HP Modular Cooling System manual Space and positioning considerations

Page 11

Space and positioning considerations

The MCS 5042 is larger (and, when fully populated, heavier) than a standard 19-inch equipment rack. Therefore, space required for maneuvering, operating, and servicing the MCS 5042 is greater than standard-sized racks.

Delivery space requirements

You must ensure the facility has adequate space to receive and remove the MCS 5042 from the shipping pallet. When unloading the MCS 5042, take into consideration the following:

Forklifts must enter and transport the shipping pallet from the side.

Delivery plans must include the possible removal of walls or door.

A total length of approximately 6.1 m (20 feet) must be allowed to safely remove the MCS 5042 from the shipping pallet down the provided ramps.

The packaged dimensions of the MCS 5042 preconfigured with a single IT rack are (including shock pallet and cartons):

2285 mm (90 inches) height x 1219 mm (48 inches) width x 1829 mm (72 inches) depth

Maneuvering space requirements

When maneuvering the MCS 5042, use the following guidelines:

Racks with casters must be moved with care. Sudden stops, excessive force, and uneven surfaces might cause the product to overturn.

Both the cooling unit and the IT rack have casters that are fixed at the front and swivel in the back due to stability and safety concerns. Therefore it is easier to move the MCS 5042with the back as the leading edge.

For long, straight distances roll the MCS 5042 with the front, fixed casters leading. For better mobility lead with the rear, swiveling casters.

When rolling the MCS 5042, push firmly on the front doors frame and not the door mesh of the IT rack. The points on where to push the MCS 5042 are marked by factory.

Make sure the rooms and doors are large enough to accommodate the movement of the MCS 5042 cabinet into the data center.

When transporting the MCS 5042 to a different building floor, be sure elevators have adequate load capacity, floor space, and door clearance to accommodate the rack. The MCS 5042 pallet can only be moved with forklifts from the side, which has a length of 1829 mm (72 inches).

When transporting the MCS 5042 within a building, be sure that doorway thresholds are adequate to hold the rack. HP does not recommend that you lift or transport the MCS 5042 by eyebolts that are attached to the upper corners of the cabinet.

Warning:

To reduce risk of personal injury or damage to the equipment, a single person must not attempt to move equipment racks alone. Obtain adequate assistance to stabilize the rack during movement or hire professional equipment riggers.

11

Image 11
Contents HP mc-Series 5042 Rack Site Preparation Guide Table of contentsNotational conventions Acronyms and abbreviations Safety and regulatory informationPreface Japanese notice Safety in material handlingOverview MCS 5042 configuration optionsMCS 5042 air flow Product overviewKey MCS 5042 components MCS 5042 component locations Reference Water module Fan module AC transfer switch Physical specifications MCS 5042 specificationsOverview Facility planning for MCS 5042 implementationSpace and positioning considerations Page Page Page Page Page Page Page Page Page Page MCS 5042 weight calculation Qty Component Page Electrical considerations Central ground stud location inside the IT rack Raised floor grounding MCS 5042 power cords Nema L6-20-to-Procon-A5 Power Cord Single-source AC power connection Coolant source planning Dedicated chiller unit directly supplying the MCS Description Quantity Above the unit 280 cm 110 inches 300 cm 118 inches Shows the recommended facility piping approaches to the MCS MCS 5042 hose openings Page Page Page Page Page Recommended plumbing configuration for the MCS Pressure rating 400 psi WOG, 125psi WSP Page General thermal requirements Coolant requirementsCoolant implementation flow chart for one rack Page Approximate fan step at certain cooling capacity Page Page Page Page Page Control system Before installing and running active componentsEnvironmental considerations Delivery survey form Appendix a Forms and checklistsPre-installation checklists Page KVA conversions Appendix B Conversion factors and formulasConversion factors for refrigeration Metric equivalentsASL GlossaryTerm Description Typical power consumption Restricted rights legend Legal noticesFor more information
Related manuals
Manual 10 pages 27.17 Kb Manual 84 pages 16.27 Kb Manual 93 pages 20.21 Kb Manual 4 pages 15.71 Kb Manual 16 pages 5.24 Kb Manual 83 pages 40.42 Kb

Modular Cooling System specifications

The HP Modular Cooling System (MCS) is a state-of-the-art solution designed to efficiently manage the heat generated by high-density IT environments. As data centers face the ever-increasing demand for processing power, traditional cooling methods often fall short, leading to inefficiencies and raised energy costs. The HP MCS addresses this issue with a scalable, flexible design that optimizes cooling performance while minimizing energy consumption.

One of the main features of the HP Modular Cooling System is its modular architecture, which allows for easy expansion and customization based on the specific needs of a data center. This scalability means that as a facility grows or changes, the cooling system can be modified without the need for extensive renovations or replacements. The MCS can be installed in various configurations, further enhancing its versatility.

The technology behind the HP MCS includes advanced cooling methods such as direct evaporative cooling and chilled water cooling. Direct evaporative cooling utilizes the principles of evaporative heat exchange to cool air without excessive energy consumption, making it an eco-friendly choice. In contrast, chilled water cooling uses a network of pipes filled with chilled water to remove heat from the server environment efficiently. This combination allows the MCS to adapt to various heat loads and ambient conditions.

Another notable characteristic of the HP Modular Cooling System is its intelligent controls and sensors. These components continually monitor temperature and humidity levels within the data center, automatically adjusting cooling output to maintain optimal conditions. This proactive approach helps to prevent overheating, reduces energy usage, and ensures the longevity of IT equipment.

Energy efficiency is further enhanced through the MCS's integration with HP's monitoring and management software. This software analyzes cooling performance trends, providing actionable insights for facility managers, enabling them to make informed decisions regarding cooling strategies. Additionally, the system is designed with environmentally sustainable practices in mind, aligning with global initiatives to reduce carbon footprints and promote green technology.

The HP Modular Cooling System stands out for its combination of innovative technologies, flexibility, and a commitment to energy efficiency. As data centers continue to evolve, the MCS remains a crucial asset in the pursuit of optimized performance and sustainability, providing a reliable solution to meet the demanding cooling needs of modern IT infrastructure.