Table 7 - Tubular Propeller Troubleshooting Guide
| SYMPTOMS | 
 | POSSIBLE CAUSE(S) | 
 | CORRECTIVE ACTION | 
| 
 | 
 | 
 | 
 | |
| Q. Cold air is delivered during | 1. Incorrect manifold pressure or input. | 1. | Refer to “Operation”. | |
| heater operation. | 2. Air throughput too high. | 2. | Refer to “Operation”. | |
| 
 | 
 | 
 | 
 | |
| R. High limit tripping. | 1. Unit is over fired. | 1. | Burner orifices may be too large, verify | |
| 
 | 
 | 
 | 
 | and replace. | 
| 
 | 2. | Air flow is low. | 2. | Check for proper voltage, ensure fan | 
| 
 | 
 | 
 | 
 | blade is correct. | 
| 
 | 3. | Defective switch. | 3. | Check operation of switch, did the switch | 
| 
 | 
 | 
 | 
 | open when unit is running or is the switch | 
| 
 | 
 | 
 | 
 | open during  | 
| 
 | 4. | Defective control board. | 4. | Check for 24v on line side of the high limit. | 
| 
 | 
 | 
 | 
 | Constant voltage should be recorded if not | 
| 
 | 
 | 
 | 
 | control board is suspect. Check flash code. | 
| 
 | 
 | 
 | 
 | |
| S. Power ventor will not run. | 1. Loose wiring or connections. | 1. | Check all wring in the power vent circuit to | |
| 
 | 
 | 
 | 
 | ensure good connection, including “Neutral”. | 
| 
 | 2. | Motor overload is tripped or bad motor. | 2. | Check for 115v between motor leads and | 
| 
 | 3. | Bad control board. | 
 | check amp draw of motor. Replace if needed. | 
| 
 | 3. | Check for continuous 115v on terminal | ||
| 
 | 
 | 
 | 
 | “CBM Blower” and neutral during call for | 
| 
 | 
 | 
 | 
 | heat. If not present and all checks are | 
| 
 | 
 | 
 | 
 | normal, replace. | 
| 
 | 
 | 
 | 
 | |
| T. Power ventor turns on and off | 1. Power ventor improperly wired. | 1. | Check power ventor circuit per wiring | |
| during operation. | 2. | Motor overload cycling or defective motor. | 
 | diagram. | 
| 
 | 2. | Check motor voltage and amp draw to motor | ||
| 
 | 3. | Defective control board. | 
 | name plate, replace if motor found defective. | 
| 
 | 3. | Check for continuous 115v on terminal | ||
| 
 | 
 | 
 | 
 | “CMB Blower” during call for heat, replace | 
| 
 | 
 | 
 | 
 | board if found defective. | 
| 
 | 
 | 
 | 
 | |
| U. Power ventor will not stop. | 1. Power ventor improperly wired. | 1. | Check power ventor circuit per wiring | |
| 
 | 2. | Main burner did not light on call for heat. | 
 | diagram. | 
| 
 | 2. | Heater is in lockout mode check flash code | ||
| 
 | 3. | Defective control board. | 
 | table for problem. | 
| 
 | 3. | No flash codes present along with no call | ||
| 
 | 
 | 
 | 
 | for heat, replace control board. | 
| 
 | 
 | 
 | 
 | 
 | 