Marley / NC Class Stainless CoolingTower / Specifications: Options

19

 

Specifications

Inlet Flow Control Valves:

8.2: Add the following to the end of the paragraph: Heavy-dutyflow-regulator valves shall be provided at the hot water inlet connections. These valves shall be disc-type, with cast iron bodies and stainless steel operating stems. There shall be a locking handle to maintain the valve setting in any position. Valves shall be right-angle configuration, precluding the need for inlet elbows.

Equalizer Flume Weir Gates:

11.2: Add the following paragraph under Cold Water Collection Basin: The interconnecting flume between cells shall be equipped with a removable cover plate to permit the shutdown of one cell for maintenance purposes, or to permit independent cell operation.

Sound Control

1.2Add the following paragraph under Base: The cooling tower shall be quiet operation, and shall produce an overall level of sound not higher than _______

dB(A) measured at _______ m from the locations in the table below. All low noise options and combinations shall be CTI Certified for thermal perfor- mance.

Location

63

125

250

500

1000

Discharge

 

 

 

 

 

Air Inlet

 

 

 

 

 

Cased Face

 

 

 

 

 

 

 

 

 

 

 

Location

2000

4000

8000

Overall dB(A)

Discharge

 

 

 

 

 

Air Inlet

 

 

 

 

 

Cased Face

 

 

 

 

 

Inlet Sound Attenuation

1.3Add the following paragraph under Base: The cooling tower shall be equipped with inlet sound attenuation baffles positioned and spaced verti- cally. The baffles will be spaced across the entire length and extend the full height of the air inlet. The baffles will be constructed of perforated sheet metal and contained within a steel

Specification Value

Marley flow-control valves have been a favorite of users since the 1950s. They remain serviceable for the life of the tower and provide a continuing means of flow- regulation between hot water basins—and between cells of multicell towers as well.

Where it is your intention to be able to operate both cells of the tower while the flume cover plate is installed, separate outlet connections, float valves and overflows must be provided for each cell. Likewise, this would require separate sensors and controls for basin heater systems, if installed.

Sound produced by a standard NC Cooling Tower operating in an unobstructed environ- ment will meet all but the most restrictive noise limitations—and will react favorably to natural attenuation. Where the cooling tower has been sized to operate within an

enclosure, the enclosure itself will have a damping effect on sound. Sound also declines with distance—by about 5 or 6 dB(A) each time the distance doubles. Where noise at a critical point is likely to exceed an acceptable limit, you have several options—listed below in ascending order of cost impact:

Where only a slight reduction in noise will satisfy—and the source of concern is in a particular direction—merely turning the cooling tower may be the answer. Less sound emanates from the cased face of the cooling tower than does from the air intake face.

In many cases, noise concerns are limited to nighttime, when ambi- ent noise levels are lower and neighbors are trying to sleep. You can usually resolve these situations by using two-speed motors—operating the fans at reduced speed without cycling “after hours”.The natural nighttime reduction in wet-bulb temperature makes this a very feasible solution in most areas of the world, but the need to avoid cycling may cause the cold water temperature to vary significantly.

A Marley Variable Speed Drive automatically minimize the tower’s noise level during periods of reduced load and/or reduced ambient

Image 19
Contents Marley NC Class Stainless Crossflow Cooling Tower Marley / NC Class Stainless CoolingTower / Contents Marley / NC Class Stainless CoolingTower Base Specifications Specification ValueThermal Performance and Efficiency WarrantyDesign Loading Construction Mechanical Equipment SpecificationsFill, Louvers and Drift Eliminators Casing, Fan Deck and Fan Guard Hot Water Distribution SystemCold Water Collection Basin AccessLadder Extension Convenience and Safety Options Guardrail and LadderLadder Safety Cage Ladder Safety GateGuardrail Ladder Extension Plenum Walkway Access Door PlatformInterior Mechanical Equipment Control Options Basin Heater Vibration Limit SwitchElectric Water Level Control Specifications Specification Value Marley Premium VFD System Fan Cylinder Extensions Miscellaneous Options Motor out of the AirstreamInlet Sound Attenuation Inlet Flow Control ValvesEqualizer Flume Weir Gates Sound ControlLow Noise Fan Outlet Sound AttenuationHigh Wind Load/Seismic Designs Ultra Low-Noise FanSingle Hot Water Inlet Connection per Cell Air Inlet ScreensBasin Sweeper Piping Multicell Basin Equalizer OutletsExtended Geareducer Lube Line with Dipstick Page Worcester WR3 8AB United Kingdom

SS-NC-08A specifications

The SPX Cooling Technologies SS-NC-08A is a cutting-edge, open-circuit cooling tower designed for a variety of industrial applications. Renowned for its efficiency and durability, the SS-NC-08A exemplifies modern engineering innovations, catering to facilities that require reliable temperature regulation while minimizing water usage.

One of the standout features of the SS-NC-08A is its superior thermal performance. Equipped with advanced fill media, this closed cooling tower optimizes heat transfer, allowing for enhanced cooling capacity in a compact footprint. This makes it an excellent choice for industries such as power generation, petrochemical processes, and manufacturing, where maintaining strict temperature control is essential.

In addition to its thermal performance, the SS-NC-08A is designed with energy efficiency in mind. Featuring a low-sound fan design, this unit minimizes operational noise, making it suitable for urban installations or environments where noise pollution is a concern. The axial fan technology used in the SS-NC-08A is not only energy-efficient but also capable of achieving high airflows with lower energy consumption compared to conventional fan designs.

The SS-NC-08A also integrates advanced corrosion-resistant coatings to prolong its lifecycle and minimize maintenance needs. This characteristic is particularly important for facilities operating in harsh environments with exposure to chemicals or brine solutions. The unit's robust construction ensures it can withstand the challenges of demanding applications, reducing downtime and repair costs.

Another key characteristic of the SS-NC-08A is its modular design. This allows for easy installation, maintenance, and scalability. Whether expanding a facility or replacing older systems, the modular nature of the SS-NC-08A streamlines the process. Additionally, it incorporates a simplified water distribution system that enhances water flow and distribution across the fill.

In conclusion, the SPX Cooling Technologies SS-NC-08A cooling tower stands as a reliable, efficient, and durable solution for various industrial cooling needs. With its advanced thermal performance, energy efficiency, corrosion resistance, and modular design, it addresses the requirements of today’s modern industries, ensuring optimal performance and longevity. This makes it an excellent investment for organizations aiming to maintain efficient operations while adhering to environmental sustainability goals.