SPX Cooling Technologies none user manual Maintenance Schedule

Page 26

Maintenance Schedule

Maintenance Service

Monthly

Semi-annually

Seasonal Startup or Annually

 

 

 

 

Inspect General Condition and Operation

x

 

x

 

 

 

 

Observe Operation of:

 

 

 

 

 

 

 

Mechanical–motor, pump, fan and drive mechanism

x

 

x

 

 

 

 

Makeup valve (if equipped)

x

 

x

 

 

 

 

Inspect for unusual noise or vibration

x

 

x

 

 

 

 

Inspect and Clean:

 

 

 

 

 

 

 

Air inlet

x

 

x

 

 

 

 

PVC drift eliminators

x

 

x

 

 

 

 

Distribution system and nozzles

x

 

x

 

 

 

 

Collection basin

x

 

x

 

 

 

 

Fan and pump motor exterior

x

 

x

 

 

 

 

Coil surface

 

x

 

 

 

 

 

Check:

 

 

 

 

 

 

 

Collection water basin level

x

 

x

 

 

 

 

Blowdown–adjust as required

x

 

x

 

 

 

 

Lube lines if equipped:

 

 

 

 

 

 

 

Check for leaks in hoses or fittings

x

R

x

 

 

 

 

Belt drive:

 

 

 

 

 

 

 

Fan shaft bearing lubrication (every 3 mo.)

 

every 3 months

every 3 months

 

 

 

 

Check and tighten support fasteners

 

 

x

 

 

 

 

Check shaft, sheave and belt alignment

 

 

x

 

 

 

 

Check belt tension and condition

 

x

x

 

 

 

 

Check sheave bushing fastener torque

 

 

x

 

 

 

 

Fan:

 

 

 

 

 

 

 

Check fan assembly fasteners

 

 

x

 

 

 

 

Motor:

 

 

 

 

 

 

 

Lubricate (grease as required)

 

 

R

 

 

 

 

Check mounting bolts for tightness

 

 

x

 

 

 

 

Operate at least

3 hours a month

3 hours a month

3 hours a month

 

 

 

 

Basin Heater (if equipped):

 

 

 

 

 

 

 

Check for proper operation of temp/low water level sensor

 

 

x

 

 

 

 

Inspect/clean buildup of contaminant from sensor

 

x

x

 

 

 

 

Structure:

 

 

 

 

 

 

 

Inspect/tighten all fasteners

 

x

x

 

 

 

 

Inspect and touch up all metal surfaces

 

 

x

 

 

 

 

R — Refer to Component User Manual

Note: It is recommended at least weekly, that the general operation and condition be observed. Pay attention to any changes in sound or vibration that may signify a need for closer inspection.

26

Image 26
Contents Marley MC Fluid Cooler Page Contents Safety First PreparationFluid Cooler Location Receiving Fluid Cooler InstallationShipment Hoisting Fluid CoolerFluid Cooler Installation Motor Wiring When using a starterWhen using a two-speedstarter When using a VFDInstallation Mechanical Equipment Water System OperationFluid Cooler Start-Up Fluid Cooler Operation GeneralOperation Wintertime Operation Intermittent Wintertime Operation Model Coil Volume Protection Against Coil FreezingWater Treatment and Blowdown Maintaining Water QualityFluid Cooler Cleaning BlowdownWhen water treatment chemicals are added, they should not be Bushing Fastener Torque Values MaintenanceFluid Cooler Maintenance Belt TensioningMaintenance Seasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies Services Maintenance Schedule Additional Services Troubleshooting Trouble Cause RemedyTroubleshooting Page Page Manual uk07-1185C