SPX Cooling Technologies none user manual Installation, Shipment, Receiving Fluid Cooler

Page 6

Caution

Warning

Installation

Shipment

Unless otherwise specified, the MC Fluid Cooler ships by truck (on flat bed trailers), which lets you receive, hoist, and install the tower in one continuous operation. Single-cell coolers ship on one truck. Multicell fluid coolers, depending on their size, may require more than one truck.

Responsibility for the condition of the fluid cooler upon its arrival belongs to the trucker—as does the coordination of multiple shipments, if required.

Receiving Fluid Cooler

Prior to unloading the fluid cooler from the delivering carrier, inspect the shipment for evidence of damage in transit. If damage is apparent, note the freight bill accordingly. This will support your future recovery claim.

Find and remove the installation instruction drawings and bills of material located in a plastic bag in the collection basin. This information should be kept for future reference and maintenance purposes.

Hoisting Fluid Cooler

All MC Fluid Cooler models consist of two modules per cell. The upper module includes hoisting clips at the bottom corners. Hoisting clips on the lower module are attached to the top at the horizontal cross channels. A Hoisting-Installationlabel which has hoisting dimensional information is located on the side casing near the tower centerline. Remove fluid cooler modules from the carrier and hoist into place according to the instruc- tions on the label.

MC Fluid Cooler upper and lower modules must be hoisted and set separately. Do not preassemble modules prior to hoisting.

Hoisting clips are provided for ease of unloading and positioning the fluid cooler. For overhead lifts or where additional safety is required, safety slings should also be placed under the fluid cooler modules. Under no circumstances should you combine the top and bottom modules of modular models and attempt to hoist them at the same time by utilizing the hoisting clips alone!

6

Image 6
Contents Marley MC Fluid Cooler Page Contents Safety First PreparationFluid Cooler Location Receiving Fluid Cooler InstallationShipment Hoisting Fluid CoolerFluid Cooler Installation Motor Wiring When using a starterWhen using a two-speedstarter When using a VFDInstallation Mechanical Equipment Operation Fluid Cooler Start-UpWater System Fluid Cooler Operation GeneralOperation Wintertime Operation Intermittent Wintertime Operation Model Coil Volume Protection Against Coil FreezingWater Treatment and Blowdown Maintaining Water QualityFluid Cooler Cleaning BlowdownWhen water treatment chemicals are added, they should not be Bushing Fastener Torque Values MaintenanceFluid Cooler Maintenance Belt TensioningMaintenance Seasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies Services Maintenance Schedule Additional Services Troubleshooting Trouble Cause RemedyTroubleshooting Page Page Manual uk07-1185C