Toshiba RAV-SP1100UT-E, RAV-SP560AT-E Accessory and Refrigerant, Accessory and Installation Parts

Page 19

When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.

Install the air conditioner securely in a location where the base can sustain the weight adequately.

Perform the specified installation work to guard against an earthquake.

If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.

If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.

After the installation work, confirm that refrigerant gas does not leak.

If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.

Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply.

An insufficient power supply capacity or inappropriate installation may cause fire.

Use the specified cables for wiring connect the terminals securely fix. To prevent external forces applied to the terminals from affecting the terminals.

Be sure to provide grounding.

Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.

Conform to the regulations of the local electric company when wiring the power supply. Inappropriate grounding may cause electric shock.

Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks, and stays around the unit, a fire may occur.

Required tools for installation work

R410A (Special requirement)

1)Philips screw driver

2)Hole core drill (65 mm)

3)Spanner

4)Pipe cutter

5)Knife

6)Reamer

7)Gas leak detector

8)Tape measure

9)Thermometer

10)Mega-tester

11)Electro circuit tester

12)Hexagonal wrench

13)Flare tool

14)Pipe bender

15)Level vial

16)Metal saw

17)Gauge manifold

(Charge hose : R410A special requirement)

18)Vacuum pump

(Charge hose : R410A special requirement)

19)Torque wrench

1/4 (17 mm) 16 N•m (1.6 kgf•m) 3/8 (22 mm) 42 N•m (4.2 kgf•m) 1/2 (26 mm) 55 N•m (5.5 kgf•m)

5/8 (15.9 mm) 120 N•m (12.0 kgf•m)

20)Copper pipe gauge adjusting projection margin

21)Vacuum pump adapter

SP1100AT-E

SP1400AT-E

RAV-

RAV-

 

 

2 ACCESSORY AND REFRIGERANT

Accessory and Installation Parts

1

3

Outdoor unit

 

Installation manual x 1

Protective bush

Drain nipple

 

2

4

 

Guard material for

Waterproof rubber cap

passage part

Refrigerant Piping

Piping kit used for the conventional refrigerant cannot be used.

Use copper pipe with 0.8 mm or more thickness for Ø9.5.

Use copper pipe with 1.0 mm or more thickness for Ø15.9.

Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut attached to the main unit of the air conditioner, and use it.

51

Image 19
Contents Split Type Adoption of NEW Refrigerant Indoor Unit 4-Way Air Discharge Cassette Type New Refrigerant Air Conditioner Installation Precautions for SafetyTo Disconnect the Appliance from Main Power Supply Accessory and Installation Parts Refrigerant Piping Accessory and RefrigerantBefore installation Selection of InstallationObstacle at front side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at rear side Upper side is freeInstallation of Outdoor Unit Piping connection Optional Installation Parts Local ProcureRefrigerant Piping Connection For ReferenceHow to remove the front panel Knockout procedureKnockout of Pipe Cover Projection margin in flaring B Unit mm Flaring Refrigerant PipingPipe Forming/End Positioning Flaring size a Unit mmDo not apply refrigerating machine oil to the flared surface Tightening of Connecting PartAir Purge EvacuatingVacuum pump Evacuating How to open the valveElectrical Work SM560AT-E How to remove the valve coverHow to wire Stripping length power cord and connecting cableCheck and Test Operation Final Installation ChecksSelf-Diagnosis by LED Indication New tools for R410A Changes in the product and componentsPrecautions for Safety Accessory and Installation Parts SP1100AT-E, SP1400AT-E SP1100AT-E, SP1400AT-E onlyLength of refrigerant pipe SM1100AT-E, SM1400AT-E Single unitIn installation Moreor Liquid side Gas side Outer diameter Thickness Ø9.5 Ø15.9 Rigid Clutch type Projection margin in flaring B Unit mmValve at gas side Evacuating How to open the valve Model RAV SM1400AT-E Useful Functions Final Installation Checks

RAV-SP1100UT-E, RAV-SP800AT-E, RAV-SP1100AT-E, RAV-SP1400UT-E, RAV-SP560AT-E specifications

Toshiba has consistently been at the forefront of advancing air conditioning technologies, and its line of products, including the RAV-SP1100AT-E, RAV-SP1100UT-E, RAV-SP1400UT-E, RAV-SP800AT-E, and RAV-SP560AT-E, exemplifies this commitment to quality and innovation. These models reflect Toshiba’s dedication to energy efficiency, user comfort, and technological sophistication.

The RAV-SP1100AT-E and RAV-SP1100UT-E are notable for their robust cooling capacities, making them ideal for medium to large spaces. With energy efficiency ratings that comply with global standards, these units help reduce electricity costs while maintaining optimal indoor temperatures. Both models feature advanced inverter technology, which allows for precise cooling and heating control. This technology not only ensures energy savings but also supports quieter operation, enhancing the overall comfort of the environment.

The RAV-SP1400UT-E stands out for its high-performance capabilities, designed to provide efficient climate control even under extreme conditions. This model integrates cutting-edge refrigerant technology, which minimizes environmental impact without compromising on performance. The RAV-SP1400UT-E offers advanced air purification systems that help eliminate dust and allergens, contributing to improved indoor air quality.

For those seeking compact yet powerful solutions, the RAV-SP800AT-E and RAV-SP560AT-E models are excellent choices. They are designed for smaller spaces without sacrificing efficiency. These units are equipped with compact designs that make installation straightforward, while still incorporating Toshiba’s inverter technology, allowing for both heating and cooling functions that adapt seamlessly to changing weather patterns.

All these models support advanced connectivity options, enabling users to monitor and control their units remotely through smart devices. This feature adds convenience and flexibility, allowing for greater energy management and comfort personalization.

In conclusion, Toshiba’s RAV-SP series embodies a blend of energy efficiency, advanced technology, and user-friendly features. These models not only cater to various cooling and heating needs but also prioritize environmental responsibility. With their ability to provide reliable performance across a range of conditions, Toshiba’s RAV-SP1100AT-E, RAV-SP1100UT-E, RAV-SP1400UT-E, RAV-SP800AT-E, and RAV-SP560AT-E stand out as exemplary choices for residential and commercial climate control solutions.