power ventor circuit per wiring

 

2.

Main burner did not light on call for heat.

 

diagram.

 

2.

Heater is in lockout mode check flash code

 

3.

Defective control board.

 

table for problem.

 

3.

No flash codes present along with no call

 

 

 

 

for heat, replace control board.

 

 

 

 

 

25

Image 25
Contents Receiving Instructions Tubular GAS Fired Direct Spark Propeller Unit HeatersDescription Table of ContentsGeneral Safety Information Dimensional Drawing Tubular 30 thru 90 Propeller Unit Heater Installation Installation Pipe Sizing GAS PipingGas Pipe Size Gas Piping Requirements Pipe InstallationElectrical Connections Thermostat Wiring and LocationElectrical Connections Venting Additional Requirements for Canadian InstallationsVenting into an unlined masonry chimney is prohibited Venting Categories Vertically Vented Unit Heaters CategoryNot apply to equipment specified Within this manualVent Systems Termination Clearance Requirements Structure Vent Maximum Number Maximum Horizontal Minimum Extension Category I Horizontal Venting RequirementsVent Support Horizontally Vented Unit Heaters Category Type B Draft Hood Connector Venting Venting Explanation of Controls See Figure OperationDetermine and Correct the Cause of the flame roll-out Shut DownGAS Input Rate Primary AIR Shutter AdjustmentMain Burner Orifice Schedule Tubular Unit Heater High Altitude DerationNever over oil the motor or premature failure may occur Periodic ServiceSymptoms Possible Causes Corrective Action Tubular Propeller Troubleshooting GuideRealign power ventor wheel Check for continuous 115v on terminal LED Status Indicates CHECK/REPAIR Troubleshooting with LED Indicator AssistanceItemDescription Propeller Parts HOW to Order Replacement Parts With power and gas on With power and gas offPRE-INSPECTION Information General