HP Modular Cooling System manual Raised floor grounding

Page 26

Figure 16: Raised floor grounding

Voltage fluctuations and outages

The MCS 5042 is designed to provide immunity to power outages of less than one cycle. However, testing cannot conclusively rule out loss of service. Therefore, adherence to the following guidelines provides the best possible performance of power distribution systems for HP equipment:

Dedicated power source—Isolates the power distribution system from other circuits in the facility.

Missing-phase and low-voltage detectors—Shuts equipment down automatically when a severe power disruption occurs. For peripheral equipment, these devices are recommended but optional.

Online uninterruptible power supply (UPS)—Keeps input voltage to devices constant and must be considered if outages of one-half cycle or more are common. For more information, consult a qualified contractor or consultant, as necessary.

The MCS 5042 can be protected from the sources of many electrical disturbances by using:

An isolated power distribution system

Power conditioning equipment

Over-voltage and under-voltage detection and protection circuits

Shielding to attenuate higher frequency radiated electrical energy

Surge protective devices on power cables to protect equipment against electrical storms

26

Image 26
Contents Table of contents HP mc-Series 5042 Rack Site Preparation GuideNotational conventions Acronyms and abbreviations Safety and regulatory informationPreface Safety in material handling Japanese noticeMCS 5042 configuration options OverviewProduct overview MCS 5042 air flowKey MCS 5042 components MCS 5042 component locations Reference Water module Fan module AC transfer switch MCS 5042 specifications Physical specificationsFacility planning for MCS 5042 implementation OverviewSpace and positioning considerations Page Page Page Page Page Page Page Page Page Page MCS 5042 weight calculation Qty Component Page Electrical considerations Central ground stud location inside the IT rack Raised floor grounding MCS 5042 power cords Nema L6-20-to-Procon-A5 Power Cord Single-source AC power connection Coolant source planning Dedicated chiller unit directly supplying the MCS Description Quantity Above the unit 280 cm 110 inches 300 cm 118 inches Shows the recommended facility piping approaches to the MCS MCS 5042 hose openings Page Page Page Page Page Recommended plumbing configuration for the MCS Pressure rating 400 psi WOG, 125psi WSP Page Coolant requirements General thermal requirementsCoolant implementation flow chart for one rack Page Approximate fan step at certain cooling capacity Page Page Page Page Page Control system Before installing and running active componentsEnvironmental considerations Appendix a Forms and checklists Delivery survey formPre-installation checklists Page Metric equivalents Appendix B Conversion factors and formulasConversion factors for refrigeration KVA conversionsGlossary ASLTerm Description Typical power consumption Restricted rights legend Legal noticesFor more information
Related manuals
Manual 10 pages 27.17 Kb Manual 84 pages 16.27 Kb Manual 93 pages 20.21 Kb Manual 4 pages 15.71 Kb Manual 16 pages 5.24 Kb Manual 83 pages 40.42 Kb

Modular Cooling System specifications

The HP Modular Cooling System (MCS) is a state-of-the-art solution designed to efficiently manage the heat generated by high-density IT environments. As data centers face the ever-increasing demand for processing power, traditional cooling methods often fall short, leading to inefficiencies and raised energy costs. The HP MCS addresses this issue with a scalable, flexible design that optimizes cooling performance while minimizing energy consumption.

One of the main features of the HP Modular Cooling System is its modular architecture, which allows for easy expansion and customization based on the specific needs of a data center. This scalability means that as a facility grows or changes, the cooling system can be modified without the need for extensive renovations or replacements. The MCS can be installed in various configurations, further enhancing its versatility.

The technology behind the HP MCS includes advanced cooling methods such as direct evaporative cooling and chilled water cooling. Direct evaporative cooling utilizes the principles of evaporative heat exchange to cool air without excessive energy consumption, making it an eco-friendly choice. In contrast, chilled water cooling uses a network of pipes filled with chilled water to remove heat from the server environment efficiently. This combination allows the MCS to adapt to various heat loads and ambient conditions.

Another notable characteristic of the HP Modular Cooling System is its intelligent controls and sensors. These components continually monitor temperature and humidity levels within the data center, automatically adjusting cooling output to maintain optimal conditions. This proactive approach helps to prevent overheating, reduces energy usage, and ensures the longevity of IT equipment.

Energy efficiency is further enhanced through the MCS's integration with HP's monitoring and management software. This software analyzes cooling performance trends, providing actionable insights for facility managers, enabling them to make informed decisions regarding cooling strategies. Additionally, the system is designed with environmentally sustainable practices in mind, aligning with global initiatives to reduce carbon footprints and promote green technology.

The HP Modular Cooling System stands out for its combination of innovative technologies, flexibility, and a commitment to energy efficiency. As data centers continue to evolve, the MCS remains a crucial asset in the pursuit of optimized performance and sustainability, providing a reliable solution to meet the demanding cooling needs of modern IT infrastructure.