SPX Cooling Technologies none Maintenance, Bushing Fastener Torque Values, Belt Tensioning

Page 21

Bushing Fastener Torque Values

Warning

Maintenance

Belt Tensioning

The belts are adjusted by means of a hinged base with tensioning bolts accessible through the access panel/fan guards. Check tension frequently during the first 24-48 hours of run-in operation. To properly adjust the belt tension, position the fan motor so that moderate pressure on the belt midway between the sheaves will produce a 12" deflection. Overtensioning shortens belt and bearing life. Keep belts free from foreign material which may cause slipping. Never apply belt dressing as this will damage the belt and cause early failure. A Dodge® V-Belt Tension Tester is an alternate method for tensioning V-belts. Check with you local belt supplier.

Sheave Alignment

The motor sheave is to be positioned as close as possible to the motor in order to minimize torque on the motor bushings.

The motor and fan sheaves may have grooves that are not used. The bottom surface of the motor and fan sheaves must be aligned within 3mm of each other and level within 12° (3mm in 300mm) in order to not adversely affect belt and sheave life.

Alignment can be achieved by placing a straight edge across the top of the sheaves making sure that it is level and measuring down to the bottom surface of both sheaves at four points.

The belt is located in the inboard set of grooves closest to the bearing.

Bushing

Fastener

Torque N·m

 

 

 

 

SD

14

- 20

8

SK

516 - 18

18

SF

38

- 16

30

E

12

- 13

48

Fluid Cooler Maintenance

Some maintenance procedures may require maintenance personnel to enter the fluid cooler.

The purchaser or owner is responsible for providing a safe method

for entering or exiting the access door.

21

Image 21
Contents Marley MC Fluid Cooler Page Contents Preparation Safety FirstFluid Cooler Location Shipment InstallationReceiving Fluid Cooler Hoisting Fluid CoolerFluid Cooler Installation When using a starter Motor WiringWhen using a VFD When using a two-speedstarterInstallation Mechanical Equipment Operation Fluid Cooler Start-UpWater System General Fluid Cooler OperationOperation Wintertime Operation Intermittent Wintertime Operation Protection Against Coil Freezing Model Coil VolumeMaintaining Water Quality Water Treatment and BlowdownBlowdown Fluid Cooler CleaningWhen water treatment chemicals are added, they should not be Fluid Cooler Maintenance MaintenanceBushing Fastener Torque Values Belt TensioningMaintenance Seasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies Services Maintenance Schedule Additional Services Trouble Cause Remedy TroubleshootingTroubleshooting Page Page Manual uk07-1185C